Reproduction of and changes to the manual are permitted only by agreement and with the permission of the manufacturer! Fischer Panda GmbH, 33104 Paderborn, reserves all rights regarding text and graphics in this document. Details are given to the best of our knowledge. No liability is accepted for correctness. Please note: technical modifications aimed at improving the product may be implemented without prior notice.
1.1 Download Weitere verfügbare Sprachen dieses Handbuches können unter dem unten angegebenen Link heruntergeladen werden. Other available languages of this manual can be downloaded under the link below. Vous trouvez d’autres langues disponibles de ce manuel en suivant le lien ci-dessous: Otros idiomas disponibles en este manual se pueden descargar en el link de abajo: ...
Environmental specifications, physical data of the fpControl MM-3..... 14 Installation............................14 2.2.1 Installation of the Electronic Control Unit (ECU) fpControl - GC-S ........14 2.2.2 Installation of the Connection Box fpControl - CB-G ............14 2.2.3 Installation of the fpControl - CP-G .................
Page 6
Table of Contents 2.5.2.7 Setting the Temperature Unit ................34 2.5.2.8 Setting the Aural Alarm ..................34 2.5.2.9 Setting the display to flash in the event of a fault ..........34 2.5.2.10 Setting the Panel Heating..................35 2.5.2.11 Setting the display of the optional measurement data ........
This applies in particular to systems with an automatic start- up function. The automatic start-up function shall be deactivated before starting work. The flooding valve must be closed. (For PMS version only.) 27.5.20 Chapter 1: Panda fpControl Safety Instructions - Page 7...
The fpControl system is intended for the operation, monitoring and control of piston-powered generators. 1.4 Proper use Intended exclusively for use with Fischer Panda generators, the proper use of which arises from the declaration of conformity of the complete machine.
(Control Panel – Generator) Display and Control Element of the fpControl Fig. 2.1.1-1: Control Panel - Generator The fpControl CP-G is the display and control element Power is supplied via the bus cable. Multiple control elements can be installed in a single system.
The fpControl GC-S is suitable for 12 V and 24 V starting systems. The connected actuators are supplied with power via switching outputs with input voltage. Current measurement is single-phase and can be done directly. A voltage sensor is not necessary. Current measurement takes place via an external current sensor.
FP part number 0000306 Circuit board FP1801 2.1.4 fpControl CAN Interface - SAE J1939 (fpControl CI-SAE J1939) The »fpControl CAN Interface - SAE J1939« manages the Fig. 2.1.4-1: fpControl CAN Interface - SAE J1939 communication between the »fpCAN« and an external SAE J1939-CAN-BUS.
(FP CAN BUS 2) 1 x 4-pole Phoenix contact socket Alternative for the external fpCAN (USER CAN BUS) 2.1.4.2 Environmental specifications, physical data of the fpControl CI-SAE J1939 Storage temperature -30 °C – +60 °C Operating temperature -20 °C – +50 °C Supply voltage 12 V or 24 V, automotive (12–13,5 V or 24–28 V)
The measuring range is 65 A per phase. Higher currents can be measured by means of optional external current sensors. Figure: »fpControl Measurement Unit - MM-3« (fpControl MM-3) - Circuit board Figure: »fpControl Measurement Unit - MM-3« (fpControl MM-3) in housing...
2.2.3 Installation of the fpControl - CP-G The fpContol - CP-G is a CAN Bus module. All Fischer Panda CAN bus modules have two RJ45 ports. One for connection to the module on the CAN bus, the second to relay the CAN bus. The last module on the CAN bus must have a terminating resistor in the RJ45 port.
Fig. 2.2-1: fpControl CP-G rear RJ45 Fig. 2.2-2: Connection Diagram 2.3 Operation The fpControl is operated by means of the fpControl CP-G panel. Fig. 2.3-1: fpControl CP-G front with buttons 2.3.1 Switching on the generator Press the "ON/OFF" button to switch on the control Fig.
The “Autostart” also remains active, if the fpControl CP-G is switched off and on again. If a fault should arise when the generator is started or is already operating, it is stopped and the Autostart is set to "off".
Overview Page 1 is the same in all languages. Overview Page 2 (Generator): Fig. 2.3.2-2: Overview Page 2 Symbols/English 06. Output voltage [V] 07. Generator current [A] 08. Generator apparent power [kVA] 27.5.20 Chapter 2: Panda fpControl - Page 17...
Page 18
Fig. 2.3.2-4: Voltage display 3-P Symbols/English/ Overview Page 4: Fig. 2.3.2-5: Overview Page 3 Symbols/English 09. Frequency of the generator [Hz] 10. Generator speed (r.p.m.) 11. Voltage of the starter battery [V] Page 18 - Chapter 2: Panda fpControl 27.5.20...
Page 19
Panel menu. Final Overview Page: Fig. 2.3.2-7: Final overview page Proceed to this menu by pressing the Start/Stop - Enter key Overview Page 5 is the same in all display modes/languages. 27.5.20 Chapter 2: Panda fpControl - Page 19...
Panda fpControl 2.3.3 The fpControl AGT overview pages The display mode/language of the display can be set in the menu. The battery-specific charging parameters are set by the Warning: Fischer Panda Service Point. When exchanging a battery this must be checked and adjusted accordingly.
Page 21
If the information pages of optional components (e.g. fuel Note: gauge, oil pressure) are available, then these pages are inserted after Overview Page 4. Whether these pages are displayed automatically, always or 27.5.20 Chapter 2: Panda fpControl - Page 21...
(back to Standby). Activation of the battery monitor as well as the storage of individual parameters for UIU charging/the connected battery bank are performed by your Fischer Panda Service Point. 2.3.3.2 Functional description of the UIU charging process Fig.
Page 23
Once the float time has elapsed, the generator is stopped automatically if float-timeout [min] float the battery guard is activated. The graphic display of the UIU charging curve displays the NOTE: basic principle and symbolises the functionality. 27.5.20 Chapter 2: Panda fpControl - Page 23...
Panda fpControl 2.3.4 The fpControl Inverter overview pages The display mode/language of the display can be set in the menu. AC Out Fischer Panda Inverter Generator Overview Page 1: Fig. 2.3.4-1: Symbols used in Overview Page 1 01. Generator Status (on/off) 02.
Page 25
Example of the voltage display of a 3-phase generator. Fig. 2.3.4-4: Voltage display 3-P Symbols/English/ Overview Page 3: Fig. 2.3.4-5: Overview Page 3 Symbols/English 09. Phase/Phase voltage 10. Generator apparent power [kVA] 11. Power Factor 27.5.20 Chapter 2: Panda fpControl - Page 25...
Page 26
If the information pages of optional components (e.g. fuel Note: gauge, oil pressure) are available, then these pages are inserted after Overview Page 4. Whether these pages are displayed automatically, always or Page 26 - Chapter 2: Panda fpControl 27.5.20...
Page 27
Panel menu. Final Overview Page: Fig. 2.3.4-9: Final overview page Proceed to this menu by pressing the Start/Stop - Enter key Overview Page 5 is the same in all display modes/languages. 27.5.20 Chapter 2: Panda fpControl - Page 27...
The generator should only be started without a load. 5. Open fuel valve, if installed. 6. Close main battery switch (switch on). 7. Open the raw water intake valve (only in the case of Fischer Panda Marine generators) Page 28 - Chapter 2: Panda fpControl...
2. Press the Start/Stop - Enter key Fig. 2.4.3-2: Start the generator. 3. The fpControl preheats the diesel engine. Fig. 2.4.3-3: Preheating After preheating, the generator is started by the fpControl system. 4. Starter on. Fig. 2.4.3-4: Electric starter In order to minimise current consumption, preheating is interrupted briefly when the starter is operated.
The engine idles for the first few seconds. Thereafter, the Fig. 2.4.3-6: Increase revolutions fpControl increases the speed to the operating speed and indicates this in the display. As soon as the AC voltage is within limits (e.g. 207 V-253 V Fig.
2. "Generator" sub-menu - All settings related to the generator can be made in the "Generator" sub-menu, e.g. bleeding the fuel pump etc. 3. The "Service" sub-menu is blocked and can only be accessed by trained personnel and Fischer Panda employees.
Fig. 2.5.2.2-1: Sub-menu: Contrast keys and the setting is confirmed with the "Start/Stop-Enter“ key. "Cancel" or "Confirm" can be selected by using the "Step-up"/ "Step-down" keys and then confirmed with the "Start/Stop- Enter“ key. Page 32 - Chapter 2: Panda fpControl 27.5.20...
2.5.2.6 Setting the language of the text pages of the CP-G The menu item is selected by using the "Step-up"/"Step-down" keys and confirmed with the "Start/Stop-Enter“ key. The respective menu item opens. 27.5.20 Chapter 2: Panda fpControl - Page 33...
2.5.2.9 Setting the display to flash in the event of a fault The menu item is selected by using the "Step-up"/"Step-down" keys and confirmed with the "Start/Stop-Enter“ key. The respective menu item opens. Page 34 - Chapter 2: Panda fpControl 27.5.20...
This menu item is only available in the case of inverter Fig. 2.5.2.12-1: Note generators The menu item is selected by using the "Step-up"/"Step-down" keys and confirmed with the "Start/Stop-Enter“ key. The respective menu item opens. 27.5.20 Chapter 2: Panda fpControl - Page 35...
- resets the service interval 7. Reset to standard - all parameters of the "Generator" sub-menu are reset to the factory settings 8. back - Switching from the "Generator" sub-menu to the Main Menu Page 36 - Chapter 2: Panda fpControl 27.5.20...
The "Autostart" also remains active if the fpControl CP-G is switched off and then on again. If a fault should arise when the generator is started or is already operating, it is stopped and the Autostart is set to "off".
The menu item is selected by using the "Step-up"/"Step-down" keys and confirmed with the "Start/Stop-Enter“ key. The respective menu item opens. Siehe “Table of Faults” auf Seite 41. Siehe “Description of the symbols” auf Seite 43. Page 38 - Chapter 2: Panda fpControl 27.5.20...
8. Press the Start/Stop-Enter key to access the "Language Selection" sub-menu. 9. Scroll to the desired language and confirm with the "Start/Stop-Enter" key. 10.Scroll down to the "confirm" menu item and press the "Start/Stop-Enter" key. 27.5.20 Chapter 2: Panda fpControl - Page 39...
2.6 Faults 2.6.1 Symbols and messages on the display 2.6.1.1 Example of message - "Sensor defective" A soon as a defective sensor is detected, the fpControl Fig. 2.6.1.1-1: Sensor defective reports this on the display. 2.6.1.2 Example of message - "Sensor/Cable break"...
Winding temperature sensor not available/Contact open/Cable break Exhaust temperature Exhaust temperature sensor not available/Contact open/Cable break Electronics temperature Temperature sensor for the electronic system (sensor on the fpControl circuit board) not available/defective Starter motor current Starter motor not connected/Starter motor defective...
Page 42
Communication with the external motor controller (ECU) has been interrupted communication Air filter Air filter has generated an error message Diagnostic message (ECU) Control device of the diesel engine has transmitted a diagnostic warning Page 42 - Chapter 2: Panda fpControl 27.5.20...
Generator output Faults No contact Voltage Generator output Broken Short circuit (%)/Load Generator runs AC Voltage Generator off Run-up phase/Over- Generator start-up Temperature ride Standby Engine Automatic start-up. Exhaust system Starter battery Winding 27.5.20 Chapter 2: Panda fpControl - Page 43...