Ascon Tecnologic S.r.l. a socio unico
via Indipendenza 56,
27029 - Vigevano (PV)
Tel.: +39 0381 69871,
Fax: +39 0381 698730
www.ascontecnologic.com
E
General description
20
19 10
21
1
17
16
18
DIN RAIL 35 x 7.5 (EN50022);
1
2
X1: 2 poles plug to connect the power supply;
3
X2: 5 poles plug to connect DI5... DI8 High Voltage Digital Inputs;
X3: 4 poles plug to connect OP9... OP11 SPST-NO 5 A output relays;
4
5
X4: 6 poles plug to connect DI1... DI4 Digital Inputs;
X5: 5 poles plug to connect OP4, OP5 (SPST-NO 5 A) and OP6 (SPDT 8 A)
6
output relays;
X6: 5 poles plug to connect AO1... AO4 analogue outputs (0/4... 20 mA,
7
PWM and Hz);
8
X7: 5 poles plug to connect CN1... CN4 High speed Digital Inputs;
9
X8: 10 poles plug to connect AI1... AI4 Analogue Inputs (mA, TC, PT100,
PT1000, NTC)
X10: USB type A receptacle to connect a flash drive;
10
11
X11: RJ45 plug to connect the Ethernet TCP/IP network for programming
purposes or for the MODBUS through the TCP port;
12
X12: 3 poles plug to connect COM1 serial port (RS485);
-
4 mswitches to configure the serial port parameters;
13
14
-
Reset button;
15
-
Status/diagnostic LEDs: COM1 (green, COM1 traffic), USB (white, USB
activity), MSG (red, message), RUN (green, program status run/stop),
PWR (blue, power supply ON);
16
X13: 3 poles plug to connect OP3 (SPDT 16 A) output relay;
X14: 3 poles plug to connect OP2 (SPDT 16 A or SPST-NO 30 A) output relay;
17
18
X15: 3 poles plug to connect OP1 (SPDT 16 A or SPST-NO 30 A) output relay;
X16: 4 poles plug to connect OP14... OP16 SPST-NO 5 A output relays;
19
20
X17: 4 poles plug to connect OP12... OP13 (SPST-NO 5 A output relays or
12 V outputs for SSR drives or 4 A/250 Vdc SSR outputs);
X18: 4 poles plug to connect OP7... OP8 (SPST-NO 5 A output relays or 12 V
21
outputs for SSR drives or 4 A/250 Vdc SSR outputs).
Disposal
The appliance (or the
product) must be
disposed of separately in
compliance with the local
standards in force on
waste disposal.
SAT1
mod.
24/02 - Code: ISTR_I_SAT1_E_01_--
Installation
Manual
Contents
- General description
- Accessories
- Installation
- Electrical connections
- Electric safety
11
6
5
4
3
2
24 Vdc Power supply
APS2ALEDR12024 (120 W, 5.0 A),
APS2ALNDR75-24 (75 W, 3.2 A),
APS2ALMDR20-24 (20 W, 1.0 A)
Integrated system,
CPU module
with on-board I/O
SAT1
model
Dimensions (mm)
15
14
1
X5
1
X4
1
X12
13
12
7
1
X8
8
X2
1
X1
203
9
Mounting position
- Mount the module vertically;
- In order to help the ventilation flow
of air, respect the distances betwe-
en modules and walls or other
modules.
Mounting position (mm)
min. 80
Accessories
Screw Terminal Blocks
KIT_SAT1_00
Installation
Operating conditions
Environmental condition
T
Operating
conditions
%Rh
T
Special
%Rh
conditions
70
P
C
Forbidden
conditions
E
Mounting/removing the modules
on/from the DIN rail
Mounting the module
1
min. 60
55
1
Clip the upper part of the module to
the rail;
2
Rotate the module downwards until
the lower hook engages the DIN rail;
min. 100
Removing the module
3
Switch OFF the Power Supply
With two fingers, press in the area
indicated by the arrow until the
hook is freed from the DIN guide;
4
Turn and lift the module upwards to
remove the CPU from the DIN rail.
Suggestion
B
Temperature
0...+50°C
Umidity:
5... 95% Rh non
condensing
Use forced
Temperature
> 50°C
ventilation
> 95% RH
Warm up
Conducting
Use filter
atmosphere
Corrosive
atmosphere
Explosive
atmosphere
2
4
3
Need help?
Do you have a question about the D2 Series and is the answer not in the manual?
Questions and answers