How to Replace the Battery ..............................14 Dimensional Drawings ................................17 Bottom Mount ................................... 17 All-Angle Mount ................................. 17 Return for Calibration Service..............................18 Thank you for purchasing a Wahl Digi-Stem® DSPG Advanced Digital Pressure Gauge. We appreciate your business. 2 of 18...
Manufacturer. In addition, if the product is tampered with in any way or calibrated in any way other than by the instructions supplied by Palmer Wahl, it will immediately void the warranty. No agent is authorized to assume, for the manufacturer, any liability except as set forth above. Freight cost to return item(s) for evaluation, duties and other fees are not covered by the manufacturer.
Instrument Disposal Disposal of old instruments should be handled according to professional and environmental regulations of your area for electronic waste. Includes Wahl Digi-Stem® DSPG Advanced Digital Pressure Gauges comes with: • 1 - DSPG Precision Pressure Gauge Assembly •...
DSPG Advanced Digital Pressure Gauge Available Ranges RoHS The Wahl Digi-Stem® DSPG Advanced Digital Pressure Gauge conforms to RoHS requirements according to EU Directive (EU) 2015/863- amending Annex II to Directive 2011/65/EU for restriction of Hazardous substances. 6 of 18...
Unpacking & Inspection If you have any questions about the shipment, please call our Customer Service Department at 1-800-421-2853 or 828- 658-3131. We can also be reached online at www.palmerwahl.com, or by email to info@palmerwahl.com. Display and Keypad Info 7 of 18...
Status Battery 24VDC Transmitter Data Logger Switch (Relay) Menu Unit Refresh Clock 2nd Display Alarm Settings Calibration Info Display Readings Options Unit • • ▲▼: • Bar / mbar Choose Unit of • Pa / kPa / MPa Measure • kg/cm2 •...
Page 9
Clock – Date • ▲▼: Choose Value • ► Move between MM, MM-DD-YYYY DD, YY Example: 05/17/2023 • MENU key: Select and Exit Clock – Time • ▲▼: Choose Value • ► HH-MM-SS Example: 16/35/20 Move between HH, MM, SS •...
Page 10
Alarm - Low • ▲▼: Alarm – Choose Value Low Point • MENU key: Select and Exit • ▲▼: Choose Value Alarm – Low Point • ► Move between Digits • Setting MENU key: Select and Exit Visual Alarm – Blue Blacklight Low Point 10 of 18...
Page 11
Alarm - High • ▲▼: Alarm – Choose Value High Point • MENU key: Select and Exit Alarm – • ▲▼: High Point Choose Value • MENU key: Select and Exit Setting Visual Alarm – Red Blacklight Low Point Damping Rate (Pressure) •...
Page 12
Transmitter Range – Low Limit outL • ▲▼: Choose Value • ► Move between Digits • MENU key: Save and Exit Transmitter Range – High Limit outH • ▲▼: Choose Value • ► Move between Digits • MENU key: Save and Exit Analog Output Type O typ •...
Each wire is labeled individually with its purpose. How to Replace the Battery Replace battery only with a C size, Lithium Thionyl Chloride battery, 3.6 V, 8.5 Ah Capacity (Palmer Wahl PN: DSA3062). DO NOT USE ALKALINE BATTERIES. When the battery status indicator shows low battery, replace the battery by first removing the 4 screws and lock washers on the corners of the case with Philips head screwdriver.
Page 15
Lift the case cover up carefully. When the PC Board is exposed, hold down the board gently while pulling the battery out of the holder. Place the new battery in the holder and snap into place. 15 of 18...
Page 16
When the new battery is connected the board will cycle through red, blue and green lights. Gently replace the case cover and insert the screws with the lock washers back into place. 16 of 18...
Standards used have a test ratio of four times greater than the unit being calibrated. We can perform certified, traceable calibrations in support of companies that require meeting FAA and FDA quality standards. Palmer Wahl Instruments, Inc. 234 Old Weaverville Road Asheville, NC 28804 Phone: 800-421-2853 •...