General Description
The products listed above are micro-PLC+HMIs, rugged programmable logic controllers that comprise
built-in operating panels.
Detailed Installation Guides containing the I/O wiring diagrams for these models, technical specifications,
and additional documentation are located in the Technical Library in the Unitronics website:
https://unitronicsplc.com/support-technical-library/
Alert Symbols and General Restrictions
When any of the following symbols appear, read the associated information carefully.
Symbol
Meaning
Danger
Warning
Caution
Caution
▪ Before using this product, the user must read and understand this document.
▪ All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
▪ Please dispose of this product according to local and national standards and regulations.
▪ Only qualified service personnel should open this device or carry out repairs.
▪ Failure to comply with appropriate safety guidelines can cause severe injury or property
damage.
▪ Do not attempt to use this device with parameters that exceed permissible levels.
▪ To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
▪ Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration, in
accordance with the standards given in the product's technical specification sheet.
▪ Do not place in water or let water leak onto the unit.
▪ Do not allow debris to fall inside the unit during installation.
▪ Ventilation: 10mm space required between controller's top/bottom edges & enclosure walls.
▪ Install at maximum distance from high-voltage cables and power equipment.
Unitronics
6 Digital Inputs including 2 HSC,
4 Transistor Outputs
6 Digital Inputs including 2 HSC, 2 Analog/Digital Inputs,
2 Analog Inputs, 8 Transistor Outputs
6 Digital Inputs including 3 HSC/Shaft-encoder,
2 Analog/Digital Inputs, 2 Analog Inputs,
10 Transistor Outputs
Description
The identified danger causes physical and property damage.
The identified danger could cause physical and property damage.
Use caution.
User Guide
1

Advertisement

Table of Contents
loading

Summary of Contents for Jazz JZ20-T10

  • Page 1 ® Jazz User Guide ▪ 6 Digital Inputs including 2 HSC, JZ20-T10/JZ20-J-T10 4 Transistor Outputs ▪ 6 Digital Inputs including 2 HSC, 2 Analog/Digital Inputs, JZ20-T18/JZ20-J-T18 2 Analog Inputs, 8 Transistor Outputs JZ20-J-T20HS ▪ 6 Digital Inputs including 3 HSC/Shaft-encoder,...
  • Page 2: View Area

    Installation Guide Mounting Note that figures are for illustrative purposes only. Dimensions * * Note that for JZ20-J modules those dimensions are 7.5 mm (0.295”). Model Cut-out View area 117 x 89mm (4.606”x 3.504”) 66 x 19.2mm (2.598”x 0.755”) JZ20-xxx\JZ20-J-xxx Add-on modules- Integral USB Port Available by separate order for...
  • Page 3: Wiring Procedure

    JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS Wiring ▪ Do not touch live wires. ▪ This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power environments. ▪ All power supplies in the system must include double insulation. Power supply outputs must be rated as SELV/PELV/Class 2/Limited Power. ▪...
  • Page 4 Installation Guide UL Compliance The following section is relevant to Unitronics’ products that are listed with the UL. The following models: JZ20-R10,JZ20-J-R10,JZ20-R16,JZ20-J-R16,JZ20-J-R16HS, JZ20-R31, JZ20-J-R31,JZ20-J-R31L,JZ20-T10,JZ20-J-T10,JZ20-T18,JZ20-J-T18,JZ20-J-T20HS,JZ20-T40, JZ20-J-T40,JZ20-UA24, JZ20-J-UA24, JZ20-UN20,JZ20-J-UN20, JZ20-J-ZK2. are UL listed for Ordinary Location. UL Ordinary Location In order to meet the UL ordinary location standard, panel-mount this device on the flat surface of Type 1...
  • Page 5 All the products comprise I0-I5; these digital inputs are arranged in a single group. Via wiring, the entire group may be set to either pnp or npn. The following information concerns JZ20-T10/JZ20-J-T10 and JZ20-T18/JZ20-J-T18: I0 and I1 can function as high-speed counters or as normal digital inputs.
  • Page 6 Installation Guide JZ20-T18/JZ20-J-T18 Note: The inputs are arranged in two groups. You can wire one group as npn and the other as pnp, or wire both groups as npn, or as pnp. In either case, the n/p pins must be connected. Input wiring (I0-I7), npn (sink) Input wiring (I0-I7), pnp (source) Input wiring, (I0-I5), pnp (source), (I6-I7), npn (sink)
  • Page 7 JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS HSC input wiring, npn (sink) HSC input wiring, pnp (source) Shaft-encoder wiring, npn (sink) Shaft-encoder wiring, pnp (source) Digital Outputs, Outputs’ Power Supply JZ20-T18/JZ20-J-T18 JZ20-T10/JZ20-J-T10 JZ20-J-T20HS Unitronics...
  • Page 8: Analog Inputs

    Installation Guide Analog inputs Note: Shields should be connected at the signal source. Analog Input wiring, current (JZ20-T18/JZ20-J-T18/JZ20-J-T20HS only) 4-wire,(AN0-AN1) 2 or 3-wire,(AN0-AN1) Analog Input wiring, voltage Note: If either I6 or I7 is wired as an npn digital input, the remaining input may not be wired as an analog input.
  • Page 9: Technical Specifications

    If 1 input is wired as npn, the other may not be wired as analog. Only in JZ20-T10/JZ20-J-T10 and JZ20-T18/JZ20-J-T18: • I0 and I1 can each function as either a high-speed counter or as a normal digital input.
  • Page 10 If I0, I1, I4 are set as high-speed counters (without reset), I2, I3, I5 can function as normal digital inputs. • When used as a normal digital input, normal input specifications apply. Source Digital Outputs Number of outputs JZ20-T10/JZ20-J-T10 JZ20-T18/JZ20-J-T18/JZ20-J-T20HS 4 pnp (source) 8 pnp (source) Output type P-MOSFET (open drain)
  • Page 11 JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS Resolution 10 or 12-bit (0 to 4095) (Via Software) Conversion time All analog inputs are updated every 8 PLC scans, regardless of how many inputs are actually configured.  2% Precision Yes – if an analog input deviates above the permissible range, its Status indication value will be 4096.
  • Page 12 Installation Guide Notes: The JZ20 built-in USB port may be used for programming. Add-on Modules are available by separate order for communication and cloning. Note that the USB port and an Add-on module cannot be physically connected at the same time. Add-on module JZ-PRG, with 6-wires communication cable (supplied in PRG kit –...

This manual is also suitable for:

Jz20-j-t10Jz20-t18Jz20-j-t18Jz20-j-t20hs

Table of Contents