  • Page 1 USER MANUAL For Central Battery Systems - INV220V Series...
  • Page 2: Table Of Contents

    Table of Contents Part 1 : Overview Central Battery Systems Page Features Technical Specifications Indicators Electrical Connector Part 2 : Installation and Operation Battery Connection Steps for Connecting the Input and Output Device Initialization 10-11 Testing the Unit’s Operability Part 3 : Maintenance Device Maintenance Initial Trouble Shooting Important Note on Using the Unit...
  • Page 3 Part 1 Overview Central Battery Systems...
  • Page 4: Features

    คุ ณ สมบั ต ิ ท ั ่ ว ไป 1.1 Features Central Battery Systems by Inverter 220V is used to detect any abnormalities of the main power distribution system. In case of error or emergency, the unit will convert the battery voltage stored in the chemical form into the electric power and supply it to the inverter where the DC voltage from the battery will be converted into the AC voltage at 220VAC 50Hz to turn on the emergency light.
  • Page 5: Technical Specifications

    1.2 Technical Specifications Model INV220 Series Rated Capacity 1000 1200 1500 2000 2500 3000 4000 (Wattage) Mode of Operations Maintained and Non - Maintained Voltage 220 -240VAC Input Frequency 50Hz Voltage AC220V ± 2% (Battery Mode) Output Frequency 50Hz ± 1%...
  • Page 6: Indicators

    1.3 Indicators Symbol Description AC. VOLTMETER Indicating the input and output voltage. DC.VOLTMETER Indicating the battery voltage. LED AC. Input Indicating the status of the input voltage of 220-240VAC. LED DC. Input Indicating the status of the battery power into the device. LED Operate Indicating the operation status of the inverter unit.
  • Page 7: Electrical Connector

    1.4 Electrical Connector Symbol Description Terminal for connecting power to the device AC.INPUT 220VAC MAINTAINED Terminal Maintained for Continuous Power Supply Mode NON - MAINTAINED Terminal Non-Maintained for Use in Emergency Power Supply Mode BATT AC.INPUT 220VAC MAINTAINED NON-MAINTAINED Symbol Description BATT Circuit Breaker for Battery Operation On/Off...
  • Page 8: Part 2 : Installation And Operation

    Part 2 Installation and Operation...
  • Page 9: Battery Connection

    2.1 Battery Connection Since the inverter operates at a voltage of 24 Volts and 48 Volts, for maximum efficiency the batteries are connected together to increase its voltage from 12 Volts to 24 and 48 Volts as shown in the diagram connecting the battery with the battery in the box connecting the positive (+) and negative (-) cables correctly.
  • Page 10: Steps For Connecting The Input And Output

    2.2 Steps for Connecting the Input and Output 1.) Test the readiness of the output load, for example, check for any short-circuits or if the total wattage exceeds the acceptable load. (Caution: The Output Line and Neutral circuit should be independent from other circuits otherwise damage could occur to the inverter.) 2.) When connecting to the Load Output in the circuit box there will be 2 outputs to choose from, which are 2.1 Output Maintained.
  • Page 11: Device Initialization

    2.3 Device Initialization 1.) Turn on the Circuit Breaker BATT and the Circuit Breaker AC INPUT 220VAC (as indicated by the red frame). The device will begin charging the battery and enter a ready-to-use state. The front of the device will display the following status: BATT AC.INPUT 220VAC MAINTAINED...
  • Page 12 2.) Set the Breaker AC.Input 220VAC to Off, the inverter will start operation as the same time set the Breaker MAINTAINED, NON-MAINTAINED to On (shown in the red marking), the unit should now be providing power to the load. BATT AC.INPUT 220VAC MAINTAINED NON-MAINTAINED...
  • Page 13 3.) Test to see if the overall current level and load stability is at a normal level. 4.) Set the Breaker AC.Input to ON (shown in the red marking), after the unit should stop using the inverter and use the main power supply to provide power instead. BATT AC.INPUT 220VAC MAINTAINED...
  • Page 14: Testing The Unit's Operability

    2.4 Testing the Unit’s Operability 1.) To test the unit, the user can set the Circuit Breaker AC Input 220VAC to OFF (shown in the red markings), the unit should start providing backup power to the emergency lights immediately. BATT AC.INPUT 220VAC MAINTAINED NON-MAINTAINED...
  • Page 15 4.) If during the self-tests the battery is found to be faulty and cannot hold a charge or less charge that normal the unit will show a “Battery Fail” warning. The display of device operation AC. VOLTMETER Shows the current level at the Input to be about 220-240VAC.
  • Page 16: Part 3 Maintenance

    Part 3 Maintenance...
  • Page 17: Device Maintenance

    การบํ า รุ ง รั ก ษาตั ว เครื ่ อ ง 3.1 Device Maintenance 1.) Keep ventilation fan of the unit clean. 2.) The unit has an Automatic testing system, automatically enabling 30 minute test every 30 days. If your unit does not have a self-test system you should manually test the unit once a month for 30 minutes to make sure the unit is fully operational and to help extend the life of the battery.
  • Page 18: Terms For Warranty And Service

    Part 4 Terms for Warranty and Service...
  • Page 19 การบํ า รุ ง รั ก ษาตั ว เครื ่ อ ง 4.1 Terms for Warranty and Service 1. The Warranty will only be covered if the customer fills in the “warranty registration form” and mail the return part back to the company within 7 days from the day of purchase. If this is not carried out the warranty will be considered void.
  • Page 20 Contact us ISON IMPORT-EXPORT CO., LTD. Head Office 2915-2917 Ladprao Road, Klongjan, Bangkapi, Bangkok 10240 phone 02 378 1034-5 02 370 1672 www.sunnyemergencylight.com © Ison Import-Export Co.,Ltd. All Right Reserved. Specifications subject to change without notice.