Download Print this page
MG MAX Instruction Manual
MG MAX Instruction Manual

MG MAX Instruction Manual

Lighting surge protector for power supply use

Advertisement

Quick Links

INSTRUCTION MANUAL
LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE
(5A; high discharge current capacity)
BEFORE USE ....
Thank you for choosing us. Before use, please check contents of
the package you received as outlined below.
If you have any problems or questions with the product, please
contact our sales office or representatives.
■ PACKAGE INCLUDES:
Lightning surge protector
(body + base socket + surge absorber element) ............... (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
LIMITATION APPLICABLE TO M-RESTER
The M-Rester will protect electronics equipment from damage
caused by lightning by absorbing most of the surge voltages.
However, M-Rester may not be effective against certain
extremely high voltages caused by a direct or almost direct
hit by lightning.
M-Rester must be installed according to this installation /
instruction manual.
GENERAL
■ FUNCTION & FEATURES
• Designed specifically for AC power supplies up to 5 amps
• Discharge current capacity 10000 A
• Absorbs surges only without affecting instrumentation signal
• No power supply interruption even when the surge absorber
is broken
• Relay contact turns ON with surge absorber failure
• Surge absorber element replaceable without power interruption
■ SPECIFICATIONS
MAX-100
Discharge voltage (p-p)
190 V min.
Max. surge voltage*
350 V max.
Leakage current
≤ 1 mA
@150V DC
Response time
Discharge current
Max. load current
Internal series resist.
*The maximum voltage that could pass through M-RESTER. Pro-
tected equipment must be able to withstand this voltage for a very
short time period.
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
BETWEEN LINES
LINE TO
GND
MAX-200
410 V min.
640 V min.
700 V max.
800 V max.
≤ 1 mA
≤ 1 mA
@300V DC
@300 V DC
≤0.01 µsec.
10000 A (8 / 20 µsec.)
5 A
≤ 0.5 Ω including return
MODEL
POINTS OF CAUTION
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the atmos-
phere, install M-RESTER inside proper housing and ventilate it.
• Do not install the M-RESTER where it is subjected to continu-
ous vibration. Do not apply physical impact to the M-RESTER.
• Environmental temperature must be within -10 to +55°C (14
to 131°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■ WIRING
• Remove cables connected to the ground terminals (2 or 7) from
the base socket before insulation test. Otherwise the element
will start discharging at discharge voltage, which can cause
insulation failure. Be sure to return the cables as they were
after the testing is complete.
■ RATED CURRENT
• Be sure that the rated current of protected equipment does
not exceed the maximum load current specification of the
M-RESTER.
• Be sure to install a breaker which matches the current rating
at the power source side of the M-RESTER.
COMPONENT IDENTIFICATION
Body
Specification
Label
Surge Absorber
Failure Indicator Hole
Surge Absorber Element
(model: MEL)
■ FRONT PANEL CONFIGURATION
Surge Absorber
Element
Surge Absorber
Failure Indicator Hole
Model No. Label
for Surge Absorber
Element
Model suffix code of the surge absorber element (model: MEL)
changes according to the line voltage. Use correct model and
suffix code when ordering.
MAX
MAX
Base Socket
M A X
Model No. Label
for Surge Absorber Element
EM-8175 Rev.7
P. 1 / 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the MAX and is the answer not in the manual?

Questions and answers

Summary of Contents for MG MAX

  • Page 1 Surge Absorber Element Discharge voltage (p-p) 190 V min. 410 V min. 640 V min. Surge Absorber Max. surge voltage* 350 V max. 700 V max. 800 V max. Failure Indicator Hole Leakage current ≤ 1 mA ≤ 1 mA ≤...
  • Page 2 ■ WALL MOUNTING Refer to the next drawings. ■ GROUNDING A cross-over wire between M-RESTER and ground or metallic MG CO., LTD. www.mgco.jp EM-8175 Rev.7 P. 2 / 4 5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN...
  • Page 3 BREAKER The model MAX is designed to separate its surge absorber element (model: MEL) from power supply lines when there is anomaly with the element. It ensures no interruption of power supply...
  • Page 4 Terminals (1) – (8), (1) – (7), (7) – (8) • Check that discharging occurs across the same terminals with a 1000 V DC megger. (Indicator of the megger reaches over-scale.) MG CO., LTD. www.mgco.jp EM-8175 Rev.7 P. 4 / 4...