Machine Translated by Google
Security technologies
GS290K GAS DETECTOR WITH RELAY OUTPUT
FEATURES
Standby Loop Current
Alarm Status Loop Current
Operating Voltage
Supply Alarm Current
Working Environment Humidity Level: 10% to 93% Relative Humidity, Non-condensing
Working Environment Temperature: -10°C - 50°C
Opening Preparation Time
Detection Area Volume
Dimensions
GENERAL DESCRIPTIONS
GS290K Gas detector is designed to detect gas leaks in the environment in which it operates.
The detection line and the supply line must be entered into the device separately.
The device detects methane, butane (cylinder gas), propane, LPG and natural gases.
In case of any gas leakage, it detects the leak thanks to the sensor on the device and sends information to the control panel via the
detection line.
Energy, ready, error and alarm on the device
There are 4 LED indicators.
INSTALLATION
The installation of the device should be done according to the type of
gas it will detect. For example, LPG (Liquified Petrolium Gas) is a type
of gas that is heavier than air, so the detector should be mounted 30-40 cm
above the floor.
If it is to detect all gases, the device must be mounted at the
breathing level of an average human.
The device should be installed away from areas where there is no air flow and where
food is cooked.
The gas detector consists of two main parts: a body containing
the electronic card and a hanging bracket for hanging on the
wall. During assembly, the hanging apparatus is first fixed by
passing the cables through it. After the cable connections are
made to the body, the body is attached to the hanging apparatus.
Doc: KK-GS290K-0319-TR
:<600µA @ 24
:<7 mA @ 24 VDC (Led On)
: 12 to 30 VDC
:<50mA @ 24VDC
:max 2 min.
:max 50 m3
:90 x 90 x 38 mm