WIRING DIAGRAM

[LEGEND]
SYMBOL
NAME
I.B
INDOOR CONTROLLER BOARD
CN2L
CONNECTOR (LOSSNAY)
CN32
CONNECTOR (REMOTE SWITCH)
CN41
CONNECTOR (HA TERMINAL-A)
CN51
CONNECTOR (CENTRALLY CONTROL)
CN105
CONNECTOR (IT TERMINAL)
F1
FUSE (T6.3AL250V)
LED1
POWER SUPPLY (I.B)
LED2
POWER SUPPLY (R.B)
LED3
TRANSMISSION (INDOOR-OUTDOOR)
SW1
SWITCH (MODEL SELECTION) Refer to <Table 1>.
SW2
SWITCH (CAPACITY CODE) Refer to <Table 2>.
SWE
SWITCH (EMERGENCY OPERATION)
DP
DRAIN PUMP
FS
DRAIN FLOAT SWITCH
MF
FAN MOTOR
MV
VANE MOTOR
MF
MS
3~
I.B
1
4
+
1
3
BK
TB4
YE
S1
OG
TO
S2
OUTDOOR
OG
UNIT
S3
BN
Notes:
1. Symbols used in wiring diagram on the left are,
,
:Connector.
2. Indoor and outdoor connecting wires are made with polarities, make
wiring matching terminal numbers (S1, S2, S3).
3. Since the outdoor side electric wiring may change be sure to check
the outdoor unit electric wiring for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting
wires (specification of 230V), adopting superimposed system of
power and signal.
● If the separate indoor/outdoor unit power supplied system is
applied, refer to Fig. 2.
● For power supply system of this unit, refer to the caution label
located near this diagram.
5. When installing the automatic filter elevation panel and the 3D Total
Flow Unit together, refer to the wiring diagram of the 3D Total Flow Unit.
Caution when connecting the remote controller cable to the terminal block TB5
<Fig. 1>
Do not connect 230V power supply cable.
Be sure to connect the remote
controller cable (0.3mm
) to the
2
locations shown in diagram
OCH783B
SYMBOL
NAME
TERMINAL BLOCK (INDOOR/OUTDOOR
TB4
CONNECTING LINE)
TERMINAL BLOCK (REMOTE CONTROLLER
TB5,TB6
TRANSMISSION LINE)
ROOM TEMP. THERMISTOR
TH1
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
PIPE TEMP. THERMISTOR/LIQUID
TH2
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
COND. / EVA. TEMP. THERMISTOR
TH5
(0°C / 15kΩ, 25°C / 5. 4kΩ DETECT)
R.B
WIRED REMOTE CONTROLLER
OPTION PART
PCB OF SIGNAL RECEIVER
W.B
BZ
BUZZER
LED1
LED (OPERATION INDICATION : GREEN)
LED2
LED (PREPARATION FOR HEATING : ORANGE)
RU
RECEIVING UNIT
SW1
EMERGENCY OPERATION (HEAT / DOWN)
SW2
EMERGENCY OPERATION (COOL / UP)
MT
i-see Sensor MOTOR
TERMINAL BLOCK (INDOOR UNIT POWER
TB2
AND TRANSMISSION LINE)
DP
MS
TH5
TH2
TH1
3~
FS
7
4
4
1
2
3
1
1
CNP
CN4F
CN44
CN20
CNMF
(WH)
(WH)
(RD)
(WH)
(WH)
1
5
~
CN105
(RD)
~
SWE
F1
LED1
ON OFF
J58
CN01
CN3C (BU)
CN32 (WH)
(BK)
3
5
1
3
1
Cut the J58 when a remote
controller other than
PAR-4*MAA/CT01MAA
is connected.
:Terminal (block),
[Self-diagnosis]
1. For details on how to operate self-diagnosis with the wireless remote controller,refer to the technical manuals etc.
Cable strap
Secure with a
band at the location
shown in the diagram
<Table 1> SW1 (MODEL SELECTION)
Manufacture/Service
1 2 3 4 5 6
ON
OFF
<Table 2> SW2 (CAPACITY CODE)
CAPACITY Manufacture/Service
1 2 3 4 5
35
1 2 3 4 5
50
1 2 3 4 5
60
● AUTOMATIC FILTER
i-see Sensor
ELEVATION PANEL
CORNER PANEL
● 3D Total Flow Unit
(OPTION PART)
(OPTION PART)
M
i-see
Sensor
4
1
CN4G
MT
1
2
1
2
4
1
5
1
5
CN2L
CN41
CN51
(WH) 1
5
(RD)
(WH)
1
4
CN5Y
4
(WH)
1
4
LED3
LED2
1
4
CN4G
(BU)
CN4Z(WH)
CN90(WH)
J57
J52
J41 J42
SW2
SW1
1
9
9
Refer to Table 1 and 2
9
1
LED2 LED1
CNB
SW1
<Fig. 2>
POWER SUPPLY
~(1 PHASE)
230V 50Hz
TO OUTDOOR
UNIT
Check code
Symptom
P1
Abnormality of room temperature thermistor (TH1).
P2
Abnormality of pipe temperature thermistor / Liquid (TH2).
P4
Float switch connector open (FS).
P5
Malfunction of Drain pump.
P6
Freezing / overheating protection is working.
P8
Abnormality of pipe temperature.
Abnormality of pipe temperature
P9
thermistor / Cond. /Eva. (TH5).
PA
Leakage error (refrigerant system)
15
CAPACITY Manufacture/Service
CAPACITY Manufacture/Service
1 2 3 4 5
1 2 3 4 5
ON
71
ON
140
OFF
OFF
1 2 3 4 5
The black square ( ) indicates
ON
100
ON
a switch position.
OFF
OFF
1 2 3 4 5
ON
125
ON
OFF
OFF
MV
MV
MV
MV
M
M
M
M
5
5
5
5
20
20
19
CNV
(WH)
R.B
TB5
2
B
2
1
A
TB6
W.B
SIGNAL RECEIVER
BZ
CORNER PANEL
RU
(OPTION PART)
SW2
RD
TB2
5
CN01
L
BU
3
(BK)
N
BK
1
S2
BU
3
CN3C
S3
GY
(BU)
1
Check code
Symptom
PB(Pb)
Indoor unit fan motor error.
PL
Refrigerant circuit abnormal.
Abnormality of the signal transmission between
E0~E5
remote controller and indoor unit.
Abnormality of the signal transmission between
E6~EF
indoor unit and outdoor unit.
FB(Fb)
Abnormality of indoor controller board.
Abnormality in outdoor unit. Refer to outdoor
U*, F*
unit wiring diagram.