DESCRIPTION AND OPERATING INSTUCTIONS POWERCOM 485 6A | EN 2014...
Page 2
The VAHLE POWERCOM 485 device is a modem for secure data transmission via conductor rails. It can communicate with all PROFIBUS compatible products. It accepts the various protocol variants of the PROFIBUS, and multiple VAHLE ® POWERCOM 485 units can be connected via the conductor rails.
Page 3
VAHLE POWERCOM units can only operate safely and without problems in an EMC suitable environment (see also "EMC-suitable installation and configuration of VAHLE electronic components”).
485 devices regenerate the signal form and ampli- tude of the received data. Note: Due to the complexity and versatility of switching power supplies a custo- mer's check in connection with Vahle - electronic components is recom- mended. 1.1.4 Wiring the conductor rails...
POW ER SIGN AL 1 2 3 4 L L N N PE Xn Xl – A mounting depth of at least 175 mm is required for installing the VAHLE ® POWERCOM COM 485 device in a switch cabinet. – Set up the devices such that adequate space is available for wiring the con- nections.
Page 6
485 device Warning ® If the supply voltage for the VAHLE POWERCOM 485 devices and all con- nected devices is not switched off when installing or removing the devices, this could lead to fatal accidents, severe injuries and/or material damage.
Page 7
Description and operating instuctions ® VAHLE POWERCOM 1.1.7 Mounting a 485 device on a top- hat-rail ® Proceed as follows for mounting a VAHLE POWERCOM 485 device on a top- hat rail: Figure 5 Mounting a VAHLE ® POWERCOM device on a top-hat- rail –...
Page 8
Powercom 485 Description and operating instuctions 1.1.8 Installation the field wiring Observe the following directives when installing and wiring the VAHLE ® POWERCOM 485 device: – Make sure that all valid and mandatory standards are complied with when wi- ®...
Page 9
3. In column 3 (routing ...): read off the routing guidelines to be observed. ® – Mark all lines leading to the VAHLE POWERCOM 485 device. – Provide suitable surge arrestors for all lines which may be exposed to lightning...
Therefore observe the following safety instructions: ® • Do not connect the VAHLE POWERCOM 485 devices via PROFIBUS lines to plant components which are connected to a different ground potential. The voltage differences arising could lead to destruction of the devices! •...
Page 11
® 1. The delay time of the VAHLE POWERCOM 485 devices is 1.5 bit times. 2. The total transmission delay time is given by the number of modules passed through from the transmitter of a telegram to the receiver, multiplied by 1.5 bit...
Page 12
Powercom 485 Description and operating instuctions 3. Please determine the transmission delay times from the respective product do- cumentation for other active PROFIBUS network components. 4. Transmission Delay Time TTD The total delay time is the sum of the values determined in 1., 2. and 3.
Page 13
Powercom 485 Description and operating instuctions 1.1.12 Adjustment of the Retry-Level (Number of repeats at the Profibus transmission) Following steps in the HW Config – Opening of the tab „General” and select properties > „Network settings” tab in the DP Master system.
Vahle documentation for con- ductor rails Vahle RC closures are not cor- Check closures according to rectly connected the Powercom documentation Closures at the profibus cables Check the stationary and mo-...
Injury cause of electric shock! When operating the VAHLE POWERCOM 485 systems, certain parts in the device are necessarily energised. Incorrect handling of this device can lead to fatal accidents, or severe injuries or material damage.
Page 16
Paul Vahle GmbH & Co. KG Westicker Str. 52 59174 Kamen Germany Tel.: +49 2307 704-0 Fax: +49 2307 704-444 info@vahle.de www.vahle.com...