MAYDAY LMW2 Loner Worker Safety System

Specification

The MAYDAY is a lone worker safety system. It is designed to give audible and visual warning to prompt staff to take action
by cancelling a warning after a pre-determined period. Failure to take action will result in a secondary alarm operating after
a further pre-determined period. This is used to raise an alarm to call for assistance which can be either a simple sounder
and visual indicator or a voice message transmitted via a speech dialler (not supplied) via a landline. The two time periods
are separately adjustable. 20 - 60 minutes and 2 - 10 minutes respectively. The MAYDAY is mains powered and supplied with
a rechargeable 12v 0.8Ahr standby battery. The integral 12v power supply will deliver 150ma for ancillary items. The unit is
housed in a plastic enclosure approx. 125w x 175h x 55d (mm).
The MAYDAY has the following integral indications and controls:-
1. An On Off key switch to arm the unit.
2. An OK button to restart the countdown timer and reset the alarm.
3. A green Power On LED.
4. Four red System Active countdown LEDs.
1. 5 . An integral piezo sounder. (85db at 10cm)
5. Two adjustable countdown timer controls. These are fitted internally and only used during the installation set-up.
Five inputs are provided for connecting ancillary devices:
IN1 Remote OK buttons to supplement the front panel OK button. (Normally Open -close to acknowledge OK)
IN2 To arm the MAYDAY from a key switch or other device. (Normally Closed - open to start lone working)
IN3 Input from a movement detector such as a PIR (Normally Closed -open on detection - i.e. OK)
IN4 Input from a speech dialler. (Apply a -ve for OK)
IN5 Timer set-up. This is a divide by 60 facility (eg 57mins= 57sec).
Volt free contacts are provided by three independent relays:
Relay 1 operates when the key switch is thrown to arm the unit.
Relay 2 operates at the end of the first pre-determined run-down delay T1 (20-60 minutes).
Relay 3 (normally on, off when operated) operates at the end of the second pre-determined countdown delay T2
(2-10 minutes).
Eight outputs are provided for remote indications:
LED1 - 4 follow the LEDs on the front panel.
LED5 Remote buzzer, follows internal buzzer.
LED6 Remote LED, all indications.
LED7 Remote LED to indicate T2 has run out.
LED8 Remote power LED.

Timer Set-Up Procedure

With IN2 closed (or key switch OFF), link out IN5, LED's 2 and 4 only illuminate. Set T1 and T2 pots approx. (Best guess).
Press the OK button, the unit bleeps and LEDs 1 and 3 only illuminates for T1 time in seconds. At the end of T1 the unit
bleeps and LEDs 1 and 2 only illuminate for T2 time in seconds. At the end of T2 the unit bleeps and reverts to LEDs 2 and 4
only. Adjust the pots accordingly and repeat until time T1 and T2 minutes are correct as indicated in seconds. Remove the
link IN5 and the unit is set to operate in minutes.
DWG 60108
Hoyles Electronic Developments Ltd
Sandwash Close, Rainford, St Helens, WA11 8LY, UK
www.hoyles.com
sales@hoyles.com
+ 44 (0) 1744 886600

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MAYDAY LMW2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Hoyles MAYDAY LMW2

  • Page 1 MAYDAY LMW2 Loner Worker Safety System Specification The MAYDAY is a lone worker safety system. It is designed to give audible and visual warning to prompt staff to take action by cancelling a warning after a pre-determined period. Failure to take action will result in a secondary alarm operating after a further pre-determined period.
  • Page 2 The notes below will assist in deciding how MAYDAY and ancillary equipment should be used and configured for any situation. The first consideration should be; where are the responders located? Hoyles Electronic Developments Ltd Sandwash Close, Rainford, St Helens, WA11 8LY, UK www.hoyles.com...
  • Page 3 Hoyles Electronic Developments Ltd Sandwash Close, Rainford, St Helens, WA11 8LY, UK www.hoyles.com sales@hoyles.com DWG 60108 + 44 (0) 1744 886600...
  • Page 4 SD1E. When you have recorded the phrase, press ESC. This will stop the timer and the display will again alternate between ENT 1-4 : OR O-D. waiting for you to record the next phrase. Hoyles Electronic Developments Ltd Sandwash Close, Rainford, St Helens, WA11 8LY, UK www.hoyles.com...
  • Page 5 ERASE-. Press B the display should read SPEECH press ENT and the display should revert to ENT 1-4 : OR O-D.. Press ESC to return to READY. All phrases now need to be re-recorded, see 3 above. To erase telephone numbers. (assuming you are in programme mode) Hoyles Electronic Developments Ltd Sandwash Close, Rainford, St Helens, WA11 8LY, UK www.hoyles.com sales@hoyles.com...
  • Page 6 SD1+ wait for 60 seconds or repeatedly press ESC. Other options such as changing the passcode or setting up the BT line as pulse or tone should be done from the SD1+ operating manual. Hoyles Electronic Developments Ltd Sandwash Close, Rainford, St Helens, WA11 8LY, UK www.hoyles.com...

Table of Contents