FAULTY OPERATION AND ITS POSSIBLE DIAGNOSIS
Green LED (POWER) indicator does not light up
AC power failure.
Yellow LED (CHARGE) lights up
Battery during charging process. LED will go off after the battery is full.
Red LED (FAULT) indicator lights up
Battery not connected or damaged.
The luminaire does not operate in emergency mode the required time for a selected model
It is possible that the battery requires a full charge cycle (24h). If after 24 hours of charging the luminaire still does not keep a
predefined autonomy, it is possible that the battery is run-down or damaged due to possible incorrect formatting and needs to be
replaced.
RECOMMENDED PERIODICAL MAINTENANCE
The luminaire should be tested on regular basis in accordance with valid laws and regulations. The results of the tests should be
recorded and stored for the use of a fire safety inspector.
One time daily
It is suggested to check visually if the LED (POWER) indicator in the luminaire lights up in green.
One time each month
It is necessary to perform a function test by disconnecting the AC power supply and checking whether the luminaire is operating in
emergency mode - the green LED indicator should turn off, and LEDs light up.
One time each year
In order to make an autonomy test, disconnect the AC power supply and test if the luminaire operates in emergency mode for a
specified time. If the autonomy time of emergency operation is not sufficient, the battery needs to be fully recharged and the test
is to be carried out again. If the result of the test continues to be negative, the battery needs to be replaced.
CAUTION!
All damage that might occur as a result of the device being used not in accordance to this instruction will result in loss of guarantee.
Used or damaged lamps including batteries, are subject to be recycled. They should be delivered to the point of collection of
electrical and battery waste or to the manufacturer.
The light source contained in this
luminaire shall only be replaced by the
manufacturer or his service agent or a
similar qualified person.
Handling of obsolete equipment
Pursuant to the Act of 29 July 2005 on waste
electrical and electronic equipment and the Act
of 24 April 2009 on batteries and accumulators,
the presented device, after use, due to
hazardous substances contained in it, is subject
to collection of waste electrical and electronic
equipment. Detailed information on WEEE
collection can be obtained from municipal
authorities.
4
Intelight Sp. z o.o.
19, Gwiaździsta str.
01-651 Warsaw, Poland
KTM 97133 - Instruction KASJOPEJA, EN, ver.20221123
OV
TECHNICAL SPECIFICATIONS:
Light source (user non-replaceable):
Operating modes *:
Test versions:
Emergency autonomy *:
Battery (user non-replaceable) *:
Battery charging duration max.:
Power supply *:
Max. power:
Module:
Visibility:
Enclosure IP rating:
Ambient temperature:
*- depending on model
1.
The lamp should be installed when power supply is off. Safety rules, construction and electrical installation standards should
be followed all the time.
2.
The luminaire should not be powered with circuits connected to inductive power-receiving devices at the same time. This type
of solution may cause damage to the electronic module of the luminaire.
3.
The luminaire should be used indoors.
1.
Before installation one has to make sure that the luminaire will be connected to 220-240VAC power supply by the use of a
2
minimum 1,5mm
wire.
2.
Connecting the battery:
- the battery should be already connected;
- if it is not connected, one need to remove housing's plastic end cap from the signal panel's side, then slide off housing's
aluminium cover and insert white battery plug into its socket; after connection one need to slide the housing's cover and the
cap back into their positions.
KASJOPEJA LED EMERGENCY LUMINAIRE
Installation and maintenance instructions
KASJOPEJA LED
White LED
SA (M) - mains and emergency operation or
A (NM) - emergency operation
MT – manual test
1h, 2h or 3h
NiCd or NiMH 3.6V 400mAh ÷ 800 mAh
24h
220-240V AC 50Hz (for MT) or 230V AC / 220V DC (for CB)
2W
Kasjopeja LED
30 metres
IP20
10°C ÷ 40°C
INTRODUCTION
INSTALLATION
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the KASJOPEJA LED and is the answer not in the manual?

Questions and answers

Summary of Contents for Intelight KASJOPEJA LED

  • Page 1 KASJOPEJA LED EMERGENCY LUMINAIRE FAULTY OPERATION AND ITS POSSIBLE DIAGNOSIS Installation and maintenance instructions Green LED (POWER) indicator does not light up AC power failure. Yellow LED (CHARGE) lights up Battery during charging process. LED will go off after the battery is full.
  • Page 2 TESTING KASJOPEJA LED luminaire is equipped with a TEST button, which enables to test emergency operation of the luminaire. MT manual test function When the emergency luminaire is connected to mains and there is no voltage drop, pressing and holding TEST button will result in activation of the “voltage drop”...