Advertisement

Quick Links

Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau | Germany
Support Tel. +49 6441 9642-22
info@janitza.com | www.janitza.com
PowerToStore
Operation Instructions
Art.Nr. 15.06.405

Advertisement

Table of Contents
loading

Summary of Contents for janitza PowerToStore 15.06.405

  • Page 1 PowerToStore Operation Instructions Art.Nr. 15.06.405 Janitza electronics GmbH Vor dem Polstück 6 35633 Lahnau | Germany Support Tel. +49 6441 9642-22 info@janitza.com | www.janitza.com...
  • Page 2: Table Of Contents

    PowerToStore www.janitza.com Content 1. In General 1. 1 Safety regulations 1. 2 Short description 1. 3 Intended use 2. Transportation and storage 3. Installation and connection 3. 1 Dimensions 3. 2 Installation 3. 3 Connection 3. 4 Principle circuit diagram 4.
  • Page 3: In General

    PowerToStore In General The capacitor buffered DC power supply ensures the secure DC supply in case of mains failure. Do not use the device for any other purpose! Before installation respectively use of the power supply, the operation instructions must be read carefully. The general information must be followed.
  • Page 4: Short Description

    PowerToStore www.janitza.com 1.2 Short description The buffered DC power supply of the PowerToStore includes ultra-capacitors as energy storage inside the housing. During normal operation this capacitor is charged from AC-mains. The connected DC consumers are supplied as well from AC mains. In case of an interruption of the AC supply, the energy of the ultra-capacitor is realesed regulated.
  • Page 5: Installation

    PowerToStore 3.2 Installation · The power supply must be installed in the way, that sufficient air cooling is guaranteed. · A minimum distance in the area o fair in- and outlets to neighbouring devices of at least 40 mm must be observed.
  • Page 6: Connection

    PowerToStore www.janitza.com 3.3 Connection · Prior to connection, the values of the DC supply must be compared with the values on the type plate. · Connection according to the designations of the connection terminals (see terminal allocation). · Not used connection screws must be tightened.
  • Page 7: Principle Circuit Diagram

    PowerToStore 3.4 Principle circuit diagram DC-DC- Transformer DC-Transformer LOAD Operation Ue-o.k. 30V DC/ 0.5A Uc> 30V DC/ 0.5A Putting into operation The power supply is switched on by the switch on of the mains voltage (230 V AC). The status-LED Ue-O.k.
  • Page 8: Display And Messages

    PowerToStore www.janitza.com 4.1 Display and messages Inside the housing there are four LED’s for status display: Display Designation Operation LED green illuminates: - if input voltage is present at terminal Ue - as long as the device is supplied internally...
  • Page 9: Back-Up Operation

    PowerToStore 5.3 Back-up operation · With the switch off of the input voltage respectively with the underrun of the minimum input voltage, the PowerToStore switches over in back-up operation. The green LED Ue-OK goes out. If the energy in the capacitor is <30% Uc>...
  • Page 10: Maintenance

    PowerToStore www.janitza.com Maintenance · Inside the housing there are no parts, which should be maintained by the user. · To ensure the back-up capability of the power supply, the units should be tested regularely in inter- vals of 3 to 6 months on their back-up capability.
  • Page 11: Putting Out Of Operation

    PowerToStore Putting out of operation · The putting out of operation is realized by the switch off of the supply voltage. · Subsequently the device buffers the load until the capacitors are discharged. Directly after the dis-charge the voltage-free output is signalized by the illumination of the LED Operation and the fast blinking of the LED Uc>.
  • Page 12: Technical Data

    PowerToStore www.janitza.com 10. Technical Data Input Nominal input voltage 115 V…230 V AC ±15 % Input voltage range for charging operation 97.8 V…264.5 V AC ±0 % Nominal frequency 47 Hz…63 Hz 1.5 A @ 115 V AC Max. nominal input current 0.75 A @ 230 V AC...
  • Page 13 Janitza electronics GmbH Vor dem Polstück 6 | 35633 Lahnau Germany Tel.: +49 6441 - 9642-0 info@janitza.com | www.janitza.com The current status of the document can be found in the download area at www.janitza.com.

Table of Contents