Kilsen CR255 Installation Sheet
Kilsen CR255 Installation Sheet

Kilsen CR255 Installation Sheet

Electronic delay control unit
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

CR255 Electronic Delay Control Unit Installation
Sheet
EN ES
1
EN: Installation Sheet

Description

The CR255 Electronic Delay Control Unit is designed for use
with double-leaf fire doors.

Figures

Figure 1: Wiring
(1) Fire panel
(2) 24 VDC supply line
(3) Normally closed relay input
(4) Immediate release
electromagnet

Installation

Caution:
This product must be installed and maintained by
qualified personnel adhering to EN 54-14 and all local or
national installation requirements and any other applicable
regulations.
Install the unit as close to the fire doors as possible, at a
maximum distance of 200 m from the power supply.
© 2022 Carrier. All rights reserved.
(5) Delayed release
electromagnet
(6) CR255 module

Wiring

Connect the CR255 as shown in Figure 1.

Maintenance

Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.

Specifications

Operating voltage
Maximum current
Delay time
Wire size (cross-sectional area)
Maximum wire length
Operating environment
Operating temperature
Storage temperature
Relative humidity
Dimensions (W × H × D)
Weight
1 / 4
20 to 27 VDC
0.5 A
5 seconds
1.5 mm
2
200 m
–10 to +60°C
–20 to +70°C
0 to 95% noncondensing
40 × 35 × 12 mm
24 g
P/N 10-4109-501-3CR2-07 • ISS 21NOV22

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CR255 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kilsen CR255

  • Page 1 EN: Installation Sheet Connect the CR255 as shown in Figure 1. Description Maintenance The CR255 Electronic Delay Control Unit is designed for use Basic maintenance consists of a yearly inspection. Do not with double-leaf fire doors. modify internal wiring or circuitry.
  • Page 2 Cableado dispose of it at designated collection points. For more information see: recyclethis.info. Conecte el CR255 tal y como se muestra la Figura 1. Mantenimiento Contact information El mantenimiento básico consiste en una inspección anual. No For contact information, visit firesecurityproducts.com.
  • Page 3 Kelvinstraat 7, 6003 DH Weert, Países Bajos. Año de la primera marca CE N.º de Declaración de 360‐5151‐0199 rendimiento EN 54 EN 54-18:2005/AC:2007 Identificación del CR255 producto Consultar la Declaración de rendimiento del Uso previsto producto Rendimiento Consultar la Declaración de rendimiento del declarado producto 2012/19/UE (directiva WEEE): aquellos productos que tengan este símbolo no podrán...
  • Page 4 4 / 4 P/N 10-4109-501-3CR2-07 • ISS 21NOV22...

Table of Contents