Lennox A97DF2E Installation Instructions Manual page 10

Warm air gas furnace downflow air discharge direct vent & non-direct vent
Table of Contents

Advertisement

Figure 11.
Improper installation of the furnace can result in
personal injury or death. Combustion and flue products
must never be allowed to enter the return air system or
air in the living space. Use sheet metal screws and joint
tape to seal return air system to furnace.
In platform installations with furnace return, the furnace
should be sealed airtight to the return air plenum. A door
must never be used as a portion of the return air duct
system. The base must provide a stable support and an
airtight seal to the furnace. Allow absolutely no sagging,
cracks, gaps, etc.
For no reason should return and supply air duct systems
ever be connected to or from other heating devices
such as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Figure 12. Setting Equipment
Page 10 of 52
Units with 1/2 HP
Blower Motor
WARNING
WARNING
The unit may be installed three ways in downflow
applications: on non-combustible flooring, on combustible
flooring using an additive base, or on a reverse-flow
cooling coil cabinet. Do not drag the unit across the floor
in the downflow position. Floor and furnace flange damage
will result.
Refer to Figure 15 for clearances in downflow applications.
Installation on Non-Combustible Flooring
1.
Cut floor opening keeping in mind clearances listed
on unit rating plate. Also keep in mind gas supply
connections, electrical supply, flue and air intake
connections and sufficient installation and servicing
clearances. See Table 1 for correct floor opening size.
2.
Flange warm air plenum and lower the plenum into the
opening.
3.
Set the unit over the plenum and seal the plenum to
the unit.
4.
Ensure that the seal is adequate.
Cabinet Width
B (17.5")
C (21")
NOTE: Floor opening dimensions listed are 1/4" (6 mm) larger
than the unit opening. See dimension drawing on Page 2.
Table 1. Non-Combustible Floor Opening Size
Issue 2327
Figure 13.
Front to Rear
Side to Side
in.
mm
in.
19-3/4
502
16-5/8
19-3/4
502
20-1/8
Figure 14.
mm
422
511
508391-01

Advertisement

Table of Contents
loading

This manual is also suitable for:

97g2dfe

Table of Contents