Introduction
This quick installation guide describes the main steps to follow for successful commissioning of the Copeland™ CO
Scroll refrigeration unit models OME-16T-TEM & OMTE-37/49/64T-TEM. It is not intended to replace the unit's
application guidelines, to explain the functionality of the refrigeration unit or to help optimize the system parameters.
2
First steps
When receiving the unit, please do the following:
✓ Check the integrity of the unit's transport packaging.
✓ Check if the unit is pressurized with 2 bar nitrogen.
✓ For the OME-16T model only, remove the transport bracket from the unit. Please refer to Figure 1 below and
to section 3.6 "Transport bracket" in the unit's application guidelines for more information.
Figure 1: Transport bracket on the OME-16T model
✓ Follow the instructions in the application guidelines when dealing with BOM version OM(T)E-**T-TEM-*-2**
(split/flexible models).
The piping between the unit and the evaporators shall be designed taking into account the design pressures.
If the system piping design pressure (PS) is lower than 90 bar in the liquid line, additional safety devices are required.
An additional safety device in the suction line is required in any case.
The minimum required design pressure (PS) is 80 bar for the liquid line and 60 bar for the suction line. Longer
standstill times of the unit can be achieved by a design pressure of more than 60 bar in the suction line.
TI_Unit_OMTE_CO2_Scroll_06_EN_Rev01
™ CO
S
R
CROLL
2
Q
I
UICK
NSTALLATION
Ref: TI_Unit_OMTE_CO2_Scroll_06_EN_Rev01
Application Engineering Europe
U
EFRIGERATION
NITS
G
UIDE
2
1/9

Advertisement

loading
Need help?

Need help?

Do you have a question about the OME-16T-TEM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Copeland OME-16T-TEM

  • Page 1 UIDE Introduction This quick installation guide describes the main steps to follow for successful commissioning of the Copeland™ CO Scroll refrigeration unit models OME-16T-TEM & OMTE-37/49/64T-TEM. It is not intended to replace the unit’s application guidelines, to explain the functionality of the refrigeration unit or to help optimize the system parameters.
  • Page 2 The piping connection sizes of the Copeland CO Scroll refrigeration units are shown in Table 1 below. Unit Suction line Liquid line OME-16T-TEM 5/8" (15.875 mm) 1/2" (12.07 mm) OMTE-37T-TEM 3/4" (19.05 mm) 5/8" (15.875 mm) OMTE-49T-TEM 7/8" (22.225 mm) 3/4"...
  • Page 3 Enabling the components of the OMTE-37/49/64T models: ✓ Switch on the unit main switch (Q01 - located on the outside of the electrical cabinet cover). ✓ Switch on the circuit breakers for the gas cooler fans (F11 + F12). ✓ Switch on the circuit breaker for the crankcase heater 12 hours before compressor start-up (F2). ✓...
  • Page 4 The shut-off valves (number 6 in Figures 5 & 6 below) in the unit can be used for the tests. Figure 5: P&I diagram of the OME-16T model Figure 6: P&I diagram of the OMTE-37/49/64T models Position Description Position Description Copeland CO scroll compressor High-pressure limiter (variable speed) Copeland CO scroll compressor Compressor inverter...
  • Page 5 Evacuation IMPORTANT The evacuation procedure is based upon achieving an actual system vacuum standard and is NOT TIME DEPENDENT! The installation must be evacuated with a vacuum pump before commissioning. Proper evacuation reduces residual moisture to 50 ppm. The installation of adequately sized access valves at the furthest point from the compressor in the suction and liquid lines is advisable.
  • Page 6: Charging Procedure

    4) Click on "ENABLE". " " Figure 9: Enable button in the evacuation menu 5) The flashing "EVACUATION" on the main page indicates that the evacuation mode is active. Starting the evacuation mode: The evacuation mode will start when clicking on "ENABLE" only if the suction, discharge and liquid receiver pressures are below 10 bar.
  • Page 7 Figure 10: Enabling the compressor via F1 and SB12 on the OME-16T model Figure 11: Enabling the compressors via F1, Q03, SB12 & SB22 on the OMTE-37/49/64T models The unit starts automatically. First the gas cooler fan(s) start(s) up, then the compressor(s) switch(es) on and start(s) controlling according to the suction pressure.
  • Page 8 Copeland recommends charging the liquid receiver only up to 60 %. Charging must be done with compressor(s) switched on. NOTE: Never charge the system to a liquid level higher than the upper sight glass of the liquid receiver.
  • Page 9 Copeland does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Copeland product remains solely with the purchaser or end user.