HERZ clever&smart Room Sensor narrow It
HERZ clever&smart Room Sensor narrow It 3 F810 61
Digital room temperature sensor with communication via 1-Wire bus in connection with the HERZ clever&smart Control Box.
Wall Installation
1-Wire ID
Electrical Connection
Herz Armaturen Ges.m.b.H. | Richard-Strauss-Straße 22 | 1230 Vienna, Austria | +43 (0) 1 616 26 31 - 0 | office@herz.eu | www.herz-armaturen.at
3F81061-EN-07/2023
Technical Data
Power Supply
5 VDC SELV or PELV
Measurement Range
0 °C ... 60 °C
Accuracy: +/- 1 °C
Resolution: 0,1 °C
Protection Class
IP 20
Max. Cable Length
up to 100 m powered (three-wire connection recommended), using twisted pair cables
Dimension
21 mm x 43 mm
Housing Design
plastic housing pure white
Installation Methods
flush-mounted switch box
Mount the HERZ clever&smart Room Sensor narrow It in a suitable place.
Caution!
Device and function may be damaged. Select a suitable environmental condition. Direct sunlight,
sources of heat and cold, e.g. radiators and windows must be avoided.
Mounting in flush-mounted switch box
Use the supplied screws (3.0 x 16 mm) to fix the mounting frame to the switch box. Open the terminals with a
screwdriver and make the electrical connection as described below.
Each HERZ clever&smart Room Sensor narrow It has a unique 16-digit 1-Wire ID. This ID is required for sensor-
room assignment in HERZ clever&smart Room Controller . The ID can be found inside the sensor on the type plate
and on the supplied sticker. We recommend placing the sticker in the table of the HERZ clever&smart Control Box
instruction manual or in the HERZ clever&smart Control Box terminal plan sticker to simplify the later configuration of
the system.
To connect a HERZ clever&smart Room Sensor narrow It one of the terminal points VDD/ GND/ DQ is required in
each case. The additional three clamping points are for easy connection of further sensors. Use a suitable twisted
pair cable and ensure sufficient wire cross-section e.g. LIYCY 2 x 2 x 0.75mm²
Only to be used with SELV or PELV protective extra-low voltage.
If shielded cables are used, contact between the shielding and the PCB can cause damage to the
device and lead to malfunctions.