Download Print this page

Bamo MEMPRO S6.6 Manual

Hydrostatic multiple limit value switch

Advertisement

Quick Links

HYDROSTATIC MULTIPLE LIMIT VALUE SWITCH
SAFETY INSTRUCTIONS
- Installation, commissioning and maintenance may only be carried out by qualified personnel!
- Only connect the unit to the voltage specified in the technical data or on the type plate!
- Disconnect the unit from the power supply during installation/maintenance work!
- Only operate the unit under the conditions defined in these operating instructions!
DESCRIPTION
The MEMPRO S6.6 / MEMPRO C S6.6 hydrostatic multiple limit switch operates according to the dynamic pressure measuring principle.
The current level is derived from the hydrostatic pressure inside a measuring tube closed on one side and immersed in the medium. The
ceramic measuring cell is not touched by the medium.
The automatic calibration function adjusts the unit to the tank dimensions on site in a matter of seconds. Four limit switching points can be
assigned to the level range via the setting menu.
For tank contents with highly fluctuating temperatures, adhering or outgassing media, the MEMPRO S6.6 / MEMPRO C S6.6 should be
connected to an optionally available ventilation system. The clock control is already integrated in the measuring electronics.
TECHNICAL DATA
Power supply
Power consumption
Ambient temperature
Media temperature
Output relay
Output relay switching power
Note: The contacts are not protected against overload! Provide external protective device!
Connecting head
Protection class
Terminals
Measuring cell
(*)Please note!
The unit may only be used in media to which the EPDM measuring cell seal is resistant!
In the case of media to which EPDM is only conditionally resistant, care must be taken to ensure that the seal never comes into
direct contact with the medium during operation, assembly and maintenance!
Measuring accuracy
Display resolution
Reset hysteresis
Measurement value filter
Signalling
Setting
Ventilation connection
CE mark: The appliance fulfils the legal requirements of the applicable EU directives.
22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL
Tel
+33 (0)1 30 25 83 20
Fax
+33 (0)1 34 10 16 05
MEMPRO S6.6
24V DC (9...36V)
Max. 1 W
-20...+60°C (MEMPRO S6.6)
-15 ... +60°C (MEMPRO C S6.6)
0...60°C PVC version (MEMPRO S6.6)
0...90°C PP version (MEMPRO S6.6)
0...90°C Stainless steel version (MEMPRO CS6.6)
3+1x limit value relay 250V AC, 2A / 30V DC, 1A
(3x common root, 1x separate - fourth relay can also be used as clock generator)
250V AC, 2A / 30V DC, 1A
PBT, glass fibre reinforced
IP65 according to EN 60 529
Screw connection, max. 1.5mm²
Ceramic, with EPDM seal(*)
0.5% ±0.5 Digit
1%
Adjustable 1...99%
Adjustable 1...9.9 seconds
3-digit 7-segment LED display, 4x LED = limit relay
Combined rotary/push switch
For plugging on a hose (e.g. PVC 4x1mm) or for screwing in a compressed air connection with G1/4" thread
INTERNATIONAL
Web
www.bamo.eu
E-mail
export@bamo.fr
HYDROSTATIC MULTIPLE
LIMIT VALUE SWITCH
MEMPRO S6.6
05-09-2023
LEV
592-03
M-592.03-EN-AB
/1

Advertisement

loading

Summary of Contents for Bamo MEMPRO S6.6

  • Page 1 DESCRIPTION The MEMPRO S6.6 / MEMPRO C S6.6 hydrostatic multiple limit switch operates according to the dynamic pressure measuring principle. The current level is derived from the hydrostatic pressure inside a measuring tube closed on one side and immersed in the medium. The ceramic measuring cell is not touched by the medium.
  • Page 2: Application Limits

    INSTALLATION The MEMPRO S6.6 / MEMPRO C S6.6 can be attached to containers or tanks in various ways: • Measuring tube immersed in the tank from above • Measuring hose immersed in the tank from above, measuring head mounted near the tank Please note: The lower end of the measuring tube or hose determines the 0% level measuring point.
  • Page 3: Operating Elements

    A pulse control is integrated in the electronics; e.g. a solenoid valve can be controlled by relay 4. Ventilation connection COMMISSIONING HYDROSTATIC MULTIPLE INTERNATIONAL LIMIT VALUE SWITCH MEMPRO S6.6 22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL 592-03 +33 (0)1 30 25 83 20 www.bamo.eu 05-09-2023 M-592.03-EN-AB...
  • Page 4 The 100% point can be adjusted to the conditions on site via the setting menu. 1.) Install MEMPRO S6.6 / MEMPRO C S6.6 in tank! The measuring tube must not stand on the tank bottom or be immersed in solid bottom mud! 2.) Fill the tank to a level of 50...100%!
  • Page 5: Maintenance

    The current fill level is set to 0 and permanently saved. MAINTENANCE When used as intended, the MEMPRO S6.6 / MEMPRO C S6.6 operates maintenance-free. In case of strongly adhering liquids (e.g. milk of lime), the measuring tube or the measuring hose should be checked and cleaned at regular...
  • Page 6: Setting Menu

    Relay 3 Relay 4 or clock generator HYDROSTATIC MULTIPLE INTERNATIONAL LIMIT VALUE SWITCH MEMPRO S6.6 22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL 592-03 +33 (0)1 30 25 83 20 www.bamo.eu 05-09-2023 M-592.03-EN-AB...

This manual is also suitable for:

Mempro c s6.6