Operating instructions Varitain
Required materials
Prepare the power
supply cable�
Unscrew and open the cover
1
ATTENTION
When removing the cover, ensure that the seal is undamaged�
Insert the cable
3
Varitain PushIn Rack 2x/x2 only: Lay on the wires.
4b
(Use cables with stripped leads)
Use Phase (L1, L2, L3) conductors�
L3
L2
L1
PushIn Rack
®
Power supply cable: Use L1, L2, L3, and Protective Earth (PE), and the cable shield�
3 wire end ferrules (only Varitain PushIn Rack 2x/ x2) or lugs ( all other).
Strip the cable insulation and bend the cable shield�
Strip each conductor's insulation approx� 10 mm�
Varitain PushIn Rack 3x/ x3/ 4x/ x4/ 5x/ x5 only:
Fit and press the wire end ferrules or M10 cable lugs�
Article-No.: 50108392
Screw up the cable gland's cap nut
2
Varitain PushIn Rack 3x/x3/4x/x4/5x/x5:
4a
Lay on the wires�
Use Phase (L1, L2, L3) conductors�
L3
L2
L1
The tightening torque for the screws should be 4 Nm
i
Screw-down the cable gland's cap nut
5