Oil burner controls

Advertisement

Technical data
General unit data LAL...
Environmental
conditions
6/20
Building Technologies
HVAC Products
Mains voltage
- With LAL1... / LAL2... / LAL3... incl.
Mains frequency
Unit fuse (built-in)
Primary fuse (external)
Weight
Power consumption
Mounting position
Degree of protection
Safety class
Perm. input current at terminal 1
Perm. current rating of control terminals
3, 6, 7, 9...11 and 15...20
Required switching capacity of switching
devices
-
Between terminals 4 and 5
-
Between terminals 4 and 12
Between terminals 12 and «LP»
-
Between terminals 4 and 14
-
-
«LP»
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Condensation, formation of ice and ingress of water are not permitted!
AC 230 V –15 / +10 %
AC 100 V –15 %...AC 110 V +10 %
50...60 Hz ±6 %
T6.3H250V to DIN EN 60 127
max. 10 A (slow)
approx. 1,000 g
approx. AC 3.5 VA
optional
IP 40, when fitted, with the exception of the
connection area (terminal base)
II
max. 5 A (peaks of 20 A / 20 ms)
max. 4 A (peaks of 20 A / 20 ms)
1 A, AC 250 V
1 A, AC 250 V
1 A, AC 250 V
5 A (peaks of 20 A)
5 A
DIN EN 60721-3-1
class 1K3
class 1M2
-20...+60 °C
< 95 % r.h.
DIN EN 60 721-3-2
class 2K2
class 2M2
-50...+60 °C
< 95 % r.h.
DIN EN 60 721-3-3
class 3K5
class 3M2
-20...+60 °C
< 95 % r.h.
CC1N7153en
20.04.2005

Advertisement