Mercury Security MRDT Quick Start Manual

Display terminal

Advertisement

MRDT Display Terminal
Installation and Specifications:

1. General:

The MRDT integrates a 2 line x 16 character back-lit LCD display with a 16-position keypad and a reader
port. This highly functional I/O device can communicate to:
1) SCP/EP serial I/O port via a 2-wire RS-485 using MSP1 protocol. The total cable length is limited to
4,000 feet (1220 meters).
2) Reader interface port on the EP1501, EP1502, Series 2 MR50, Series 2 MR52, or MR51e via a 2-wire
RS-485 using MSP1 or OSDP * protocol. The total cable length is limited to 2,000 feet (610 meters).
3) Series 1 MR52 reader interface port with TTL signaling. The total cable length is limited to 500 feet
(152 meters).




Mercury Security © 2014
2355 MIRA MAR AVE. LONG BEACH, CA 90815-1755, (562)986-9105 FAX (562) 986-9205


Figure 1-1: Front and Side View



Figure 1-2: Mounting Dimensions
MRDT
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This
device may not cause harmful interference, and (2) this
device must accept any interference received, including
interference that may cause undesired operation.
















DOC 10107-0023
www.mercury-security.com








REV 1.05
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MRDT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mercury Security MRDT

  • Page 1 1. General: The MRDT integrates a 2 line x 16 character back-lit LCD display with a 16-position keypad and a reader port. This highly functional I/O device can communicate to: 1) SCP/EP serial I/O port via a 2-wire RS-485 using MSP1 protocol. The total cable length is limited to 4,000 feet (1220 meters).
  • Page 2 INTERFACE CABLE PIN 1 Figure 2-2: Rear and Side View of MRDT Circuit Board 2. Input Power: The MRDT requires 12 Vdc ± 15 % for power and the power source must be filtered. Mercury Security © 2014 MRDT DOC 10107-0023 REV 1.05...
  • Page 3 12 Vdc Pass Through for External Reader GREEN Reader DATA or DATA 0 WHITE Reader CLOCK or DATA 1 Optional External Reader Connections BROWN Reader LED ORANGE Reader Buzzer BLACK Ground Table 1-1 Mercury Security © 2014 MRDT DOC 10107-0023 REV 1.05 Page 3...
  • Page 4  Figure 3-1: Communications Wiring Diagrams Mercury Security © 2014 MRDT DOC 10107-0023 REV 1.05 Page 4...
  • Page 5 4. Optional External Reader Wiring: The MRDT supports the connection of a standard reader. This external reader is connected to J3 pins 9 through 14, see table 1. The power for this reader can be passed through from the 12Vdc input power of the MRDT.
  • Page 6 Prompting sequence: After you make your entry, wait (3 seconds) to be prompted to accept or change an entered value. If a prompt is not responded to after 2 minutes, the MRDT will return to the PowerUp Complete screen. Comm:...
  • Page 7 When the MRDT is not communicating to the SCP/EP controller communication port or the reader port, the following will be displayed: “ooo “ “ ooo” If the SIO of the reader port that the MRDT is connected to is off-line with the SCP/EP controller, the following will be displayed: “… “ “ …”...
  • Page 8 This product is not intended for, nor is rated for operation in life-critical control applications. Mercury Security is not liable under any circumstances for loss or damage caused by or partially caused by the misapplication or malfunction of the product. Mercury Security's liability does not extend beyond the purchase price of the product.

Table of Contents