Page 1
Low Voltage Alternators - 4 pole TAL 044 Installation and maintenance Three-phase 6-wire Single phase 4-wire...
Page 2
5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole This manual concerns the alternator which you have just purchased. We wish to draw your attention to the contents of this maintenance manual.
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole CONTENTS 1 - RECEIPT ...........................4 1.1 - Standards and safety measures ..................4 1.2 - Inspection ........................4 1.3 - Identification ........................ 4 1.4 - Storage ........................4...
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 2 - TECHNICAL CHARACTERISTICS 2.2 - Mechanical characteristics - Steel frame 2.1 - Electrical characteristics - End shields in cast iron...
Page 6
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole • SHUNT 4-wire single phase dedicated STATOR: 4-wire (T1 to T4 identification) MAIN FIELD EXCITER Armature Exciter field Rotating rectifiers...
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 3 - INSTALLATION • Single-bearing coupling Before coupling, check the compatibility Personnel undertaking various between the alternator and the engine by...
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole 3.3 - Terminal connection diagrams There are 2 possible methods for restoring the above minimum values. To modify the connection, change the a) Dry out the machine for 24 hours in a position of the stator cables on the terminals.
Page 9
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole • 6-wire connection Connection OUTPUTS TO THE RIGHT OUTPUTS TO THE LEFT EARTH EARTH 3 PH Star L1 (U) W(3)-L3...
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole • Connection checks 3.4 - Commissioning Electrical installations must comply with the current legislation in force in the The machine can only be started up and country of use.
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 4 - SERVICING - MAINTENANCE WARNING 4.1 - Safety measures Do not use: trichlorethylene, perchlo- Servicing or troubleshooting must be...
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole 4.3 - Bearings The bearings are permanently greased Approximate life of the grease (depending on use) = 20,000 hours or 3 years.
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 4.5 - Electrical faults Fault Action Effect Check/Cause The alternator builds up and its voltage is still correct - Lack of residual magnetism...
Page 14
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole • Checking the winding Assembly A: Connect a 12 V battery in series with a rheostat of approximately You can check the winding insulation by 50 ohms - 300 W and a diode on both exciter performing a high voltage test.
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 4.6 - Dismantling, reassembly - Refit the modules. - Refit the air intake grille [51]. WARNING • Access to connections and the...
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole 4.7 - Table of characteristics Table of average values: Alternator - 4 poles - 50 Hz - Winding n°6S NDE shield...
Page 17
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole • Dedicated single-phase M: 4-pole • Table of weights SHUNT excitation - 50 Hz (values given for information only) Resistances at 20 °C (Ω) - Series...
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole 5 - SPARE PARTS 5.3 - Accessories 5.1 - First maintenance parts • Space heater for use when stopped Emergency repair kits are available as an The space heater must run as soon as the option.
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole 5.4 - Exploded view, parts list and tightening torque • Single bearing, SHUNT...
Page 20
Installation and maintenance 5226 en - 2017.01 / f Electric Power Generation TAL 044 Low Voltage Alternators - 4 pole Bolt Torque Bolt Torque Ref. Qty Description Ref. Qty Description Ø Ø Preloading (wavy) Stator assembly washer Rotor assembly Exciter field (stator)
Installation and maintenance Electric Power Generation 5226 en - 2017.01 / f TAL 044 Low Voltage Alternators - 4 pole Disposal and recycling The oil and grease from the lubrication system should be considered as a hazardous instructions waste and has to be handled according to We are committed to limit the environmental local legislation.
Page 22
LSA50.2 - LSA51.2 - LSA52.2 - LSA52.3 - LSA53.1 - LSA53 - LSA53.2 - LSA54 - LSA54.2 - TAL040 - TAL042 - TAL044, as well as their derivatives, manufactured by Leroy-Somer or on Leroy-Somer's behalf, comply with the following International Standards and Directive: - EN and IEC 60034-1, 60034-5 and 60034-22 - ISO 8528-3 “Reciprocating internal combustion engine driven alternating current generating sets.
Page 23
•Genuine spare parts •Repair services Contact us: Americas: +1 (507) 625 4011 Europe & International: +33 238 609 908 Asia Pacific: +65 6250 8488 China: +86 591 88373036 India: +91 806 726 4867 Scan the code or go to: service.epg@leroy-somer.com www.lrsm.co/support...