11-4.Function Inquiries
No.
1
How many air conditioner units can be connected?
How many air conditioner units can the Central remote
2
controller connect?
Is it possible to turn on and off lights, ventilators, and air
3
conditioners from other manufacturers?
4
Is it possible to use a schedule timer with this system? Yes.
Is it possible to use a touch panel air conditioning
5
control system with this system?
6
Is it possible to use a BACnet system with this system? Yes. But a check is required.
Is it possible to use a LONwork system with this
7
system?
Is it possible to use a remote monitoring system in
8
conjunction with this system?
9
Is it possible to connect AI-NETwork series devices?
10
Is it possible to change zone names and other names? Use the "Setting menu" to change a zone name.
How many characters can be used for zone names and
11
other names?
12
Up to how many items are saved in the alarm history?
13
Can the alarm history be deleted?
Is a special operation required to turn off the Central
14
remote controller?
Does turning off the power to the Central remote
15
controller also turn off the air conditioners?
16
Is it possible to stop all indoor-units at once?
Is it possible to monitor the operation status of the
17
outdoor units?
Is there a priority order for setting air conditioner
18
operations?
Is it possible to connect indoor units without local
19
remote control?
20
I have forgotten the administrator password.
21
I want to check the software version.
Questions
Up to 64 units can be connected.
A total of 10 central control devices can be connected to one TCC-LINK line.
A central control device is a Central remote controller, schedule timer or ON-
OFF controller.
If they are connected to a general-purpose device control interface, it is
possible.
Yes. But a check is required.
Yes. But a check is required.
Yes. But a check is required.
No. Use an air conditioning control system that supports the AI-NET work
series.
7 bytes for zone names (7 single-byte characters or 3 double-byte
characters)
Up to 300 instances. The 301 instance and subsequent instances are saved
by deleting old history instances starting in order from the oldest.
˄
˅
When [
]+[
]+[
] are pressed and held down for 4 seconds simultaneously
in the alarm history display screen, the confirmation screen is displayed and
it can be deleted.
No.
Air conditioners connected to a local remote control or wireless adapter are
not turned off when the Central remote controller is turned off.
Air conditioners not connected to a local remote control or wireless adapter
are turned off.
Yes.
Use the All screen to stop operation.
Use the Central remote controller to make an All stop external input.
No.
A latter setting overrides a former setting.
Yes.
˄
˅
When [
]+[
]+[
]are pressed for at least 4 seconds simultaneously in the
"All" screen, the "Initialize admin. password" confirmation screen is
displayed, and then it can be reset.
The password after resetting will be "0000". Reset the password to a
password of your choice on the setting menu.
Press [
] in the control screen to display the menu. It can be confirmed on
the "Information" in "Model information".
Answers
21