Conventional Gas Sensor SGM595/A-H2CH
The sensor SGM595/A-H2CH is a Catalytic gas detection unit with IP66 protection that, together with one
of BEINAT's industrial type Control Units, detects the presence of esplosive gas.
Thanks to innovative technical features such as the control software, the sensor is suitable for industrial
applications, boiler rooms and industrial kitchens, detecting methane and hydrogen.
The sensor is managed by a microprocessor which not only supplies an alarm signal to the control unit
connected to it, but also allows execution of a self-diagnosis and therefore an AUTOMATIC CALIBRATION, in
order to always have the maximum detection accuracy.
The self-calibration means the sensor adapts in harsh and variable temperature environments, avoiding false
alarms due to anomalous events.
The sensor has a 0 ÷ 20 % LEL linear output conforming to the 4 ÷ 20mA standard, for which can be connected
with one of BEINAT's industrial control units.
The important innovation of this probe is the possibility to substitute the sensor at the end of the operating
cycle or fault by the technician without having to send to BEINAT Srl.
Indispensabile instrument for the annual check of the probes
Instrument of testing TS1008
To facilitate the reading of the functional parameters of the probe as well as the control of annual
operating, the BEINAT S.r.l. has built a new portable tester TS1008.
The tester allows to read all the data in the memory of the probes eand by serial transmission, it
prints the ticket that confirms the testing data.
Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.
Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and
keep it for future reference. It is also recommended to perform the electrical connections correctly as
per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side
Installation and user
guide
CONFORMITY
Installation
Reports issued by
Electric connections also available on
Channel: Beinat gas solutions
Belonging to
V. R1bd04
EN 50270
EN
EN 60079-29-2
TUV Italia

Advertisement

loading

Summary of Contents for BEINAT SGM595/A-H2CH

  • Page 1 Conventional Gas Sensor SGM595/A-H2CH V. R1bd04 The sensor SGM595/A-H2CH is a Catalytic gas detection unit with IP66 protection that, together with one of BEINAT’s industrial type Control Units, detects the presence of esplosive gas. Thanks to innovative technical features such as the control software, the sensor is suitable for industrial applications, boiler rooms and industrial kitchens, detecting methane and hydrogen.
  • Page 2: Technical Specifications

    When doing the electrical connections, follow the drawing closely. Any use of the detector for purposes other than the intended one is considered improper, and as a result of which BEINAT S.r.l. therefore disclaims any responsibility for possible damages caused to people, animals or objects.
  • Page 3: Maintenance

    Compatible control units CONTROL UNITS MOUNTING PROBES Max. DEGREE ALARMS POSITIVE OPERATING protec. alarms safety range GS100M unit 1 zone Wall/cabinet I P 4 4 Y E S GS300M unit 1 zone Wall/cabinet I P 4 4 Y E S GS300-Mc unit 1 zone Wall/cabinet I P 4 4...
  • Page 4 Electrical connections WARNING Before connecting to the mains power, ensure the voltage is correct. Carefully follow the instructions and the connections according to Regulations in force, keeping in mind that the signal cables should be laid separate from the power cables Optional Relay Board CARD03 Power Supply...
  • Page 5 220 Ohm resistance installed between 12÷24 V. terminal 2 and terminal 3. Linear Otput 4-20 mA If other pr oblems arise, a specialised and/or authorised technician and/or the Distributor of BEINAT S.r.l. should be contacted directly. Page 5...
  • Page 6 The probes must be selected with an "IP" degree of protection depending on the area to be controlled (Kitchens, Boiler rooms, Laboratory, Factories, etc.) by choosing one of the probes produced by Beinat that goes from IP30 to ATEX. The GAS sensors connected to this equipment are of various types and must be positioned at different heights depending on the type of gas to be detected.
  • Page 7 Gas imput Test Test SGM595/A-H2CH The installation of the SGM595/A-H2CH probe, its ordinary and extraordinary maintenance, and its out of service removal at the end of the functional life guaranteed by the manufacturer, must be carried out by authorized or specialized personnel.
  • Page 8 Purchase date: Registration number: The Beinat S.r.l. following the targhet to improve its products, reserves the right to modify the technical features, aesthetic and functional any time without prior notice. BEINAT S.r.l. Via Fatebenefratelli 122/C 10077, S. Maurizio C/se (TO) - ITALY Tel.