3. Answer the commissioning tool's question that asks if this is complete.
Adjusting the High Fire Setting on a Modulating Valve:
1. Hook-up a manometer to the test port/s on the burner manifold/s in question when the commissioning
tool prompts you to do so. Answer the furnace commissioning tool question that asks if this is complete.
2. The next step will state that the furnace is being called to high fire. The commissioning tool will prompt
you to adjust manifold pressures in the correct order for your furnace configuration.
3. To set the high fire pressure setting on a modulating valve, Press and hold button #1 (see Figure 2)
until the LED lights solid red on the modulating valve. Release once the LED is lit solid.
4. Observe the manifold pressure with the manometer and compare it to what the commissioning tool is
asking for.
5. Adjust the modulating valve's pressure by pushing button #1 to increase the pressure and button #2 to
decrease the pressure (see Figure 2). The gas pressures that the commissioning tool will ask for can
be found in Figure 3.
Copyright © 2023 Greenheck Fan Corporation 
 
April 2023
Figure 1: Combination Regulator Valve
Figure 2: EXA Modulating Gas Valve (With Cover Removed)
 