ACFEE ACTIVE POWER FILTER
AcFee APF(V3.0)
Operation manual

Advertisement

Table of Contents
loading

Summary of Contents for Lafaelt AcFee APF

  • Page 1 ACFEE ACTIVE POWER FILTER AcFee APF(V3.0) Operation manual...
  • Page 2 AcFee 有源电力滤波器 Safety Instructions These safety instructions apply to all active power filter device of our company. Ignoring these instructions could result in personal injury and death. Live Operation Forbidden!  Specific Purpose Active power filter (APF for short, the same below) is a new generation of power quality control device, which is mainly used for harmonic control.
  • Page 3 AcFee Active Power Filter the device must be familiar with this manual. Exemption from Liability  The content of the user manual describes the characteristics of the product, but is usually not a guarantee. If you encounter any questions and problems, please contact us in time to avoid irreparable accidents!
  • Page 4: Table Of Contents

    AcFee 有源电力滤波器 Catalogue Safety Instruction ..........错误!未定义书签。 About This Manual ..........错误!未定义书签。 Brief Instruction ..........错误!未定义书签。 Model Description ........错误!未定义书签。 AcFee Series APF Features ..........5 Technical Specifications ......错误!未定义书签。 Working Principle ........错误!未定义书签。 Dynamic and Steady-State Features of APF ...... 12 Initial Inspection and Installation ..........
  • Page 5: About This Manual

    AcFee Active Power Filter About This Manual Before installing and operating the SVG, this manual should be read carefully. This manual contains the necessary information for the perfect performance of the device and to avoid incorrect operation. The following symbols, terms and names are used in this manual. Table1 Use of symbols, terms and names Note Follow the instructions in the manual to...
  • Page 6: Model Description

    Wiring 3: Three-Phase Three Wire 4: Three-Phase Four Wire Current(A) 25-500 Voltage(V)200、400、690 Product Name:Lafaelt Active Power Filter  AcFee Series Features 1. Modular design, the failure of any module will not affect the normal operation of other modules, which greatly improve...
  • Page 7 AcFee Active Power Filter 2. It can simultaneously filter out the harmonic current below the 2 to 51st orders, or select order compensation. Reactive power compensation can make the power factor reach 1. It can correct unbalanced three-phase current to complete balance.
  • Page 8 AcFee Active Power Filter output automatically, maintain normal operation, and will not happen faults such as overload or burned; 8. The main circuit adopts tri-level three leg, with high output waveform quality and low switching loss. 9. It adopts a 7-inch high definition touch screen, which is easy to operate.
  • Page 9: Technical Specifications

    AcFee Active Power Filter  Technical Specifications Table 2 Technical Specifications Module Specifications 100A 150A Specification Working Voltage 200V/400V/690V(± 15%) Working 50Hz(-10% ~ +10%) Input Frequency Current 100:5 ~ 10000:5 Transformer Harmonics 2nd-51st Compensation Harmonics Function >97% Rejection Rate Compensation -1~+1 adjustable for Reactive Communication...
  • Page 10 AcFee Active Power Filter CT Install Load side/Grid side Optional Location Single Machine See APF dimension drawing for details Mechanical (P13-15) Size Properties Weight 25kg~40kg Working -10℃~+45℃ Temperature <5000 meters (Above 1500 meters, the Altitude capacity will reduce 1% for every Environment additional 100 meters)...
  • Page 11 AcFee Active Power Filter  Working Principle Picture1 APF Working Principle Chart 1. Working Principle User can set parameters so that the device can simultaneously have the function of filtering harmonics, dynamic reactive power compensation, and three-phase unbalance compensation. The principle of filtering harmonic is that APF collects the current signal in real time through current transformer, separates the harmonic part through the internal detection circuit,...
  • Page 12 AcFee Active Power Filter automatically limit the output to 100% of the rated capacity, no overload will happen. The principle of three-phase unbalance compensation is that APF collects system current signals in real time through external current transformers and sends them to DSP for real-time calculation to judge where the system current is in an unbalanced state, and at the same time calculates the current difference of each phase when it reaches a balanced state.
  • Page 13 AcFee Active Power Filter capacitor through the soft start circuit, and the process lasts for more than ten seconds. DC capacitor acts as an energy storage device, and supplies energy by outputting compensation current through IGBT and internal reactor. DC capacitor acts as an energy storage device, and supplies energy by outputting compensation current through IGBT and internal reactor.
  • Page 14: Initial Inspection And Installation

    AcFee Active Power Filter CH1:Mains Voltage;CH2:Mains Current(Compensation Target); CH3:Load Current;CH4:Device Current Dynamic characteristic at sudden load Steady-state characteristics at full changes: response time <10ms load: THDi compensated from >70% to <3% Picture3 Dynamic and steady-state characteristics Initial Inspection and Installation This chapter introduces the relevant requirements that must be considered when selecting the location and wiring of the APF and its related device.
  • Page 15 AcFee Active Power Filter If used in an IT AC distribution system, a 4-pole circuit breaker should be configured for the input, and reference can be made to relevant IT system standards  The APF can only be powered on with the approval of the commissioning engineer.
  • Page 16: Initial Inspection

    AcFee Active Power Filter  Parts behinds protective cover that require tools to open are not user-operable parts.  Tearing the anti-tear label without permission is regarded as giving up the manufacturer’s maintenance service.  Strong recommendation: Although the rack-mounted APF has its own circuit breaker, this manual still recommends users install a Danger circuit breaker between APF and the mains for...
  • Page 17 AcFee Active Power Filter APF cabinet. Do not block the vents. Due to the air duct isolation, there is no need to install a dust filter in general environment, but for hash environment, such as high temperature, high humility, and a lot of conductive dust environment, please contact our product engineers when making on-site application solutions, and confirm the specific heat dissipation scheme.
  • Page 18 AcFee Active Power Filter temperature.  Device Handling  Since the weight of a single APF module is 30kg-55kg, it is recommended to be transported by two people within a short Attention! distance, if transported over a long distance, it needs to be completed with the help of transportation device.
  • Page 19 AcFee Active Power Filter For higher requirements, please contact Humility <90% the manufacture At least 600mm of ventilation space Installation Modular should be reserved at the front and rear outlets of the cabinet Table 4 Conditions of Module Installation Position Minimum Required Installation Space No need Front side to front door panel...
  • Page 20 AcFee Active Power Filter  Touch Screen Size Chart Picture4 Touch Screen Size...
  • Page 21: Apf Dimension

    AcFee Active Power Filter  APF Dimension Picture5 Schematic Diagram of Module Appearance...
  • Page 22 AcFee Active Power Filter Picture6 Module Dimensions...
  • Page 23: Optional Accessories Installation

    AcFee Active Power Filter  Optional accessories installation 1. External Sampling CT The APF is installed in parallel in the system, and the current transformer CT can be optionally connected to the grid side or load side on the touch screen, default is load side for installation.
  • Page 24 AcFee Active Power Filter In Figure6, if there are several modules in a cabinet, the total output current sampling CT2 is required in the cabinet to realize the sampling on the grid side. For the wiring when APF and capacitor are used together, the principle is that the main incoming line point of APF is closer to the load than the capacitor.
  • Page 25 AcFee Active Power Filter  Make sure that the current transformer is in a short circuit status until the CT connect terminals of the APF are connected.  Short-circuit the current transformer with the separable short-circuit terminal before separating the current transformer and APF. External CT Specification Option Model...
  • Page 26 AcFee Active Power Filter transformer. Picture9 Wiring of current transformer when a single APF module running ② Wiring of current transformer when multiple APF modules running in parallel. The parallel operation of APF modules can increase the compensation current value. When multiple APFs are connected in parallel, they share a set of current transformers, and the CT secondary side cables are connected in series.
  • Page 27: External Incoming Cable Specification

    AcFee Active Power Filter Picture10 CT Cables Connection Diagram 【Note】: The installation of the electric part of APF device must be carried out by trained and qualified engineers in accordance with the “Electrical Code”, and other personnel are strictly prohibited from installing.
  • Page 28: User Operation Guideline

    AcFee Active Power Filter Table 6 Cable Specification Device Rated Current 100A 150A BVR Cable(mm2) User Operation Guideline APF can be operated through touch screen.  Main Menu After the device is powered on, the screen is in the startup state, and the startup process lasts for about 10 seconds.
  • Page 29 AcFee Active Power Filter  Real-time Data Picture12 Real-time Data (Voltage, Current, Inverter Current) Picture13 Real-time Data2(Power Factor, Aberration Rate)...
  • Page 30 AcFee Active Power Filter Picture14 Real-time Date3 (Detect the magnitude of each harmonic current)  Module Information Picture15 Module Information...
  • Page 31 AcFee Active Power Filter Picture16 Module Information2 (Detect the size of each harmonic current) Picture17 Module Information3...
  • Page 32: User Setting

    AcFee Active Power Filter Picture18 Module Information4  User Setting Click User Setting, enter technician user password:8888 to enter the user settings page Picture19 User Setting...
  • Page 33: Communication Setting

    AcFee Active Power Filter  Communication Setting Picture20 Communication Setting The HMI number has been set to 1 by default before leaving the factory.  Overall Setting Picture21 Overall Setting Number of units in the cabinet: corresponding to the number of...
  • Page 34 AcFee Active Power Filter modules in the cabinet. The number of all parallel units: for the total number of modules in the master and slave machines. APF units: The number of corresponding modules of mixed cabinet (o for non-mixed cabinets) Picture22 DIP Setting When there are multiple modules in the whole cabinet, the numbers need to be set, and the dial code is set according to the device...
  • Page 35 AcFee Active Power Filter  System Setting Picture23 System Setting Click the parameter you want to set, and a corresponding dialog box will pop up to enter the parameter. More detailed internal control parameter settings have been set before leaving the factory.
  • Page 36 AcFee Active Power Filter 40. After clicking the input box, an input dialog box will pop up. According to the transformation ratio setting, the larger the transformation ratio, the lager the sampling scape and the larger sampling error. (Factory default is 0). 4.
  • Page 37: Current Records

    AcFee Active Power Filter displayed as 0, and it is reactive power priority at this time.  Operation Interface Picture24 Operation Interface If there is an abnormality in the device and it is in automatic mode, press the “Reset” and “Restart” buttons, and the machine will clear the fault and wait for about 2 minutes before starting itself.
  • Page 38 AcFee Active Power Filter page displays various internal and external faults and alarm information records during this power-on process。 Picture25 Current Record [Note]: 1. If the user has not clicked to start the device after it is powered on, the device will automatically start and run after 10 minutes.
  • Page 39: History Records

    AcFee Active Power Filter  History Record Fault information will be recorded in “History Record” eventually. Picture26 History Record...
  • Page 40: List Of Common Faults

    AcFee Active Power Filter List of Common Faults This device has the function of maintenance-free. When a fault occurs, the device will automatically reboot after a maximum of 5 minutes. If the fault still occurs frequently after rebooting, please contact us and we will try our best to troubleshoot for you.
  • Page 41 AcFee Active Power Filter AC current offset calibration temperature too low failed AC voltage offset Heatsink temperature too calibration failed high DC current offset calibration Output overcurrent failed DSP short circuit between Unknow grid type drive phases RAM BIT Fault Phase sequence error fault ROM BIT Fault Zero line overcurrent fault...
  • Page 42 AcFee Active Power Filter APF Communication Data Point Table 1. Protocol RS485 MODBUS RTU, Communication Band Rate 9600BPS, Date Bit 8 bits, no check digit, stop bit 1. Support protocol read function code 03. 2. The address and data table of each module in the access screen are as follows: 1# Module 2# Module 3# Module...
  • Page 43 AcFee Active Power Filter Actual Value = Device Current B 0~65535 Communication Phase Value /10 Actual Value = Device Current C 0~65535 Communication Phase Value /10 System Power -100~100 Factor A Phase System Power -100~100 Factor B Phase System Power -100~100 Factor C Phase System Current...
  • Page 44 AcFee Active Power Filter Communication Value Actual Value = Phase A CT -30000~+3000 Communication Transformation Ratio Value Actual Value = ℃ Heat Sink Temperature -2000~+2000 Communication Value Actual Value = Phase B CT -30000~+3000 Communication Transformation Ratio Value Actual Value = Parallel Number 0~65535 Communication...
  • Page 45: After-Sales Service

    AcFee Active Power Filter After-sale Service The products of our company are guaranteed for 1 year, and the warranty period starts from the date of product sale. If the product faults or the parts are damaged during the warranty period, our company will provide free maintenance after it is identified by our technicians as occurring under normal use.
  • Page 46 Jiangsu Lafaelt Electric Co.,Ltd Hotline: 400-882-1973 Tel: +86 0510-81811717 Email: marketing@lafaelt.com Sales Center Add: 2nd Floor, No. 268, Tongxie Road, Changning District, Shanghai, China Factory Add: No. 79, Qunxing Road, Xinwu District, Wuxi City, Jiangsu Province, China Net: www.lafaelt.cn...