Page 4
AMENDMENT SHEET Version No. Amendment Amended By Date Document re-write R Vahter 24/10/2022 Gateway Hub Update R Vahter 05/12/2022 Format changes R Vahter 06/02/2023 Update to page numbering R Vahter 10/03/2023 Update to Display Express R Vahter 05/06/2023 General Updates to Display Express & R Vahter 09/11/2023 Communications Protocols.
2 System Architecture When unpacking your equipment, please ensure that all of the items listed in the included Quick Start Guide (QSG) are present. If any item is missing, please contact your distributor directly or contact support@tandeltasystems.com for further assistance. Figure 1 - System Architecture Page | 10...
3 Accessories Tan Delta Systems produce and supply a range of accessories and add-ons specifically designed and engineered to work with the Oil Quality Sensor range. Accessories include the following: Oil Condition Display Express Oil Condition Telemetry Gateway Oil Condition Telemetry Gateway Hub Oil Condition Sensor Manifold A range of cables and fittings For details of the full range of available accessories, please contact your distributor.
4 Introduction The Tan Delta range of Oil Quality Sensors allow real-time reporting of oil quality in virtually any application. The sensor utilises sophisticated electronics to indicate the current condition of oil, relative to an initial profiled condition of new oil. Based on the sensor output, the oil drain-down intervals may be extended on large industrial equipment where the cost of replacing and monitoring the oil is expensive.
5 Measuring Oil Quality 5.1 Introduction There are a number of ways to describe oil wear and oil condition: Tan Delta Number (TDN) Loss Factor Percentage 5.2 Tan Delta Number To make it easier to monitor and trend the overall oil condition, regardless of your current method, we have introduced the “Tan Delta Number”...
5.5 Traffic Lights First and foremost, the TDN scale offers a ‘traffic light’ view of oil quality. There is a Green section, an Amber section and a Red section to illustrate OK, Warning and Alarm conditions respectively. The thresholds for these sections can be user-defined for any application. Factors such as likelihood/nature of contamination, how critical the machinery is and manufacturers’...
5.8 Loss Factor A clean oil has a Loss Factor Percentage of approximately 0% and then as the oil changes and degrades this Loss Factor Percentage increases. For most applications, oil would be considered to be degraded at a Loss Factor Percentage of 25% and at the “end of life” at a Loss Factor Percentage of 30% or above.
6 OQSxG2 (Standard Sensor) 6.1 Sensor Configuration Before installation, it is necessary to configure the sensor to your specifications using the Tan Delta Configuration and Data Management Software (CADS). This is a software application, supplied on the USB memory stick, which must be installed on a windows PC or laptop. (Please note the software does not operate on Mac devices or on Chromebook devices.) 6.1.1 Set Up 6.1.1.1...
Page 19
Figure 4 - Setting up a sensor for configuration (Standard sensor shown) 6.1.1.2 Launch the software Launch CADS and wait for the home screen to load. 6.1.1.3 Connect OQSxG2 Once the home screen has loaded, select ‘Configure Oil Quality Sensor’ from the tiles on the home screen.
Page 20
6.1.1.5 Communications settings This next screen lists the options for the device you wish to connect the sensor to: Oil Quality Display Express – sets the sensor to use our proprietary RS485 communications protocol. Oil Quality Telemetry Gateway – This sets the sensor to CANbus for use with our legacy range of gateway devices operating on CANbus.
Page 21
6.1.1.6 Advanced Settings This function uses hysteresis to reduce the noise caused by changes in the oil such as temperature. In order for the algorithms to settle the sensor must go through at least one ‘thermal cycle’ of the application, this just means running the machine from standby until it reaches its highest normal operating temperature.
6.2 Installation 6.2.1 Precautions Please read these instructions before installing the oil quality sensor. The sensor has been designed to be robust, however it can be damaged by mistreatment. The following must be noted: Install the sensor into the equipment before attempting electrical/wiring connections. To avoid thread damage, do not use with taper fittings.
6.2.2 Choosing the Sensor Mounting Location The performance of the sensor will be enhanced through careful consideration of the mounting location. The following guidelines should be followed, See Figure 10: Sensor should be in a horizontal position. The sensor should not be mounted in the bottom of a sump since the sensor head may become restricted preventing correct operation.
6.2.4 Electrical Connection 6.2.4.1 Power Supply Connect a suitable power supply (9-30Vdc, at least 100mA) to pins 1&5. Figure 11 - Pin Outs for Power Supply & Data Output 6.2.4.2 Connecting to a Tan Delta OQDe Connect the OQSxG2 to the left-hand connector. We recommend using a Tan Delta OQSxG2 to OQDe cable (Cable SD –...
6.2.4.5 Using the Oil Temperature analog output The analog output on pin 2 provides a linearly scaled measure of Oil Temperature in °C between -30°C (4mA) and +130°C (20mA) – see Appendix (Section 14). 6.3 Cleaning & Maintenance Please follow this procedure to clean the sensor: Clean any excess oil from the end of the sensor with absorbent paper Remove the remaining oil by spraying Loctite 7063 cleaner (other low residue cleaners may also be suitable, please refer to your distributor for more information):...
6.4 Physical Dimensions Figure 13 - Physical Dimensions 6.5 Product Specification 6.5.1 Environmental Specifications Operating Temperature -40ºC (-40ºF) to +120ºC (+248ºF) Calibrated Temperature -20ºC (-4ºF) to +120ºC (+248ºF) Fluid Temperature -40ºC (-40ºF) to +120ºC (+248ºF) Fluid Pressure up to 70 bar (1015 psi) Storage Temperature -55ºC (-67ºF) to +150ºC (+302ºF) 6.5.2 Physical Characteristics...
6.5.4 Connections Connector 6 pin Bulgin 4000 series 6.5.5 Electrical Supply +9-30 V DC Consumption 0.4w Average 6.5.6 Data Output/Input Digital Output RS485, CANbus Protocols Supported Modbus, CANopen and J1939 Analog Output 4-20mA 6.5.7 Oil Quality Detection Parameters Frequency Every 2 seconds Output Tan Delta Number (TDN), Oil Temperature (C or F) Elements...
7 EX GEN II ATEX, IECEX, US/C, UKEX Oil Quality Sensor 7.1 Important Safety Notes Please pay attention to following safety notes: Never reassemble, repair or tamper with the sensor. Ensure that the supply voltage is within the specified range. Ensure the load currents do not exceed the rated value.
The equipment must be installed in a manner that any heating from the process connection does not exceed the ambient temperature assigned to the equipment. 7.2 Additional EX notes: 1) Working Voltage (peak value) must be less than 28.8V d.c., or 24V d.c. + 20%. 2) Sensor must be powered using an IEC / EN 60950-1 compliant power supply, or through a suitable EX barrier (e.g.
Tan Delta Systems plc. 1 Carrera Court, Church Lane, Dinnington, South Yorks. S25 2RG b. Manufacturer’s type identification. OQSExISG2 EX GEN II OIL QUALITY SENSOR c. Serial Number nnnnnnn (e.g. 1234567) d. Certificate Numbers SGS22ATEX0059X IECEx BAS 22.0033X SGSNA/22/CA/00013X BAS22UKEX0171X e.
Page 31
On Product:- Certification Markings: There are 5 options for Certification Markings of this product. These are displayed below. Unless requested otherwise by the customer the default Certification Label will be applied to the product. It is critical the customer checks which marking refers to their application. And elsewhere on Product:- S/N 1234567 Page | 29...
7.4 What’s in the box? When unpacking your OQSExISG2 unit, please ensure that all the following items are present. If any of the items are missing, please contact your dealer or support@tandeltasystems.com. OQSExISG2 Oil Quality Sensor Configuration cable Product USB memory stick...
7.5.1 Set Up To connect the OQSExISG2 to the configuration cable, connect the wires as shown in the illustration below: Figure 15 - Setting Up the OQSExISG2 for Configuration The sensor should be set up using CADS in the same manner as outlined in section 6.1.1.2 of this manual.
7.6.2 Choosing the Sensor Mounting Location The performance of the sensor will be enhanced through careful consideration of the mounting location. The following guidelines should be followed: The sensor should not be mounted in the bottom of a sump since the sensor head may become restricted preventing correct operation.
NOTE: The OQDe is not EX certified so must be mounted outside the Hazardous Area. Connect the OQSExISG2 to the left-hand connector of the OQDe. This will require a Tan Delta OQDe Cable ExSD (various length versions available) and suitable EX Zener barrier, which must be earthed to the Equipotential bonding system.
Page 36
For both analog outputs, in order to avoid excessive power dissipation inside the sensor, ensure that the 4-20mA current sense resistances fitted to the third party monitoring equipment/Zener barrier are greater than the values in the graph as shown below. Figure 18 - Current Loop Output Resistance Limitations Graph Page | 34...
Page 37
Figure 19 - Connection to other Tan Delta and 3rd Party Products / Interfaces Page | 35...
7.7 Cleaning & Maintenance Please follow this procedure to clean the sensor: Clean any excess oil from the end of the sensor with absorbent paper Remove the remaining oil by spraying Loctite 7063 cleaner (other low residue cleaners may also be suitable, please refer to your dealer for more information): Into each of the four holes at the end of the sensor.
7.9 Product Specification 7.9.1 Environmental Specifications Protection Rating IP68 Operating Temperature -20C to +120C Fluid Temperature -20C to +120C External Pressure 0 bar to 20 bar Fluid Pressure Up to 70 bar Permissible Machine Surface Temp vs. Air Temp @ 110C Oil Temp 110.5 109.5...
7.9.6 Range and Accuracy Sensor oil quality normal operating range -10% to +30% loss factor Sensor oil quality accuracy/repeatability +/- 3% loss factor Sensor temperature normalisation accuracy Pre V2.4 +/- 3% loss factor Post V2.4 +/- 1.5% loss factor Sensor oil temperature normal operating range -20C to +120C Sensor oil temperature accuracy +/-3% of full range (+/-4.2°C)
8.1 Introduction The Tan Delta Oil Quality Display Express (OQDe) is a display unit for use with a Tan Delta Oil Quality Sensor (OQSxG2). Oil Quality Oil Status LED Oil Life Oil Status key Remaining (Days) Power LED WiFi LED Event Code Display Side flange/...
OQDe using Wi-Fi via any PC, Tablet or Mobile Device. Simply search for nearby devices. The default SSID of the OQDe is “TanDelta OQDe” and password is “password”. This will create a local network between the device and the display.
Figure 25 - Connecting to the OQDe via Wi-Fi Hotspot 8.2.2 Navigating Insight On the top navigation bar, you can navigate to the different screens within Insight (Status, Data Log, Settings), and also change the units of Oil Temperature displayed on Insight (°C or °F) and Oil Condition (TDN or %LF).
Page 46
8.2.2.1.2 Oil Temperature Displays the temperature of the Oil as measured by the Sensor. 8.2.2.1.3 Sensor Internal Temperature Displays the internal temperature of the Sensor. 8.2.2.1.4 Oil Condition Displays the Oil Condition in either Tan Delta Number (TDN) or Loss Factor (%LF). With no Sensor connected to the device, the Oil Condition will display as 0 TDN or 45 %LF on Insight.
Page 47
Figure 27 - Data Log Screen To clear all historic Data Logs go to: > Settings > Clear Datalog > set to TRUE > click Apply > Reboot device by disconnecting/reconnecting. The Datalog will clear upon reboot and can take several minutes depending on the number of data logs.
Page 48
Any numerical value 255 255 255 0 Static IPv4 Gateway Any numerical value 192 168 1 1 Device Name (also appears as SSID) Numbers and letters TanDelta OQDe Clear Datalog TRUE or FALSE FALSE Clear Settings TRUE or FALSE FALSE Figure 29 –...
8.2.3 Connecting OQDe to Wireless Local Area Network (WLAN) The OQDe supports connection to a Wireless Local Area Network. To connect to your WLAN, you must first connect to the OQDe via Wi-Fi Hotspot. Connect to the OQDe via Wi-Fi Hotspot as per 8.2.1. Navigate to Insight using the IP Address 192.168.4.1.
8.2.5 Upgrading Firmware Insight provides the ability to upgrade the display firmware from a provided file. This can be done using a PC or mobile device, provided the firmware file is available on that device. Firmware is upgraded from the Status screen by selecting “Upgrade firmware” then selecting the firmware file from the PC / mobile device storage.
Page 51
Figure 34 - Upgrading Firmware (3) Figure 35 - Upgrade Reboot Once the upgrade has completed, the display will reboot. Page | 49...
8.2.6 Configuring a display using CADS CADS allows you to adjust the following OQDe parameters: • Warning & Alarm Levels: the points at which the Status LED changes from Green to Amber to Red. • Date/time. 8.2.6.1 Connect OQDe First you must select ‘Configure Oil Quality Display Express’ from the Home Screen. Next, connect the OQDe to your computer using the configuration cable.
Page 53
8.2.6.3 Configuration Options This section describes the various options presented on the OQDe configuration screen. Figure 37 - CADS Default Configurations 8.2.6.4 Date & Time Set the time for the display. This is used to time-stamp log files. You can set the time manually or take the setting from the connected PC or laptop.
Page 54
Figure 38 - CADS Custom Application Configuration These warning and alarm level settings determine when the status will show, green, amber and red. You can set upper and lower limits for oil condition, temperature and rate of change. These warning and alarms levels are optional settings and you can set the levels according to your specifications.
8.3 Installation 8.3.1 Mounting The OQDe has a flange on either side with mounting holes to allow it to be fixed to any suitable flat surface. Once your OQDe is correctly configured, you need to mount it using the flanges on the sides.
Page 56
NOTE. The right-hand connector can be used to connect an OQDe to a Laptop/PC by RS485 using Cables J & M in conjunction, or to other devices for remote monitoring purposes using a Cables M & SB combination or Cable DB (Display to Bare Ends). Cable SD Figure 40 - OQDe Connection 8.3.2.2...
Figure 41 - Wiring diagram for OQDe Power Supply and Data output (4-20mA) 8.3.2.3 Using the Oil Condition analog output Oil condition is output on the black wire and is linearly scaled from 4mA to 20mA. This can easily be converted to the TDN or % Loss Factor scale using the table at the Appendix (Section 13).
8.5.3 Functionality EMC Filtering and fuse protection on input power. Power distribution with individual fusing and EMC filtering on power output to one sensor. Datalog download facility via Wi-Fi to any internet-enabled device. Real time, continuous display of oil quality, oil temperature and Event Code on 7- segment LEDs.
Wi-Fi Activity indicator, Blue LED. 8.5.6 Data Logging Logging interval 5 minutes Clock battery backup 10 years Real time clock Data download Via Wi-Fi 8.5.7 Physical Characteristics Enclosure material Polycarbonate Dimensions 120mm x 66mm x 42mm (L x W X H) Weight 220g Color...
8.5.10 Event Codes The OQDe will analyse the data received from the OQSxG2 Sensor and based on the initial setup or amendments to the configurable parameters can provide a range of warnings or alarms. In addition to the warnings and alarms determining the colour of the oil status LED, the display will also show an event code, identifying possible action required.
9 Oil Quality Gateway 9.1 Introduction The Tan Delta Oil Quality Gateway is a comprehensive networking device. The OQTGateway — coupled with TD Online and/or another 3 party service — provides remote visibility for all connected assets. 9.1.1 IMPORTANT SAFETY NOTES Please pay attention to following safety notes: Gateway is not IECEx certified.
9.2 Gateway Configuration 9.2.1 Set up Configuration USB Before you can use the OQTg it should be configured to work on the particular network which you have chosen to use. This is done by writing the configuration settings to a USB stick and uploading to the device.
Page 63
9.2.1.2 Select required settings As shown in the screenshot below, the Configurator has 3 sections, and you just need to use the one which applies to your chosen network type. Figure 45 - OQTg Configurator Home Screen 9.2.1.2.1 Configure LAN (ethernet) 1.
Page 64
9.2.1.2.2 Configure WLAN (Wi-Fi) 1. Select from either Dynamic (DHCP) or Static – Please consult with your network administrator to ensure correct option is chosen. 2. If static is used, please enter IP Address, Subnet Mask and Gateway Figure 47 - WLAN Settings 3.
Page 65
2. Delete all networks that will not be used from the list. Scroll to bottom of list and click ‘+’ to add new network. List of required parameters is displayed, all information for your specific network will be available online, or from your carrier. 3.
Insert memory stick into USB port of OQTg. Wait for the Amber LED to turn on and off again before removing USB memory stick. Once your network configuration has been loaded, the OQTg will reboot. Wait for green LED to turn on –...
Page 67
legacy setup. Please refer to the correct manual for that product or contact support@tandaltasystems.com for further assistance. Power Sensor 1 Sensor 2 Sensor 3 Gateway 45008 Cable 45002 BK199 45008 BK199 45008 BK199 BK199 45008 BK199 Molex Connector 33481-0201 33472-1206 33472-1206 33472-1206 33482-6201...
9.4 Sensor Configuration Before installation, configure the OQSxG2 to your specifications using the Tan Delta Configuration and Data Management Software (CADS) as described in section 5.1.1.5 of this manual. 9.5 Product Specification 9.5.1 Environmental Specifications Protection Rating IP67 When connected Storage Temperature -45C to +85C Operating Temperature...
9.5.6 Gateway Hub Material Technomelt PA657 Temperature -40C to +85C Ingress Protection IP67 Capacity Connects up to 3 Sensors to Gateway Hub, or 2n+1 sensors where n equals the number of gateway hubs Mounting Mounting kit to gateway device, or by 2 screws direct to bulkhead / wall etc...
10 Configuration And Data Management Software (CADS) 10.1 Introduction The Tan Delta Configuration and Data Software (CADS) is used to configure our core products, the Oil Condition Sensor (OQSxG2), EX GEN II (ATEX, IECEX, US/C, UKEX) Oil Quality Sensor and Oil Quality Display Express (OQDe).
When prompted, select Open folder to view files. Double click the setup file and follow the instructions in the setup wizard. When prompted, click on Install. The first time you launch CADS you will be prompted to install the latest drivers for the Configuration cable.
From the home screen click the cog icon ‘Application Settings’ to bring up the settings menu and select ‘Update From File’. Select ‘OilDb.oils’ from file location and select ‘Save’. Note: At this point you can also select temperature (°C/°F) and oil condition units (Tan Delta Number/Loss Factor/Oil Quality Index) 10.4 Live Readings 10.4.1 Take Readings...
Once you are happy the data is reliable and consistent you can save the data by clicking the save icon in in top right corner. See the data graphing section below for how to view these log files in CADS. 10.4.2 Cleaning If using the Live Readings function to compare different oil samples, please follow our OQSxG2 Cleaning Procedure between each sample.
10.5.2 Data Graphing CADS can be used to graph a log file from CADS or OQDe and show oil condition and temperature trends over time. From the CADS home screen click ‘View Datalog File’ and select the .tsv file you wish to view. Once graph is plotted you can view the Oil Condition and Oil Temperature data, plotted over time.
11 Interface Options Note: Oil condition output in Loss Factor % can be converted to Tan Delta Number. This can be converted to TDN using the following formula where T = TDN, L = Loss Factor %: T = 900 - 20L Temperature outputs in °C and can be converted to °F using the following formula: T(°F) = T(°C) ×...
sequences. It is important to understand that all “bytes” and “byte-counts” referred to below comprise these pairs of ASCII characters when physically transmitted on the bus. The detailed structure of commands is as detailed below. The command structure is as follows: Byte Number Value Description...
“Wm” Write system memory 2 byte address plus 1 byte <length> plus 4 bytes <length> data Note that <length> must be exact and must match the data sent. 1. Read commands allow access to current channel and system settings for confirmation and management of the unit’s operation and current measurements (readings) acquired by the units.
allowing a read of up to 256 addresses from system memory. It commands the Tan Delta unit addressed by <iaddr> to transmit <length> memory bytes starting at <address>. If the command is correctly interpreted, the Tan Delta unit addressed will acknowledge the command with the Ack code, echo the number of bytes it will transmit, and send a response containing all the data requested, followed by a checksum.
address> relative to the software Version No. variable. Version and Serial No. information is as defined below and must be correctly interpreted by the receiving system. If the command is correctly interpreted, the Tan Delta unit addressed will acknowledge the command with the Ack code, echo the number of bytes it will transmit, and send a response containing the data requested, followed by a checksum.
The CAN interface uses a default bit rate of 125 kb/s with 11 bit identifiers. The CAN protocol complies with the CANOpen specification DS301 and the Oil Quality Sensor conforms to CANOpen device profile DS404. Node Guarding and Emergency messages are implemented to ensure high reliability.
Page 81
Bitrate: object (specific entry – read only, fixed 125kbit/s) Number of PDOs: PDO1 synchronous or asynchronous configurable Emergency message: supported Node Guarding: supported Device Profile: DS404 11.2.4.2 Object Dictionary Communication Profile Index Name Type Access Default Comment (HEX) Index DSP404 analog output, 1000 Device Type 0x000E0194...
Page 82
Default Comment 4000 Serial Type 0x01 0x01 = TanDelta via RS485 0x02 = CANopoen via CANbus 0x03 = Modbus RTU via RS485 0x05 = J2939 via CANbus Note: The high nibble of this byte is used for flags which influence the serial communications. See...
Page 83
5 = 125 kbps (default) 6 = 50 kbps 7 = 20 kbps 4004 Sensor 0x05 Writable externally to CAN ID String Sensor “Sensor ID First 7 bytes of ID string String bytes string” 0 - 6 Sensor “Sensor ID Next 7 bytes of ID string String bytes string”...
AI Dec. Digits PV3 0x02 Oil Condition Integer Scaling 6135 AI Interrupt Upper Limit I/P PV Number of entries 0x03 AI Interrupt Upper Limit IP PV8 0d30 End of Life Value (LF units) 6148 AI Span Start Number of entries 0x03 AI Span Start 1 Oil Temp.
Page 85
Message 0x700+ NodeID 0x00 Thus a startup message from a COB-ID of 0x71C indicates that the sensor has a Node ID of 0x1C, or 28 decimal. Bitrate: Object 0x4003, subindex 0. This is, by default, 125kbits/s (CAN bitrate 5) but can be changed –...
Page 86
Command 0x600+ NodeID 0x08 0x40 0x00 0x18 0x05 <Timer <Timer Reply 0x580+ NodeID 0x08 0x40 0x00 0x18 0x05 LSB> MSB> To change the Event Timer value to <NewTime> use the following command <NewTime <NewTime Command 0x600+ NodeID 0x08 0x2E 0x00 0x18 0x05 LSB>...
Page 87
Command 0x080 0x00 Reply 0x580+ NodeID 0x08 <Tb0> <Tb1> <Tb2> <Tb3> <Cb0> <Cb1> <Cb2> <Cb3> Where Tb3 to Tb0 are the most significant to least significant bytes of the 32 bit floating point Oil Temperature value and Cb3 to Cb0 similarly for the Oil Condition. Thus values of 0A,D7,D5,41,7B,14,AE,3F in databytes B0 to B7 equates to hexadecimal values of 41D5D70A and 3FAE147B (byte order rearranged) and floating point values of 26.73C and 1.36%.
Page 88
Command 0x600+ NodeID 0x08 0x2F 0x24 0x61 0x01 <Zb0> <Zb1> <Zb2> <Zb3> Reply 0x580+ NodeID 0x08 0x60 0x24 0x61 0x01 The value to be written is formatted as above. In this way the calibration of the sensor may be adjusted. 11.2.5.7 Reading the Oil Data String from the Oil Database The Oil Condition Cal Data String may be read by performing an SDO read (Domain Upload) from...
Page 89
The value to be written is formatted as above. In this way the calibration of the sensor may be adjusted. The Oil String Data comprises bytes B1 to B7 successively for each Reply message, plus B1 and B2 of the last message, in that order. The example shown above has string 0366EEEF6EC441E6BD081CB619006F775A3F663AF00366063F12A749A303021B6F12663FBF which corresponds to Avia Bantleon Synto.
11.3 Modbus To select Modbus as the preferred communication method, please use the PC/Laptop Software and refer to the appropriate manual. 11.3.1 Hardware The Tan Delta serial communication uses an RS485 multi-drop interface. 11.3.2 Configurable Parameters The serial configuration must be set to 8 bits with no parity and will communicate at 9600 baud. The OQS operates in a slave mode with a default ID of 1 which can be preset to suit on register 11 (0x0B), with the serial device which controls the communications (e.g.
3.5 Characters Time 11.3.5 Function Codes 04 (0x04) Read Input Registers 11.3.5.1 Data format Tan Delta returns all real (non-integer) values as 16 bit signed integers with the value multiplied by 100 (decimal). For example, a temperature reading of 34.14 degrees C would be returned as 3414 decimal (0D56 hex).
Page 92
Oil Data String characters 1 & 2 Oil Data String characters 3 & 4 Oil Data String characters 5 & 6 Oil Data String characters 7 & 8 Oil Data String characters 9 & 10 Oil Data String characters 11 & 12 Oil Data String characters 13 &...
Page 93
Data Lo 0CAB 06 (0x06) Write Single Register 11.3.5.4 Query The Write command specifies the register reference to be preset and allows the remote configuration of channel and system settings for management of the unit’s operation, and modification for use in monitoring. The registers which hold the configuration parameters are: Registers Registers Parameters...
11.3.6 Troubleshooting If you are experiencing a communication issue with a Tan Delta sensors following a ModBus installation, please carefully review the following points; Does whatever monitoring system you are using (Monitoring System) use an RS485, 2 wire, half duplex serial interface? Does the Monitoring System use Modbus RTU, not ASCII? Is the Monitoring System set to use the correct COM port (that is connected to the sensor)? Is the Monitoring System set to use 9600 baud, 8 bits, 1 stop bit with no parity?
Page 95
Does the Monitoring System use any non-standard data formats, e.g. inverted data? If so, the system will not communicate correctly. Is the GND lead of the sensor shared with the GND of the Monitoring System? If either part is driven by a completely different power supply, there may be significantly different voltages between the two and they will not communicate.
11.4 J1939 on CANbus The OQSx Oil Quality Sensor measures the Oil Condition, Oil Temperature and Ambient (Sensor) Temperature. The range is from a nominal -20% to +60% Oil Condition units and -30 to +130C. The measured value is transmitted on the CAN-bus using the J1939 protocol based on the SAE J1939 standards J1939-DA August 2018, J1939-21 October 2018 and J1939-82 June 2015.
11.4.4 J1939 Communication 11.4.4.1 Summary of the J1939 functions and settings J1939 type: J1939 Node Bitrate: Default 250 kb/s, can be configured to 500 kb/s using CADS Industry Group: Function: 46 (decimal) Manufacturer Code: 952 (decimal) Available PGNs: PGN 65262 (0xFEEE) Engine Temperature: here used for Oil Temperature PGN 65279 (0xFEFF) Operator Indicators: here used for Oil Condition PGN 65240 (0xFED8) Commanded Address J1939 Name/Address:...
Page 99
65262 (0xFEEE) reports Oil Temperature in bytes 3 and 4 according to J1939_DA201808 and PGN 65279 (0xFEFF) reports Oil Condition in byte 6. These values are reported as unsigned integers, with an offset of +30 on the temperature and 10* scaling on the oil condition (reported in TDN) so 0x002E = 0d46 reports an oil temperature of 46-30 = 16C.
12 Data Analysis Guide 12.1 Tan Delta Full Spectrum Holistic (FSH) Data Dynamic Maintenance Optimisation (DMO) is the method by which the data can be used to optimise the maintenance intervals for the lubricating oil in the application. Changing the oil at an interval determined by the Display Express means you are only changing the oil when you need to, not at a predetermined schedule when the oil may still be in a useable condition.
Page 101
Figure 57 - Oil Status Indicator In addition to the oil status indicator, the Oil Condition value can be viewed and checked to see the current oil condition against the standard table shown at appendix 10.1 Oil temperature and OLR are also viewable on the Display Express. Oil condition readout Oil Life Remaining (Days) status...
12.1.2 CADS application Data can also be accessed from the Display Express using CADS to either view whilst connected to the display through the in-built graphing screens, or to download to analyse and interrogate offline. Data polling Start / Stop frequency recording data Save logged data...
12.1.4 TD Online TD Online is a cloud-based Internet of Things (IoT) solution that uses a Gateway device connected to the internet to send data from either one or a multiple sensors to a cloud-based viewing platform. TD Online allows live reading of oil condition and oil temperature. Figure 60 - TD Online Live Readings Display The TD online platform allows the user to simply view the data live, or alternatively set alerts and alarms for oil condition in a similar manner to the Display Express, essentially replicating...
Page 104
Figure 61 - TD Online Alerts & Alarms Dashboard Historic data collected from the sensor and presented on TD Online can also be viewed through the Data Explorer menu, including viewing pre-set date ranges or setting a custom period to review.
12.1.5 Digital Data When not used with a Tan Delta preparatory display or gateway solution, the sensor can be configured to communicate by a number of different communication protocols: Tan Delta Protocol on RS485 CAN Open on CANbus Modbus RTU on RS485 J1939 on CANbus For full details of all of these communication protocols, please refer to section 11 of this manual or contact Tan Delta Support for further assistance.
12.1.6 Example Good Sensor Output Readings The graph shown below is a classic “sawtooth” representation of an engine in operation illustrating when oil changes have taken place at checkpoints F, L and R. The green lettered checkpoints are where oil samples would normally be sent for analysis to ensure oil condition is acceptable, with the OQSxG2 installed the need for oil sampling prior to checkpoints F, L and R is not required.
When the oil condition reaches a red alarm status, the oil is at its end of useable life and the machine should not be used until the oil has been changed. condition activating red “Alert” condition activating amber “Check” Figure 66 - OQDe DMO Alert Examples 12.2.2 TD Online TD Online presents oil condition data in percentage loss factor (%LF) values.
Page 108
Figure 68 - TD Online Setting an Alert Click to “Add Smart Rule”. Select “On measurement explicit threshold create alarm” Figure 69 - Adding a Smart Rule Select datapoint (ambTemp / oilTemp / oilCond only). This will autofill fragment & series. Enter the warning and alarm values you wish to trigger a warning and an alarm, then enter an alarm name and click “Create”...
Page 109
Figure 70 - Entering Smart Rule Values This smart rule will now appear in the info tab in the TD Online Cockpit. To set up an email alert from the platform, click “Add Smart Rule” and this time select the option to “On alarm send email”.
Page 110
Figure 72 - Completing Email Alert Details The alert is now set up and will show in the Info tab on TD Online. Figure 73 - Alerts Set Up Page | 108...
12.2.3 Partially / Fully Integrated Sensors Sensors integrated into third party solutions can feed data directly into these systems either using Analog signals or Digital Signal protocols. For more information on the available communication protocols, please contact Tan Delta Support. Oil condition is output in analog format on Pin 3 and is linearly scaled from 4mA to 20mA.
Event Check/ Algorithm Description Code Alert All OK No Sensor Connected – Please Connect the Sensor. Sensor Not Configured – Configure the Sensor via CADS. Display Not Configured – Configure the Display via Insight New Sensor Detected Oil Temperature High – Check Regularly. Current Temperature >= Temp High Warning Level Oil Temperature Very High –...
wear they will both give a small deviation, however as they progress soot will remain linear and TBN will become exponential, therefore we are able to differentiate. The following graphs give examples of different oil degradation patterns allowing you to identify the specific reasons for oil degradation when compared to the expected degradation.
Figure 77 - Water Ingress It’s often difficult to identify water in oil using lab analysis, because as the data above shows, it is only present in the oil at low temperatures. Often sampling will occur after equipment has been running and so water will have been evaporated. If your sensor shows data similar to this, we recommend waiting until the equipment has been shut down and cooled to ambient, and then running it for several minutes before taking a sample for analysis.
12.3.4 Fuel Dilution This is indicated with either a lower decrease in the oil condition over time (ROC) than expected in comparison to the assets usual ROC, or even by an increase in the oil condition that is not directly related to a fluctuation in the oil temperature. Figure 79 - Fuel Dilution In the graph example shown, we have added a comparison line of how a condition such as fuel dilution would look compared to the normal path of oil degradation over time.
The example graph provided shows how the oil is degrading faster than expected (the blue line representing the normal expected behaviour) and a point where this contamination becomes evident as the oil condition deteriorated further. 12.3.6 TBN Decrease A decrease in Total Base Number (TBN) is indicated by the exponential decrease in TDN value with time, also described by the downward curve of the plot.
Page 117
Figure 82 - Oil Change Carried Out Correctly If the TDN value does not return exactly to the same point expected of a new clean oil (2), then it is likely that there was some residual amount of used oil remaining in the system which has mixed with the new clean oil.
Figure 84 - Oil Top-Up Intervention 12.5 Rate of Change (ROC) Calculating Rate of Change (RoC) of oil condition is necessary to utilise some of the more advanced algorithms for integrated oil condition logic. You can use the following logic to set up a third-party device to show the rate of change in the oil condition: Instant RoC = Average change in oil condition for last 5 minutes.
̅ AvgTime Average time at records [ , + OilCond Oil condition at record ̅ AvgOilCond Average oil at records [ , + With the following variable definitions. 12.6 Remaining Useful Life (RUL) Remaining Useful Life is determined as the number of days that the oil can be used until it is considered as being at the end of its useable life.
13 Cleaning Guide 13.1 Cleaning the Tan Delta Sensor 13.1.1 Health & Safety Solvents and Kerosene can be harmful if inhaled and/or ingested. Eye protection and gloves should be worn and products should be used in a well ventilated area. Always follow usage instructions on the packaging.
13.1.2 Introduction If using the sensor in the Tan Delta Mobile Oil Test Kit or if the sensor is being used for bench testing, it is important to always clean the sensor properly between samples. In a fixed installation it is not necessary to clean the sensor due to the sensor being in a live oil zone, however in a situation where you have experienced a very heavy contamination we do recommend that you clean the sensor prior to refilling with oil.
13.1.4 Cleaning Procedure – Loctite 7063 or Similar Solvent Unplug and remove the sensor then use absorbent paper to wipe off the excess oil from the sensor tip and thread. While rotating the sensor, force a short blast of solvent up into each of the holes in the sensor nose, and then give the general exterior a wash on both sides as shown in the pictures below: Figure 85 - Cleaning the Sensor (1)
13.1.5 Cleaning Procedure – Odourless Kerosene Unplug and remove the sensor then use absorbent paper to wipe off the excess oil from the sensor tip and thread. Attach a bottle adaptor to a sample bottle and pour in approximately 15ml of kerosene. Screw in the sensor and shake vigorously for 2 minutes to ensure the kerosene washes up around the tip of the sensor.
13.1.6 Cleaning Procedure - Deep Cleaning Some oil testing, generally where there are extremely high levels of carbon deposits and where the sensor has not been cleaned and has been allowed to dry, can result in the sensor being difficult to clean using our standard methods, in this case we recommend a more thorough deep cleaning process cleaning process as follows: Clean sensor using one of the 2 methods described above.
13.1.7 Cleaning Procedure – Alternative Solvent Test Clean the sensor using one of the following two methods: Rinse the sensor tip thoroughly in odourless kerosene, as described at 13.1.5. Use the deep cleaning method described at 13.1.6. Test a clean oil sample, repeat the cleaning method used above and then re-test a clean oil sample, the readings from both tests should be the same (or very similar), this proves that using one of the failsafe cleaning methods is working.
14 Appendix 14.1 Oil Condition Conversion Chart Oil condition is output as a Loss Factor Percentage and the output is linearly scaled between -20% (4mA) and +60% (20mA). The Loss Factor Percentage can easily be converted to the TDN scale using the following table. (NOTE: The colour scales and alert levels used are set for a typical diesel engine setup.) 4-20mA Loss Factor...
14.2 Oil Temperature Analog Output The table below shows how the oil temperature output (4-20mA) converts to temperature. OQS Output Temperature Conversion 4.20mA value °C °F 19.5 19.99 264.2 19.49 255.2 18.5 18.99 246.2 18.49 237.2 17.5 17.99 228.2 17.49 219.2 16.5 16.99...
14.3 Software License Agreements Software User Agreement: Important - please read carefully before use of any Tan Delta Software. Your use of this computer program is subject to the terms and conditions of the following Software User Agreement. If you do not wish to accept these terms and conditions, do not install or use this Software and please return this Software to the place you obtained it for refund.
Page 129
Modifications: Modifications or enhancements made by Licensor to any Software from time to time may be made available to you at the sole option of Licensor or its Distributors. If the Software is modified by you or merged into other program materials processed or used by solely by you, Licensor and its Distributors shall not have any liability or incur any expense or be affected in any way by any such modification or merger, even if such modification or merger results in the formation of an updated or new work.
Page 130
distributors exceed an amount equal to the price paid for the Software license. This Software is to be used for indication purposes only. Special Attention: If you do not accept the terms and conditions of this license do not install or use the Software. Page | 128...