Parallel connection
The output current is the sum of the output currents of the
units. The output voltage and current of each slave unit are
controllable
with
the constant-voltage
and
constant-curent
controls of the master unit.
1) Turn off power.
2) Remove the short bar (8)-(9) of each slave unit.
3) Connect the master and slave units as shown Fig. 14.
4) Make connection between each unit and load with a cable
of the same length.
5) Ground the GND terminal of the master unit's panel. (The
output
connection
diagram
shows
the
negative
line
grounded.)
The master unit performs constant-voltage operation (CV) and
the slave units constant-current operation (CC).
For remote sensing during parallel operation, make connection
from the @S) and CS) terminals of the master (refer to the
section of remote sensing).
With the rated output voltage is less than 10 V, this connec-
tion is not possible.
Note:
For connection of the parallel operation with different models,
consult agent and our distributor.
Connect of control terminal
Fig. 13
Output connection
l = I, + L + I;
* Set the voltage controls of all slave units at maximum position.
Fig. 14
19