Specifications
Digital DC Inputs
Inputs per Module
Commons per Module
Input Voltage Range
Absolute Max. Voltage
Input Impedance
Input Current
Upper Threshold
Lower Threshold
Max Upper Threshold
Min Lower Threshold
OFF to ON Response
ON to OFF Response
HSC Max. Switching Rate
Number of Channels
Input Ranges
(Selectable)
Safe input voltage range
Nominal Resolution
Input Impedance
(Clamped @ -0.5 VDC to
12 VDC)
10 V, 20 mA, 100 mV: 32,000 counts full scale.
%AI full scale
Max. Over-Current
Open Thermocouple
Detect Current
Analog Outputs
Number of Channels
Output Ranges
Nominal Resolution
Update rate
Minimum 10 V load
Maximum 20 mA load
Analog Outputs;
Output Points Required
Maximum Error at 25C (excluding
zero)
Additional error for temperatures
other than 25C
__________________________________________________________________________________________________________________________________________________________________
10/29/2014
12 Digital DC Inputs / 12 Digital DC Outputs
2 Analog Inputs (High Resolution) / 2 Analog Outputs
12 including 4 configurable HSC inputs
1
12 VDC / 24 VDC
35 VDC Max.
10 k
Positive Logic
Negative Logic
0.8 mA
-1.6 mA
0.3 mA
-2.1 mA
8 VDC
3 VDC
1 ms
1 ms
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
2
0 - 10 VDC
0 – 20 mA
4 – 20 mA
100mV
PT100 RTD,
and J, K, N, T, E, R, S, B Thermocouples
10 VDC: -0.5 V to +15 V
20 mA:
-0.5 V to +6 V
RTD / T/C:
±24 VDC
10V, 20mA, 100mV: 14 Bits
RTD, Thermocouple: 16 Bits
Current Mode:
100 , 35mA Max. Continuous
Voltage Mode:
500 k, 35mA Max. Continuous
RTD / T/C: 20 counts / °C
35 mA
50 nA
2
0-10 VDC,
0-20 mA
12 Bits
Once per PLC scan
1 k
500 
2
0.1%
0.01% / C
Note: Highest usable frequency for PWM output is 65 KHz
Outputs per Module
Commons per Module
Output Type
Absolute Max. Voltage
Output Protection
Max. Output Current per point
Max. Total Current
Max. Output Supply Voltage
Minimum Output Supply Voltage
Max. Voltage Drop at Rated Current
Max. Inrush Current
Min. Load
OFF to ON Response
ON to OFF Response
Output Characteristics
Analog Inputs, High Resolution
Thermocouple
B / R / S
E
T
J
K / N
Thermocouple Common Mode Range
Converter Type
Max. Error at 25C
(*excluding zero)
Max Thermocouple Error
(After Warm Up Time of One Hour)
Conversion Speed, Both Channels
Converted
Conversion Time per Channel
RTD Excitation Current
Required Power (SS)
-22 Steady State Power
Required Power (Inrush)
Primary Power Range
Operating Temperature
-22 Heater Option
Storage Temperature
Relative Humidity
Filtering
Terminal Type
Weight
CE
UL
Clock Accuracy
Page 1 of 4
Digital DC Outputs
12 including 2 configurable PWM outputs
Sourcing / 10 K Pull-Down
28 VDC Max.
Short Circuit
0.5 A
4 A Continuous
30 VDC
10 VDC
0.25 VDC
650 mA per channel
None
1 ms
1 ms
Current Sourcing (Positive Logic)
Temperature Range
2912F to 32.0F (1600C to 0C)
1652F to -328F (900C to -200C)
752.0F to -400.0F (400C to -240C)
1382.0F to -346.0F (750C to -210C)
2498.0F to -400F (1370C to -240C)
Delta Sigma
*4-20 mA
*0-20 mA
*0-10 VDC
RTD (PT100)
0-100 mV
±0.2% (±0.3% below -100C)
10V, 20mA, 100mV: 30 Times/Second
RTD, Thermocouple: 7.5 Times/Second
10V, 20mA, 100mV: 16.7mS
RTD, Thermocouple: 66.7mS
General Specifications
130 mA @ 24 VDC
390mA with heater operating
30 A for 1 ms @ 24 VDC
10 - 30 VDC
-10 to 60 Celsius
-40 to 60 ° Celsius
14 to 140°F (-10 to 60°C)
5 to 95% Non-condensing
15Hz hash (noise) filter
1-128 scan digital running average filter
Screw Type,5 mm Removable
12.5 oz. (354.36)
See Compliance Table at
http://www.heapg.com/Pages/TechSupport/ProductCert.html
+/- Seven Minutes/Month at 20C
Specifications / Installation
1
±10V
±0.10%*
±0.10%*
±0.10%*
±1.0 °C
±0.05%
250 A
ECN # 947

Advertisement

loading
Need help?

Need help?

Do you have a question about the HEXT240C115 and is the answer not in the manual?

Questions and answers

Summary of Contents for HORNER APG HEXT240C115

  • Page 1 MAN0873-07-EN Specifications / Installation XLT OCS Model: HE-XT105 / HEXT240C115 / HEXT240C015 12 Digital DC Inputs / 12 Digital DC Outputs 2 Analog Inputs (High Resolution) / 2 Analog Outputs Specifications Digital DC Inputs Digital DC Outputs Inputs per Module...
  • Page 2 MAN0873-07-EN Specifications / Installation Panel Cut-Out and Dimensions Wiring and Jumpers Note: Max. panel thickness: 5 mm.  Wire according to the type of inputs / outputs used and select the appropriate jumper option. Use Copper Conductors in Field Wiring Only, 60/75° C Refer to XLe/XLt User Manual for panel box information and a handy...
  • Page 3 MAN0873-07-EN Specifications / Installation External DIP Switch Settings (or Jumpers Settings) I/O Register Map As seen when looking at the top of the XLt unit: Refer to Registers Description Section 3 for the location of the External Jumpers. The External DIP Switches are used for termination of the RS-485 ports.
  • Page 4 No part of this publication may be reproduced without the prior agreement and Technical Support written permission of Horner APG, Inc. Information in this document is subject to change without notice. For assistance and manual updates, contact Technical Support at the following...

This manual is also suitable for:

Hext240c015B2btemplate4