4. Press the springs upwards into the ceiling.
UNLOCK
Instructions for automatic test option
1. Instruction for Automatic test function
Once the unit is powered up, a self-diagnostics test
will be automatically initiated:
Check battery, lamp, charge board and transfer fault
all the time.
Run 2H duration test every half a year.
Note: All test functions are preset and no need field
adjustment.
3. Button Test
Press test button once
run a 30s duration test
Press test button twice within 2s
run a 3mins duration test
Press test button 3 times within 2s
run a 30mins duration test
Press test button 4 times within 2s
run a 2H duration test
IP20
24M
5. Finish installation. Switch on.
UNLOCK
2. Dual Colour LED Status Indicator Meaning
Green indicator solid on: Ready/ Normal Operation
Red indicator flashes:
Require service
One flash, 4s pause
Battery disconnected
Two flashes, 4s pause
Low battery voltage
••
Three flashes, 4s pause
Charge board fault
•••
Four flashes, 4s pause
AC/DC transfer fault
••••
Five flashes, 4s pause
LED lamp fault
•••••
Note: When the fault is recovered, press the test button for 2s, the red flashing
indicator will turn green. The fault is cleared, and the unit is back to normal.
Certainty at The Speed of Light
INSTALLATION
MANUAL
UNLOCK
LOCK
LED
EXIT SIGN
EXITBOX-R-B

Advertisement

loading
Need help?

Need help?

Do you have a question about the EXITBOX-R-B and is the answer not in the manual?

Questions and answers

Summary of Contents for Power-Lite EXITBOX-R-B

  • Page 1 30s duration test Press test button twice within 2s run a 3mins duration test Press test button 3 times within 2s run a 30mins duration test Press test button 4 times within 2s run a 2H duration test IP20 EXIT SIGN EXITBOX-R-B...
  • Page 2 Precautions Wall Mount Normal Operation: The green LED indicator stays on when connected to mains supply. The indicator will 1. Release the clip to UNLOCK status by a screwdriver. 2. Connect the battery with quick connector. turn off when the mains supply fails, or when the internal charger malfunctions, or when the luminaire is Slide the cover away from the housing.