4. Press the springs upwards into the ceiling.
UNLOCK
Instructions for automatic test option
1. Instruction for Automatic test function
Once the unit is powered up, a self-diagnostics test
will be automatically initiated:
Check battery, lamp, charge board and transfer fault
•
all the time.
Run 2H duration test every half a year.
•
Note: All test functions are preset and no need field
adjustment.
3. Button Test
Press test button once
run a 30s duration test
Press test button twice within 2s
run a 3mins duration test
Press test button 3 times within 2s
run a 30mins duration test
Press test button 4 times within 2s
run a 2H duration test
IP20
24M
5. Finish installation. Switch on.
UNLOCK
2. Dual Colour LED Status Indicator Meaning
Green indicator solid on: Ready/ Normal Operation
•
Red indicator flashes:
Require service
•
One flash, 4s pause
Battery disconnected
•
Two flashes, 4s pause
Low battery voltage
••
Three flashes, 4s pause
Charge board fault
•••
Four flashes, 4s pause
AC/DC transfer fault
••••
Five flashes, 4s pause
LED lamp fault
•••••
Note: When the fault is recovered, press the test button for 2s, the red flashing
indicator will turn green. The fault is cleared, and the unit is back to normal.
Certainty at The Speed of Light