  • Page 1 JUMO TAROS S46 H Pressure transmitter Operating Manual 40207100T90Z001K000 V1.00/EN/00705001/2020-12-09...
  • Page 3: Table Of Contents

    Contents Contents Safety information..........4 Introduction .
  • Page 4: Safety Information

    Safety information 1 Safety information General This manual contains information that must be observed in the interest of your own safety and to avoid material damage. This information is supported by symbols which are used in this manual as indicated. Please read this manual before starting up the device.
  • Page 5: Introduction

    The pressure transmitter is used to acquire relative and absolute pressures in liquid and gaseous media. The JUMO TAROS S46 H with analog output signal has been developed specifically for hygienic appli- cations. The pressure transmitter has a pressure measuring cell with a piezoresistive silicon sensor. The pressure is converted into an electrical current or voltage signal and output via various electrical connec- tions.
  • Page 6: Identifying The Device Version

    Identifying the device version 3 Identifying the device version Nameplate Position The nameplate is laser-etched on the device surface. Table of contents The nameplate shows important information. This includes: Description Designation on the nameplate Example Device type Type 402071/000 Part no. 00123456 Measuring range 0 to 0.1 bar relative pressure...
  • Page 7: Order Details

    3 Identifying the device version Order details Basic type 402071 JUMO TAROS S46 H – pressure transmitter Basic type extension None a, b Autoclave-compatible version Relative-pressure version without zero point adjustment Special version Input -1 to 0 bar relative pressure -1 to +0.6 bar relative pressure...
  • Page 8 3 Identifying the device version 0 to 25 bar absolute pressure 0 to 40 bar absolute pressure Special measuring range for absolute pressure Special measuring range for relative pressure Output 4 to 20 mA, 2-wire DC 0 to 10 V, three-wire DC 1 to 5 V, three-wire DC 1 to 6 V, three-wire Process connection...
  • Page 9: Accessories

    3 Identifying the device version Order code Order example 402071 - 613 - 374,870 Accessories Item Part no. Cable socket, 4-pole, M12 × 1, straight, with 5 m PVC cable, with PA pressure equalization 00512341 hose Line socket, 4-pole, M12 × 1, straight, with 2-m PVC cable, without pressure compensation 00404585 Line socket, 4-pole, M12 ×...
  • Page 10: Mounting

    Mounting 4 Mounting General information NOTE! Check that the device is compatible with the measurement medium chapter 8.4 "Environmental in- fluences", Page 20. Mounting site • Ensure that the device is fastened securely and with low vibrations • Avoid direct sunlight •...
  • Page 11: Dimensions

    4 Mounting Dimensions 4.2.1 Transmitter with electrical connections Attached cable, length of 2 m (standard) Round plug M12 × 1 L (mm) 604, 607, 613, 616, 685, 686, 997 652, 653 Cable socket DIN EN 175301-803, form A Terminal head Ø...
  • Page 12: Process Connections

    4 Mounting 4.2.2 Process connections Taper socket with union nut DN 25 Taper socket with union nut DN 50 Ø 92 Ø 63 Clamping socket (clamp) DN 25, 32, 40 Clamping socket (clamp) DN 50 Ø 50.5 Ø 64 Tank connection with grooved union nut DN 25 (includ- Tank connection with grooved union nut DN 40 (includ- ing welding socket) ing welding socket)
  • Page 13: Important Information For Usage According To Ehedg

    4 Mounting JUMO PEKA Ø 36 NOTE! Detailed specifications on the JUMO PEKA process connection system can be found in data sheet 409711. Other process connections upon request! Important information for usage according to EHEDG The following process connections are suitable for usage according to EHEDG: •...
  • Page 14: Electrical Connection

    Electrical connection 5 Electrical connection Installation notes NOTE! The electrical connection must only be performed by qualified personnel. The electromagnetic compatibility meets standard DIN EN 61326. Do not connect any additional loads to the voltage supply of the device. The device is not suitable for installation in potentially explosive areas. Connection diagram Connection Terminal assignment...
  • Page 15: Operation

    Operation 6 Operation Zero point adjustment General Information In the case of device versions designed for relative pressure, there is the option of a simple pressure/ zero point adjustment (offset) using a magnet (remanence B ≥ 1 T, e.g. NdFeB dia. 4 mm × 10 mm). This actuates a magnetoresistive switch inside the device when approaching it.
  • Page 16: Maintenance, Cleaning And Returns

    Maintenance, cleaning and returns 7 Maintenance, cleaning and returns Maintenance The pressure transmitter is maintenance-free. In the event of a malfunction, please return the device to the manufacturer together with accurate fault information. Manual cleaning for maintenance or storage The pressure transmitter – especially the parts in contact with the product – must not be damaged. Any damage to the stainless steel membrane must be avoided.
  • Page 17: Technical Data

    Technical data 8 Technical data Mechanical features Materials of parts coming into contact with the pressurized medium Membrane Stainless steel 1.4435 (316 L) O-ring/sealing ring FPM, others available as an optional extra (e.g. EPDM, VMQ) Process connection Stainless steel 1.4404 (316 L) Welding ring Stainless steel 1.4404 (316 L) Materials of other parts...
  • Page 18 8 Technical data Measuring range Linearity Accuracy at Long- Overload Burst term capabili- pressure 20 °C -20 to -20 to stability +80 °C +100 °C % MSP % MSP % MSP % MSP % MSP per year 0 to 2.5 bar relative pressure 0.15 ≤...
  • Page 19: Electrical Data

    8 Technical data Electrical data Voltage supply Two-wire 4 to 20 mA DC 8 to 30 V, nominal voltage DC 24 V Three-wire DC 0 to 10 V DC 11.5 V to 30 V, nominal voltage DC 24 V DC 1 to 5 V DC 10 V to 30 V, nominal voltage DC 24 V DC 1 to 6 V DC 10 V to 30 V, nominal voltage DC 24 V...
  • Page 20: Environmental Influences

    8 Technical data Environmental influences Admissible temperatures Ambient temperature Medium temperature Storage temperature with MSP ≤ 0.4 bar -20 to +85 °C -20 °C to +125 °C -20 to +100 °C with MSP > 0.4 bar -40 to +85 °C -40 to +125 °C -40 to +100 °C MSP = measuring span...
  • Page 21: Approvals And Approval Marks

    8 Technical data Approvals and approval marks Approval Test facility Certificate/certification Inspection basis Valid for mark number EHEDG Research Center EL Class 1/EHEDG- EHEDG design speci- Process connection Weihenstephan for C2000058 fications (doc. 8 – Hy- Brewing and Food gienic Design Clamp DN 25, 32, 40 Quality Principles)
  • Page 22: China Rohs

    China RoHS 9 China RoHS 3URGXFW JURXS  &KLQD ((3 +D]DUGRXV 6XEVWDQFHV ,QIRUPDWLRQ &RPSRQHQW 1DPH +J &G &U 9, 3%'( +RXVLQJ *HKlXVH 3URFHVV FRQQHFWLRQ 3UR]HVVDQVFKOXVV 1XWV 0XWWHU 6FUHZ 6FKUDXEH ^: d 7KLV WDEOH LV SUHSDUHG LQ DFFRUGDQFH ZLWK WKH SURYLVLRQV 6-7  *%7  ,QGLFDWH WKH KD]DUGRXV VXEVWDQFHV LQ DOO KRPRJHQHRXV PDWHULDOV¶...

Table of Contents