UNITED Fire Systems STANDPIPE-PAC SSS-101 Design, Installation, Operation, And Maintenance Manual

Advertisement

Quick Links

MODEL SSS-101
DESIGN, INSTALLATION, OPERATION,
AND MAINTENANCE MANUAL
Serial Number _______________________________________________
Date of Installation ____________Date of Commissioning ___________
UNITED
Fire Systems
Division of UNITED Fire Protection Corporation
1 Mark Road
Kenilworth, NJ USA 07033
Manual Part Number 10-540101-001
908-688-0300
Revision 2.00
www.unitedfiresystems.net
January 2019

Advertisement

loading

Summary of Contents for UNITED Fire Systems STANDPIPE-PAC SSS-101

  • Page 1 MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL Serial Number _______________________________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth, NJ USA 07033 Manual Part Number 10-540101-001 908-688-0300 Revision 2.00 www.unitedfiresystems.net January 2019...
  • Page 2 (THIS SURFACE DELIBERATELY LEFT BLANK)
  • Page 3 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 INDEX Section Description Page INDEX List Of Figures List Of Tables Safety Information Foreword Limited Warranty GENERAL INFORMATION System Purpose Boston FD TCM3-51725 Functional Description...
  • Page 4 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 INSTALLATION (Continued) 3.4.1 Required Supervisory Pressure 3.4.2 Startup 3.4.3 Testing 3.4.4 Placing In Service 3.4.5 Troubleshooting OPERATION Indicators Controls Indications 4.3.1 Normal Operation 4.3.2 Low Pressure In Standpipe 4.3.3...
  • Page 5 This manual contains safety information that is important to know and understand. This information is provided for the safety of installers, operators, and users of the UNITED Fire Systems STANDPIPE-PAC™ equipment. Carefully read, understand, and follow instructions identified by these symbols.
  • Page 6 The data contained in this manual is for information purposes only. UNITED Fire Systems believes this data to be accurate at the time of publication, but the data is published and presented without any guarantee or warranty whatsoever. UNITED Fire Systems disclaims any liability for any use that may be made of the data and information contained in this manual by any and all parties.
  • Page 7 If you break tamper seals applied by UNITED Fire Systems, the sealed parts are not covered. Any problem that is caused by abuse, misuse, or an act of God (such as a flood) is not covered. Also, consequential and incidental damages are not recoverable under this warranty.
  • Page 8 P/N 10-540101-001 1. GENERAL INFORMATION 1.1. System Purpose. The UNITED Fire Systems STANDPIPE-PAC™ Model SSS-101 Standpipe Supervisory System is a fully assembled standpipe supervisory system, including compressor, switches, alarm, and control unit providing one complete zone of standpipe supervision in compliance with Boston FD TCM3-51725. All components are mounted on a sturdy wooden backboard, suitable for hanging at a construction or demolition site.
  • Page 9 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 (15) A manual air release bleed valve for Fire Department use. This device is to be installed near the siamese connection feeding the standpipe. A cap and chain is provided to protect the outlet.
  • Page 10 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 INSTRUCTION NAMEPLATE (15) MANUAL AIR RELEASE BLEED VALVE CAP AND CHAIN Figure 2 – Manual Air Release Bleed Valve Figure 3 – Remote Weatherproof Audible / Amber Visual Device with...
  • Page 11 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 2. DESIGN. The specific STANDPIPE-PAC™ to use is chosen based on the internal volume of the standpipe to be protected, and the desired fill time. See Table 1. Four (4) different units are available, based on compressor size.
  • Page 12 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 2.3. Determining Proper STANDPIPE-PAC™ To Use. See Figure 5. 2.3.1. Find the desired fill time at the bottom of the graph. 2.3.2. Find the standpipe internal volume at the left of the graph.
  • Page 13 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 2.4. Example 1. Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 6” 1.500 1125 TOTAL = 1125 gallons Required work can be performed in 1/2 hour (30 minutes), so a fill time of 1-1/2 hours (90 minutes) is...
  • Page 14 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 2.5. Example 2. Nominal Pipe Size Pipe Length in Feet Gallons per Foot Gallons 2” 0.174 6” 1.500 8” 2.600 1430 TOTAL = 1594 gallons Fill time of 1 hour (60 minutes) required.
  • Page 15 See Paragraph 3.3.5.5 for installation instructions. IMPORTANT Signals from the STANDPIPE-PAC™ unit are NOT fire alarm signals. UNITED Fire Systems recommends that all devices connected to the Notification Appliance Circuit (NAC) of the STANDPIPE-PAC™ unit be clearly differentiated from any fire alarm signals present in the building.
  • Page 16 P/N 10-540101-001 3. INSTALLATION 3.1. Unpacking. Check shipment of the UNITED Fire Systems STANDPIPE-PAC™ system for damage. If there is any damage or missing parts, the transportation company's agent should make a notation to the effect on the Bill of Lading. Claims should be settled directly with the transportation company. Verify that all parts were received in the shipment as ordered.
  • Page 17 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.2.5. Noise. The STANDPIPE-PAC™ unit does emit noise when running. Consideration should be given to locating equipment where normal operating noise does not interfere with building operations.
  • Page 18 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.3.2. Piping. See Figure 9. The piping in BLUE is to be installed by the STANDPIPE-PAC™ system installer. Use Sch. 40 black pipe and Class 150 fittings. The tee to connect the STANDPIPE-PAC™ shall be located after the check valve, and should be located before the drain valve.
  • Page 19 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.3.4. Auxiliary Condensate Drain Device IMPORTANT The Auxiliary Condensate Drain Device does NOT take the place of a standpipe system main drain. Ensure that a main drain valve is properly installed at the lowest point of the standpipe, in an accessible area, where all the water from the standpipe may be properly drained.
  • Page 20 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.3.5. Electrical Installation. DANGER RISK OF ELECTROCUTION Voltages and currents associated with STANDPIPE-PAC™ units are LETHAL. Follow all instructions provided. Work on STANDPIPE-PAC™ unit power MUST be performed ONLY by qualified individuals. All required precautions to prevent contact with live electrical conductors and equipment MUST be taken.
  • Page 21 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.3.5.4. Battery Wiring. See Figure 11. DO NOT connect battery until commissioning. Figure 11 – Battery Wiring Page 14...
  • Page 22 REFER TO THESE INSTRUCTIONS BEFORE WIRING SIGNAL DEVICES. NOTICE UNITED Fire Systems strongly recommends that optional signal wiring be installed by a qualified electrician who is familiar with low-voltage DC signal wiring, preferably experienced with fire alarm notification appliance circuits (NACs).
  • Page 23 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 Figure 12 – Wiring Diagram – Notification Appliance Circuit Nominal Operating Voltage 13.8 VDC 12 VDC Required Device Voltage Rating (NOT 24 VDC or 110 VAC) (1) factory–installed signal horn...
  • Page 24 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 STEP-BY-STEP GUIDE TO INSTALLING ADDITIONAL SIGNAL HORNS TO STANDPIPE-PAC™ 1. Ensure that the STANDPIPE-PAC™ control unit has NOT been powered up, with AC power and batteries disconnected.
  • Page 25 8. See Figure 13.6 Run 14 AWG Solid wires from additional Signal Horn, through raceway and into factory installed Signal Horn back box. NOTE: UNITED Fire Systems recommends using RED, and GRAY or BLACK wires for consistency and polarity identification.
  • Page 26 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 STEP-BY-STEP GUIDE, CONTINUED Figure 13.8 10. See Figures 13.7, 13.8 and Figure 12 Wiring Diagram. Strip ends of wire installed in Step 8. Attach wires removed in Step 5 and wires installed in Step 8 to Signal Horn base plate terminals.
  • Page 27 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 STEP-BY-STEP GUIDE, CONTINUED 14. See Figure 13.11 and Figure 13.12. Replace Signal Horn cover(s). IMPORTANT: Cover(s) MUST be fastened correctly for proper wire contact. Trouble signal will occur if Signal Horn cover(s) is not fastened correctly.
  • Page 28 P/N 10-540101-001 IMPORTANT Signals from the STANDPIPE-PAC™ are NOT fire alarm signals. UNITED Fire Systems recommends that all devices connected to the Notification Appliance Circuit (NAC) of the STANDPIPE-PAC™ unit be clearly differentiated from any fire alarm signals present in the building.
  • Page 29 DO NOT attempt to adjust these switches without authorization from UNITED Fire Systems. These switches have factory-applied tamper seals. DO NOT break these seals. Failure to follow these instructions can lead to improper STANDPIPE-PAC™ operation and will void the factory warranty.
  • Page 30 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.4.3. Testing STEPS TO FOLLOW FOR STANDPIPE-PAC™ SYSTEM TESTING Check Step No. Description When Complete ### VERIFICATIONS BEFORE TESTING ### If control unit dialer is connected to telephone lines, ensure that party receiving signals is aware that testing activities are occurring.
  • Page 31 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 3.4.4. Placing In Service. STEPS TO FOLLOW FOR PLACING STANDPIPE-PAC™ SYSTEM IN SERVICE Check Step No. Description When Complete Verify that compressor disconnect switch (see Figure 1 item 12) is ON.
  • Page 32 Compare color of beads to decal on side Air dryer beads have changed of dryer. If beads are orange, contact absorbed water to their UNITED Fire Systems or trained capacity. Excessive moisture in standpipe. distributor for service. Battery not properly Properly connect battery.
  • Page 33 COMMISSIONING WORKSHEET AND CHECKLIST STANDPIPE-PAC™ SUPERVISORY SYSTEM UFS-238B REVISION 1.00 – PAGE 1 OF 3 DATE LOCATION INFORMATION User Address 1 Address 2 City, State, Zip System STANDPIPE-PAC™ UNIT SERIAL NUMBER PRELIMINARY Have all required on-site parties been notified that audible signals will be sounding? If the control unit dialer is connected to telephone lines, has the party receiving signals been notified that testing will take place? Are all valves on the standpipe CLOSED?
  • Page 34 COMMISSIONING WORKSHEET AND CHECKLIST STANDPIPE-PAC™ SUPERVISORY SYSTEM UFS-238B REVISION 1.00 – PAGE 2 OF 3 LOW PRESSURE SWITCH TEST Is the compressor disconnect switch OFF, and has the unit outlet lockable shutoff valve been moved to CLOSED? Has the button on the test / service device been operated, and is the pressure gauge needle moving DOWN? When the pressure gauge needle reaches approximately 7 PSIG, does the control unit ALARM indicator come ON, and do the signals operate?
  • Page 35 COMMISSIONING WORKSHEET AND CHECKLIST STANDPIPE-PAC™ SUPERVISORY SYSTEM UFS-238B REVISION 1.00 – PAGE 3 OF 3 PLACING IN SERVICE Is the compressor disconnect switch ON, and is the unit lockable shutoff valve OPEN? Have the valves on the Auxiliary Condensate Drain Device been left properly positioned per the nameplate instructions? Is the battery properly connected to the control unit? Is the control unit AC POWER indicator ON, and are all other indicators OFF?
  • Page 36 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 4. OPERATION 4.1 Indicators. 4.1.1. Pressure Gauge. The pressure gauge indicates the approximate pressure produced by the air compressor within the STANDPIPE-PAC™ piping and the standpipe.
  • Page 37 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 4.2.4. Controls Within Control Unit. 4.2.4.1. Pushbutton – “RESET”. This pushbutton resets all control unit circuits. 4.2.4.2. Pushbutton – “ACKNOWLEDGE SILENCE (HOLD 2 SEC.)”.
  • Page 38 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 When pressure drops within the standpipe, the following will be indicated: LOW PRESSURE IN STANDPIPE INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge...
  • Page 39 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 4.4. Procedures 4.4.1. Normal Operation. Under normal operation, no intervention is needed. NORMAL OPERATION INDICATOR or CONTROL ITEM STATUS Visual Indicator Pressure Gauge Indicating between 13 and 18 PSIG...
  • Page 40 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 4.4.5. To Refill Standpipe With Air Pressure After Fire Department Use CAUTION After standpipe-has been filled with water for any reason, ensure that standpipe is completely empty of water before refilling standpipe with air pressure.
  • Page 41 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001 4.4.6. To Test Standpipe with Water Pressure CAUTION After standpipe-has been filled with water for any reason, ensure that standpipe is completely empty of water before refilling standpipe with air pressure.
  • Page 42 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540101-001  Use Auxiliary Condensate Drain Device to drain all water from piping in the vicinity of the STANDPIPE- PAC™.  It may take time for water to migrate from upper floors. Allow sufficient time with drains open for all water to drain.
  • Page 43 The low- and high-limit pressure sensing switches, and the automatic control switch for the air compressor, have been factory-adjusted for proper operation per this manual. DO NOT attempt to adjust these switches without authorization from UNITED Fire Systems. These switches have factory-applied tamper seals. DO NOT break these seals.
  • Page 44 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540000-001 5.1. Weekly. Weekly maintenance consists of visual checks of the status of the STANDPIPE-PAC™ unit and the standpipe itself. What To Do If Status Is...
  • Page 45 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540000-001 * To drain water from piping in vicinity of STANDPIPE-PAC™ while standpipe is pressurized with air by STANDPIPE-PAC™: 1. Unlock and close STANDPIPE-PAC™ outlet valve.
  • Page 46 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540000-001 8. Locate desiccant air dryer on STANDPIPE-PAC™. Locate tab marked PUSH on connecting ring holding aluminum bowl in place (tab orientation may not be immediately visible).
  • Page 47 UNITED FIRE SYSTEMS STANDPIPE-PAC™ MODEL SSS-101 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL REVISION 2.00 P/N 10-540000-001 5.3.2. Replacement of Compressor Filter. The compressor filter keeps dust and other contaminants out of the compressor pump. Quarterly replacement can lengthen the lifespan of the compressor.
  • Page 48 INSPECTION / MAINTENANCE CHECKLIST STANDPIPE-PAC™ SUPERVISORY SYSTEM UFS-236 REVISION 2.00 – PAGE 1 OF 2 Is this (check Monthly Quarterly DATE =or= one): Inspection Maintenance LOCATION INFORMATION User Address 1 Address 2 City, State, Zip System STANDPIPE-PAC UNIT SERIAL NUMBER STEP INTERVAL PROCEDURE...
  • Page 49 INSPECTION / MAINTENANCE CHECKLIST STANDPIPE-PAC™ SUPERVISORY SYSTEM UFS-236 REVISION 2.00 – PAGE 2 OF 2 LIST ALL CORRECTIONS / REPAIRS MADE LIST ALL CORRECTIONS / REPAIRS NEEDED NOTES PRINT NAME SIGNATURE DATE INSPECTOR CUSTOMER Page 42...
  • Page 50 INSTALLATION AND MAINTENANCE INSTRUCTIONS APPENDIX A 3825 Ohio Avenue, St. Charles, Illinois 60174 EPS10 Series Alarm Pressure Switches 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Contact Ratings: 10 A, HP @ 125/250 VAC 8 A, 125/250 VAC (LPCB only) 2.5A @ 6/12/24 VDC Overall Dimensions: See Figure 1 Operating Temperature Range:...
  • Page 51 FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS10-1, EPS10-2 EPS10 EPS10 WIRE TO ALARM WIRE TO ALARM WIRE TO ALARM INDICATING CIRCUIT INDICATING CIRCUIT INDICATING CIRCUIT EPS10EXP EPS10EXP EPS10 OF FIRE ALARM OF FIRE ALARM OF FIRE ALARM CONTROL PANEL CONTROL PANEL CONTROL PANEL WATER SPRINKLER...
  • Page 52 INSTALLATION AND MAINTENANCE INSTRUCTIONS APPENDIX B EPS40 Series and EPS120 Series 3825 Ohio Avenue, St. Charles, Illinois 60174 Supervisory Pressure Switches 1-800-SENSOR2, FAX: 630-377-6495 www.systemsensor.com SPECIFICATIONS Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC 8A @ 125/250 VAC ~ (LPCB ONLY) 2.5A @ 6/12/24 VDC Overall Dimensions: See Figure 1...
  • Page 53 FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS40-1, EPS40-2 FIGURE 3. TYPICAL PIPING DIAGRAM FOR EPS120-1, EPS120-2 WIRE TO SUPERVISORY WIRE TO ALARM INDICATING CIRCUIT EPS120 CIRCUIT OF FIRE ALARM PRESSURE CONTROL PANEL OF FIRE ALARM EPS40 EPS10 SUPPLY CONTROL PANEL SPRINKLER SYSTEM WATER...
  • Page 54 NOTE: The sensor assembly is not field replaceable. Do not attempt to disas- FIGURE 5. ADJUSTMENTS (DUAL-SWITCH MODEL SHOWN): semble these parts. If you have any questions, consult System Sensor. System Switch 2 Sensor recommends careful consideration of the following factors when speci- (Low Switch Switch 1 fying and installing Alarm and Supervisory Pressure Switches.
  • Page 55 (THIS SURFACE DELIBERATELY LEFT BLANK)
  • Page 56 APPENDIX C Installation & Service Instructions 83-050-000 Manual Desiccant Dryer Models Model X03 Richland, MI 49083 Tel: (269) 629-5000 X06, X03, X04, and X25 with Variations and Accessories ISSUED: April, 2013 ! WARNING Supersedes: April, 2007 Doc. #83050000, EN #130200, Rev. 4 To avoid unpredictable system behavior that can cause personal injury and property damage: •...
  • Page 57 Models X06, X03, X04, and X25 d. See replacement parts list for specifics on kit numbers for replacement desiccant. 3. Desiccant regeneration: • Coalescing Filter: Should be used prior to the manual desiccant a. — For silica gel (“000”) units: Pour out used Pink desiccant dryer in any lubricated compressor system which does not utilize onto flat pan.
  • Page 58 Replacement Parts List — TRANSPARENT BOWL Units with Bowl Guards Description Part No. Qty. Part No. Qty. Qty. Cover — — — Screen Assembly — Bowl O-Ring GRP 95-259 GRP-95-256 Tube Assembly w/screen DRP-96-435 Transparent Bowl GRP-95-871 Silica Gel (000) DRP-95-303 3 Bags / .75 lbs.
  • Page 59 wilKerson warrantY SOME OF THE MATERIALS THAT WILL ATTACk POLYCARBONATE PLASTIC BOWLS. Wilkerson products are warranted to be free from defects in material Acetaldehyde Chlorobenzene Methylene chloride and workmanship, under proper use, installation, application and Acetic acid (conc.) Chloroform Methylene salicylate maintenance in accordance with Wilkerson's written recommendations Acetone Cresol...
  • Page 60 APPENDIX E GENERAL AIR PRODUCTS, INC. OIL-LESS COMPRESSOR INSTRUCTION SHEETS NOTE This compressor is intended for installation indoors for use on dry sprinkler systems in accordance with the Standard for Installation of Sprinkler Systems, NFPA 13 and the National Electrical Code, NFPA 70. The compressor should be sized to restore and maintain the air pressure in the sprinkler system in accordance with the requirements in NFPA 13.
  • Page 61 GENERAL AIR PRODUCTS, INC. diameter to minimize pressure drop from the compressor to system. Larger pipe size may be CAUTION required by code and may be substituted with no Inadequate wiring size can cause insufficient adverse effects. Smaller line size must not be used voltage at the compressor during start -up.
  • Page 62 GENERAL AIR PRODUCTS, INC. in pressure) and stopping (cut out pressure) of the proper wiring instruction drawing motor. The pressure switch is factory set. Standard recommended wiring to a starter. models switch is set at 27 psig cut in and 40 psig cut NOTE: Do not run two phases of a three out.
  • Page 63 GENERAL AIR PRODUCTS, INC. Trouble Shooting Guide Symptom Possible Cause(s) Corrective Action Motor hums and runs Low voltage or no voltage Check voltage during attempt slowly or not at all to start. Voltage must be Shorted or open motor winding within +/-10% of nominal Defective check valve voltage to start motor.
  • Page 66 (THIS SURFACE DELIBERATELY LEFT BLANK)
  • Page 67 MODEL SSS-100 DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL Serial Number _______________________________________________ Date of Installation ____________Date of Commissioning ___________ UNITED Fire Systems Division of UNITED Fire Protection Corporation 1 Mark Road Kenilworth, NJ USA 07033 Manual Part Number 10-540001-001 908-688-0300 Revision 2.00 www.unitedfiresystems.net January 2015...