INSTRUCTION
EN
Presigo PDT...C(-2)
i
Read this instruction before installation
and wiring of the product
Pressure transmitter
Presigo PDT...(-2) is a range of pressure transmitters with one or
two pressure sensors, two universal inputs and an RS485 port for
data exchange. The RS485 port can be easily confi gured for either
EXOline or Modbus communication. The transmitter can be used as a
slave unit in an EXOline or Modbus system.
Technical data
Supply voltage
24 V AC/DC ±15 %
Protection class
IP54
Calculated power consumption 2 VA (rms).
Minimum trafo size 7.5 VA.
Data transmission channel
Non-isolated RS485 (max. 100 m)
Overall accuracy, pressure
≤ 1 % full scale
Annual deviation (typical)
P1250 models
±2 Pa
P2500 models
±4 Pa
P7500 models
±20 Pa
Damping (settable)
1...12 s
K-factor (settable)
5...700
Operating temperature range
-25...+50°C
Operating humidity
Max. 95 % RH (non-condensing)
Accessories, included
Two pressure outlets (straight) and
2 m plastic tube. Art. no.: ANS-20
Overvoltage on any terminal
Max. ±18 V (referenced to GND)
Pressure data, Media
Air, non-combustable and non-aggres
sive gases
Universal inputs UI1, UI2
Confi gured as
Ambient
Accuracy
temperature
-25...0°C
±1 K
PT1000*
0...50°C
±0.5 K
-25...0°C
±1 K
Ni1000; 6180 ppm/K
0...50°C
±0.5 K
-
± 1 % full
0...10 V
scale
Digital input
Potential-free contacts on/off (closed=on)
* Factory setting
Pressure ranges (full scale)
Model
Pa (factory
mBar
setting)
PDT12C
PS1 0...1250
0...12.5
PDT25C
PS1 0...2500
0...25
PDT75C
PS1 0...7500
0...75
PS1 0...1250
0...12.5
PDT12C-2
PS2 0...1250
0...12.5
PS1 0...1250
0...12.5
PDT12S25C-2
PS2 0...2500
0...25
PS1 0...2500
0...25
PDT25C-2
PS2 0...2500
0...25
PS1 0...1250
0...12.5
PDT12S75C-2
PS2 0...7500
0...75
NOTE: The suffi x in the name denotes the number of sensors in the unit:
• No suffi x: One sensor (only PS1 is present, reading PS2 related
parameters will yield a zero value reading).
• -2: Two sensors
Presigo PDT...C(-2)
The "S" in the name denotes split/diff erent sensor ranges for PS1 and
PS2.
Flow settings
The following fl ow ranges apply when selecting a unit of measure-
ment for fl ow measurement:
Unit
l/s
m
3
/h (factory setting)
CFM [Ft
3
/min]
Range
Installation
-40...+60°C alt.
NOTE: Use a shielded, twisted pair cable for RS485 communication.
-40...140°F
At high risks of interference, a 120 Ω terminating resistor should be
-40...+60°C alt.
mounted at each end of the communications circuit.
-40...140°F
1.
Mount the transmitter horizontally or vertically on a stable,
-
vibration-free surface. If the unit is installed in a humid environ-
ment, install it vertically with the cable gland edge of the unit
pointing down to allow moisture to escape.
2.
Refer to the graphics below for wiring. Connect the communica-
tion cable to terminals 3(B) and 4(A). Use the leftmost cable
gland for supply voltage and communication. Use the rightmost
cable gland for the universal inputs.
mmH
O
inH
O
3.
Set the DIP-switches to the desired operating mode and param-
2
2
eters. DIP-switch 6 can be used to off set the ELA address to
allow setting up two units at the same time. The transmitter uses
0...125
0...5
the address 1 as a default address for Modbus. For EXOline,
0...250
0...10
dual sensor transmitters use 242:1 as default address and single
0...750
0...30
sensor transmitters use 242:3 as their default address.
0...125
0...5
4.
Power up the unit. Refer to the variable list in the Presigo
0...125
0...5
PDT...C(-2) manual for information on how to access transmitter
data.
0...125
0...5
5.
Let the unit warm up for 10 minutes, then perform a zero-set
0...250
0...10
calibration by pressing the pushbutton.
0...250
0...10
6.
Connect plastic tubes from the ventilation duct to the pressure
inlets.
0...250
0...10
NOTE: A straight cut off nipple must be used for mounting in the
0...125
0...5
ventilation duct.
0...750
0...30
For optimal measuring results, measuring points with turbulent
air fl ow should be avoided. Preferably, measuring should be
performed at a distance of 2 duct diameters before bends and
Flow ranges (full scale)
0...31000
0...65000
0...65000
1

Advertisement

loading

Summary of Contents for Regin Presigo PDT C Series

  • Page 1 INSTRUCTION The “S” in the name denotes split/diff erent sensor ranges for PS1 and Presigo PDT...C(-2) Operating humidity Max. 95 % RH (non-condensing) PS2. Accessories, included Two pressure outlets (straight) and 2 m plastic tube. Art. no.: ANS-20 Flow settings Overvoltage on any terminal Max.
  • Page 2: Push Button

    Pushbutton branching and at 6 duct diameters after bends and branching. Status LEDs Pushbutton Quick press: Zero-set pressure sensors. DIP-switches Wiring NOTE: Be sure to disconnect the pressure tubes before doing this. Sensor 1 RS485 send Let the unit warm up for 10 minutes before attempting zero-set. 1.
  • Page 3 AB Regin, Box 116, 428 22 Kållered, Sweden Confi guration as expansion units to Corrigo P1250 modell ±2 Pa When the transmitter is connected to Regin’s Corrigo controller, it is Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 P2500 modell ±4 Pa confi...
  • Page 4: Installation

    Tryckområden (fullskaliga) Ställ DIP-switcharna till önskat driftläge och önskade parametrar. DIP-switch 6 kan användas för att förskjuta ELA-adressen så att två Statusdioder Tryckknapp enheter kan driftsättas samtidigt. Transmittern har adressen 1 som Modell Pa (fabriks- mBar DIP-switchar Givare 1 fabriksinställning för Modbus. För EXOline har transmittrar med två inställning) RS485 sändnings- givare 242:1 som fabriksinställd adress och transmittrar med en...
  • Page 5 Variabler Konfi gurering som expansionsenhet till Corrigo Statusdioder När transmittern ansluts till Regins regulator Corrigo konfi gureras Tryckknapp Alla EXOline- och Modbusvariabler fi nns listade i manualen för Presigo DIP-switchar den som expansionsenhet via Corrigos display eller genom E tool ©...
  • Page 6 0...5 Verkabelung des Produkts. Änderungen vorbehalten. Kontakt PDT25C PS1 0…2500 0...25 0...250 0...10 AB Regin, Box 116, 428 22 Kållered, Sweden Drucktransmitter PDT75C PS1 0...7500 0...75 0...750 0...30 Tel: +46 31 720 02 00, Fax: +46 31 720 02 50 PS1 0...1250...
  • Page 7 Die Verdrahtung ist in den folgenden Grafi ken dargestellt. Schließen Sie das Kommunikationskabel an die Klemmen 3(B) Status LEDs Status LEDs Pushbutton Pushbutton und 4(A) an. Verwenden Sie die linke Kabeleinführung für die DIP-switches DIP-switches Stromversorgung und Kommunikation. Verwenden Sie für die Sensor 1 Sensor 1 RS485 send...
  • Page 8 DIP-Schalter 6. den werden kann. Konfi guration als Erweiterungseinheit für Corrigo Wenn der Transmitter an den Corrigo-Regler von Regin angeschlossen Inbetriebnahme und Adressänderung ist, wird er über das Corrigo-Display oder über das Application tool© Der Transmitter kann entweder mit den DIP-Schaltern oder über Dieses Produkt trägt das CE-Zeichen.

This manual is also suitable for:

Presigo pdt12cPresigo pdt25cPresigo pdt75cPresigo pdt12c-2Presigo pdt12s25c-2Presigo pdt25c-2 ... Show all