55-048 Relay Module

SPECIFICATIONS

Normal Operating Voltage:
Standby Current:
Alarm Current:
Short Circuit Current, Dry Control Input:
Maximum Resistance, Dry Contact Input:
Temperature Range:
Humidity:
Dimensions:
Accessories:
NOTE: This module is not approved for use in the European Union, at or above 50VAC or 70VDC.

RELAY CONTACT RATINGS:

CURRENT RATING
2 A
3 A
2 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to the
appropriate control panel installation manual for detailed system information.
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

Relay Module, Model 55-048, is to be designed for use in activation of the
types of products that are generally connected to an intelligent fire alarm sys-
tem. It provides two sets of form C contacts that switch together (one DPDT
relay). There is also an input that is capable of monitoring a dry set of contacts
for open or closed conditions. The module also has on-board short circuit iso-
lators to prevent shorts on the signaling line circuit from disabling more than
one device on the intelligent loop.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a listed compat-
ible control panel.

MOUNTING

The module mounts directly to 4-inch square electrical boxes. The box must
have a minimum depth of 2
1
inches. Modules must be mounted with the ar-
8
row facing upward for proper operation of the IR programming tool. Surface
mounted electrical boxes (SMB500) are available from Fike.
D500-78-00
15 to 30 VDC
580 µA max. average (continuous broadcasts)
2.0 mA (red LED on)
30 µA max. average (5 VDC)
100 Ω
32°F to 120°F (0°C to 49°C)
10% to 93% RH Non-condensing
4.675˝ H x 4.275˝ W x 1.4˝ D
Wall cover plate (included); SMB500 Surface Mount Electrical Box; CB500 Control Module Barrier
MAXIMUM VOLTAGE
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
1
LOAD DESCRIPTION
PF = 0.35
Resistive
Resistive
(L/R = 20ms)
PF = 0.35
Resistive
PF = 0.75
PF = 0.35
FIGURE 1.:
LED INDICATOR

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
NOTE: Separate cable entry openings must be used to maintain required
spacing between power limited and non-power limited wiring. Optional
EA-CT may be required to separate power limited and non power limited
wiring in the electrical box.
2.
Set the address on the module per job drawings using the IR configura-
tion tool (model no. EA-CT).
3.
Secure module to electrical box (supplied by installer).
NOTE: All references to power limited represent "Power Limited (Class 2)".
704 S. 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
APPLICATION
Non-coded
Non-coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded
Non-coded
IR RECEIVER
C0166-00
I56-2469-006
R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 55-048 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fike 55-048

  • Page 1 NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION Relay Module, Model 55-048, is to be designed for use in activation of the types of products that are generally connected to an intelligent fire alarm sys- tem.
  • Page 2 – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. D500-78-00 I56-2469-006 ©2013 Fike...

Table of Contents