TA100B & TA110B Signal Conditioners
FORM NO. L-21094-B-0801
(i)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TA100B and is the answer not in the manual?

Questions and answers

Summary of Contents for Nexen TA100B

  • Page 1 WEB CONTROL PRODUCTS User Manual TA100B & TA110B Signal Conditioners FORM NO. L-21094-B-0801...
  • Page 2 In accordance with Nexen’s established policy of constant product improvement, the specifications contained in this manual are subject to change without notice. Technical data listed in this manual are based on the latest information available at the time of printing and are also subject to change without notice.
  • Page 3: Table Of Contents

    ABLE OF ONTENTS ntroduction --------------------------------------------------------------------------------------------------------------------------- 1 Installation ----------------------------------------------------------------------------------------------------------------------------- 1 Electrical Connections ------------------------------------------------------------------------------------------------------------ 2 Calibration for PH16B and UH21 Sensor --------------------------------------------------------------------------------- 3 Specifications ------------------------------------------------------------------------------------------------------------------------ 4 Warranty ------------------------------------------------------------------------------------------------------------------------------- 5 (iii)
  • Page 4: Introduction

    INSTALLATION NOTE: TA100B and TA110B Signal Conditioners are electronic components and should be mounted in a dry, dust free, shock, and vibration free area with an ambient temperature greater than 32° F [0° C] but less than 122° F [50° C].
  • Page 5 TA110B FIGURE 1b FORM NO. L-21094-B-0801...
  • Page 6: Electrical Connections

    ELECTRICAL CONNECTIONS WARNING Before connecting any wires, be sure that AC power is turned off, locked and proper signage applied according to safety regulations. All wiring must be shielded or run through conduit. Wire runs are to be no more than 300 feet. NOTE: Make electrical connections as shown in Figures 2 through 4 for the type of sensor used.
  • Page 7: Calibration For Ph16B And Uh21 Sensor

    1. Check jumper and Range settings (See Figure 5) with chart above and adjust as necessary. JMP1 Range 2 2. Apply power to TA100B or TA110B. 3. Rotate S1 and S2 fully counterclockwise (See Figure 5). 4. Cover the sensor window completely with an...
  • Page 8: Specifications

    6. Uncover the sensor window and adjust R31 until the voltmeter displays 20.0 mA (See Figure 5). Repeat steps 5 and 6 until output current swing is acceptable. SPECIFICATIONS TA100B TA110B ) s i e r i . t f y t i .
  • Page 9: Warranty

    Buyer shall be obligated to pay or which Buyer may incur based upon, related to or arising out of its contracts with its customers or other third parties. In no event shall Nexen be liable for any amount of damages in excess of amounts paid by Buyer for Products or services as to which a breach of contract has been determined to exist.