  • Page 1 MNL205 Rev 1.3...
  • Page 2 READ THIS MANUAL CAREFULLY SAVE ALL INSTRUCTIONS This manual contains important information that you will need to operate the Chameleon™ safely and efficiently. Please read all instructions carefully before installing or operating equipment. Keep this manual handy for easy reference.
  • Page 3: Table Of Contents

    3.1.1— Startup ................................. 7 3.2— Maintenance............................... 7 3.2.1— User Serviceable Components ........................7 3.2.2— Cleaning ..............................8 3.3— Troubleshooting ..............................8 4— Product Specifications ............................9 4.1— Chameleon™ 4.4 Parts ............................ 10 5— Warranty ................................11 Contacting Power Innovations ........................... 13...
  • Page 4 Figure 3—Chameleon™ 4.4 Module (Rear) ........................4 Figure 4—Chameleon™ 4.4 Module (Front) ........................4 Figure 5—Blank Plate ..............................5 Figure 6—Slow Blow Fuse Location on Back of Chameleon 4.4 ................... 7 List of Tables Table 1—Troubleshooting Guide ............................ 8 Table 2—Product Specifications ............................. 9...
  • Page 5: 1-Introduction

    The Chameleon 4.4. comes to you ready to be installed. 1.1—Product Overview The Chameleon™ is a product family of 19-inch rack mounted transformers that provide power conversion and distribution in a data center environment. This manual covers the 4.4 kVA auto-transformer module. Up to two 4.4 kW modules can be installed in a 2U 19-inch rack space for a total of 8.8 kW per shelf (a separately sold accessory).
  • Page 6 Revision 3/5/21 MNL205-1.2 This page intentionally left blank.
  • Page 7: 2-Installation

    32 pilot screws (user provided). Figure 1—Chameleon™ Shelf 2.2—Auto-Transformer Modules The Chameleon™ 4.4 Shelf supports up to two auto-transformer modules (Chameleon 4.4-TRX-020P2A00). ELECTRICAL WARNING Always verify that the Chameleon and any OUTPUT devices are OFF before adding/removing an OUTPUT device.
  • Page 8: Figure 3-Chameleon™ 4.4 Module (Rear)

    The OUTPUTs J1 and J2 correspond with their respective breakers, S1 and S2 (Figure 4). 5. Connect a user provided INPUT cable compatible with an Anderson Power Products Saf-D-Grid 3000 600 V PN 2326G4-BK, Key B, Black receptacle. Figure 3—Chameleon™ 4.4 Module (Rear) Module Pull Handle Input Breaker Figure 4—Chameleon™...
  • Page 9: 2-Removing An Auto-Transformer Module

    4. Remove the module from the shelf remembering to support the module from underneath. 2.2.3—Blank Plate If a module space remains empty, a Blank Plate may be purchased from Power Innovations to act as an air dam for the rack. Follow these instructions to install the Blank Plate: 1.
  • Page 10: Connecting/Disconnecting A Pdu Or Output Device To The Module

    2.3.1—Adding an Output Device/Load 1. Verify that all connected devices are OFF. 2. Verify that the Chameleon™ 4.4 secondary breakers (S1, S2) associated with the OUTPUT receptacles (J1, J2) are OFF. 3. Plug in the device with a user supplied C19 INPUT cable.
  • Page 11: 3-Operation

    There are no user servable components in the Chameleon™ 4.4 auto-transformer modules except for the slow blow fuse (section 3.2.1.1). If there is a problem, replace the transformer with a spare and call Power Innovations for an RMA number. Then return the unit to Power Innovations noting the RMA number.
  • Page 12: 2-Cleaning

    3.3—Troubleshooting Due to its unique design, the Chameleon must be serviced only by authorized personnel, except for the fan fuse (see section 3.2.1.1—). If the unit fails to operate properly, contact Power Innovations customer support. If there is a problem with the Chameleon, refer to Table 1, Troubleshooting Guide before contacting Customer Service. If the problem cannot be resolved, contact Power Innovations Customer Service at 801-785-4123.
  • Page 13: 4-Product Specifications

    Revision 6/29/2023 MNL205-1.3 4—Product Specifications Table 2—Product Specifications Output Capacity (kVA) 4.4 (maximum 8.8 for two auto-transformer modules) Capacity (Watts) 4,400 W (8,800 W maximum with two auto-transformer modules) Nominal Voltage (1 phase) 240 VAC Frequency Connection Method Two C19 locking receptacles Output Circuit Protection 20 amp, Rocker Style Input...
  • Page 14: Chameleon™ 4.4 Parts

    Revision 3/5/21 MNL205-1.2 4.1—Chameleon™ 4.4 Parts The Chameleon™ is composed of various parts. A comprehensive list of included and optional parts can be found in Table 3 below. Table 3—Product Ordering Information Part Description Part Number Transformer Module 4.4 kVA Transformer.
  • Page 15: 5-Warranty

    Repair or Replacement If any part or portion of the Power Innovations product fails to conform to the Warranty within the Warranty period, Power Innovations, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part.
  • Page 16 The product must not have been previously altered, repaired, or serviced by anyone other than a service facility authorized by Power Innovations to render such service, and the serial number of the product must not have been altered or removed. To be covered by this warranty, the product will not have been subjected to accident, misuse or abuse, or operated contrary to the instructions contained in the User’s Manual.
  • Page 17: Contacting Power Innovations

    If there are any questions or comments about this product, please feel free to contact us. Power Innovations International, Inc. 801) 785-4123 Fax: (801) 785-6999 Email: support@power-innovations.com Copyright © 2020 Power Innovations International, Inc. American Fork, UT, USA All rights reserved. Building a Safer and Greener Future...