7. Lower container, you may have to place the container on its
empty carton to prevent the UN•LIME from flowing back into
the container.
8. Let UN•LIME remain in the heater for 5 minutes and then
lower the container to the "Drain" Position, see Figure 16.
9. Deliming activity is indicated by foaming on the surface of the
UN•LIME. If there is deliming activity, repeat steps 6 thru 8.
Normally, lime removal will be completed within one hour. Severe
build-up of lime may take longer than an hour to complete
descaling.
Note: To check UN•LIME for continued use, place some scale or
white chalk in a glass with a small amount of UN•LIME. If the
material is vigorously dissolved by the UN•LIME, it can be reused;
if not, the UN•LIME should be replaced.
FIGURE 16

IGNITION MODULE SYSTEM

Before calling your service agent, the following checklist should
be examined to eliminate obvious problems from those requiring
replacement or servicing.
— Check that "main manual gas shutoff valve" is fully open and
that gas service has not been interrupted.
— Check that after following the appliance OPERATING
INSTRUCTIONS, the "Top Knob" of the appliance gas valve is
in "ON" position.
— Check electrical supply to the appliance for possible blown
(or tripped) fusing or power interruption.
— Is the water temperature in tank below the thermostat dial
setting on the appliance thermostat (calling for heat)?
— It is possible that the high limit (E.C.O.) has functioned to
shut off the appliance. See FEATURES — Water Temperature
Control for reset procedure. Contact your serviceman if limit
continues to function to shut off appliance.

SYSTEM DIAGNOSTICS

Your water heater is equipped with an ignition module that
incorporates a diagnostic system to assist in troubleshooting
the appliance. The indicator codes on the ignition module are
as follows:
1 flash
System lockout (retries or cycles exceeded)
2 flashes
Pressure switch stuck close
3 flashes
Pressure switch stuck open
4 flashes
Open on high temperature limit switch (eco)
6 flashes
115 volt AC power reversed (check polarity)
7 flashes
Low flame sense signal (make sure flame
sensor is in burner flame)
8 flashes
Check ignitor
continuous flash -> continuous flame sensed > 5 seconds
without gas valve
continuous on -> internal control failure - replace ignition control
module.
Use this diagnostic system in conjunction with the
"OPERATIONAL CHECKLIST" and the "SEQUENCE OF
OPERATION" to troubleshoot the appliance.

SERVICE

The installer may be able to observe and correct certain problems
which may arise when the unit is put into operation. HOWEVER,
it is recommended that only qualified servicemen, using
appropriate test equipment, be allowed to service the heater.
As preliminary step, check wiring against diagram, check for
grounded, broken or loose wires. Check all wire ends to be
sure that they are making good contact.

ELECTRICAL SERVICING

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.

REPLACEMENT PARTS

Replacement parts may be ordered through A.O. Smith dealers,
authorized servicers or distributors. Refer to the Yellow Pages
for where to call or contact the A.O. Smith Water Products
Company, Product Service Division, 5621 West 115th Street, Alsip,
IL 60803, 1-800- 433-2545. When ordering parts be sure to state
the quantity, part number and description of the item(s) including
the complete model and serial number as it appears on the
product. Refer to the parts list for more information.