Technical information

Rating (A) 16A/250V AC resistive load
4A/250V AC inductive load
Voltage(V) 220-240V 50/60Hz
IP RATING IP20 EN 60529
Mounting 35mm top hat din rail
Torque (switch terminals) 0.8Nm
Maximum cable 4mm²
Memory locations 16 ON 16 OFF
Power consumption 7.5VA
Display LCD
Minimum setting 1 minute*
Bell function *30s (set ON and OFF time the same)
Contacts 1 changeover contact (3,4,5)
Battery Lithium battery, 150H reserve
Ambient temperature -10~ +40°C
Ambient humidity 35~85%RH
Weight 150g
Accuracy ≤2sec/day(at25°C)
Complies with EN 60730
IMPORTANT VOLTAGE FREE CONTACTS
  1. Dimensions
    Dimensions
    Connections (VOLTAGE FREE CONTACTS)
  2. Time Switch must be installed by a qualified electrician in accordance with the current IET Wiring Regulations BS 7671.
  3. Total load must not exceed the rating of the time switch or any additional limitation.
  4. For loads greater than above, we recommend an installation contactor is used, switched by the TD1 Time Switch.

BUTTON FUNCTIONS

BUTTON FUNCTION
ON LED Illuminates when switching program is on
Program button
Clock /Time button
D+ Day
H+ Hour
M+ Minute
RESET
This will DELETE ALL settings!
By pressing D+ and H+ for 3sec this will also delete all settings!
MANUAL Manual switch for the following settings:
ON, ON AUTO, OFF, AUTO OFF

Initial setup

  1. Connect SUPPLY to terminals 1 and 2 and LOAD to terminals 4 and 5.
    Torque connections to 0.8Nm. Loose connections cause fires!!!!
  2. Press and hold "RESET" button for 3seconds to initiate programing functions.

Setting the DAY and TIME

Default setting is 24H mode if you wish to change to 12H press "" button for 5 sec, and LCD will display AM. If you want to change back to 24H mode press ""button 5 sec
Step Key Setting the DAY
1 Press and hold and press D+ TO CHANGE DAY The day is displayed at the top of the LCD display
Setting the TIME
2 Press and hold and press H+ TO CHANGE HOUR Setting the hour
3 Press and hold and press M+ TO CHANGE MINUTE Setting the minutes
4 Press To return to display

Before you start programming the time clock select the function required:
PROGRAMMING, PULSE OR COUNTDOWN (Only 1 of the 3 options can be used simultaneously).

Programming

Step Key Programming ON memory locations
1 Press Setting 1 ON time (display 1 ON)
2 Press H+ or M+ Set hours and minutes
3 Press D+ DEFAULT IS EVERY DAY OF THE WEEK or you can select one of the following options by pressing the D+ button
OPTIONS: MO-FR,MO-SA,SA SU,MO-WE,TH-SA,MO WE FR,TU TH SA
Step Key Programming OFF memory locations
4 Press Setting 1 OFF time (display 1 OFF)
5 Press H+ or M+ Set hours and minutes
6 Press D+ DEFAULT IS EVERY DAY OF THE WEEK or you can select one of the following options by pressing the D+ button
OPTIONS: MO-FR,MO-SA,SA SU,MO-WE,TH-SA,MO WE FR,TU TH SA
7 Repeat step 2-6 Set 2-16 ON/OFF times
8 Press End
To review programmed time settings press

FOR THE PROGRAMMED TIMES TO OPERATE AUTOMATICALLY THE TIMER MUST BE SET TO "AUTO OFF"
(ON LED is NOT ILLUMINATED)
IF YOU ARE WITHIN THE SWITCHING TIMES YOU SHOULD SET THE TIMER TO "AUTO ON"
(ON LED is ILLUMINATED)
MANUAL OVERRIDE
Press "MANUAL" to turn ON, ON AUTO, OFF, AUTO OFF programmed times

Pulse

("P" displayed at left hand side of LCD)

Step Key Programming ON memory location
1 Press and HOLD H+ and M+ Enter pulse setting ("P" will display LHS)
2 Press and H+ or M+ Set pulse time range: 1sec to 59min 59sec
3 Press and MANUAL To confirm pulse time range ("P" flashes)
4 Press P Into setting 1 ON time (display 1 ON)
5 Press H+/M+ Set hours and minutes
6 Press D+ DEFAULT IS EVERY DAY OF THE WEEK or you can select one of the following options by pressing the D+ button
OPTIONS: MO-FR,MO-SA,SA SU,MO-WE,TH-SA,MO WE FR,TU TH SA
7 Repeat steps 4-9 Set 2-18 ON PULSE programs (OFF programs not required!)
8 Press End ("P" will continue to flash when PULSE program is set)
9 Press and HOLD H+ and M+ Exit PULSE function

Countdown

("d" displays in bottom LHC)
This is a manual operation only initiated by pressing the "MANUAL" button on the TD1

Step Key Programming COUNTDOWN function
1 Press and HOLD P and Enter COUNTDOWN setting ("d" displays in bottom LHC)
2 Press and H+ or M+ Set COUNTDOWN time range: 1sec to 99min 59sec
3 Press MANUAL Start COUNTDOWN
4 Press P Return to start of COUNTDOWN
5 Press and HOLD P and End COUNTDOWN ("d" no longer displayed in bottom LHC)

PAUSE program settings

Step Key Programming PAUSE function
1 Press and MANUAL for 3s Permanent "AUTO OFF" state("┌" flashes in bottom LHC)
2 Press and MANUAL for 3s To restore "AUTO" settings
PAUSE function can only be accessed when "AUTO ON" or "AUTO OFF" is displayed on the LCD

Auto time correction

("7d" displayed at left hand side of LCD)

Step Key Programming ON memory location
1 Press P and MANUAL Into count
2 Press D+ Setting -30s to +30s
3 Press Confirm

Testing

  1. On completion of the installation, it must be tested in accordance with the latest edition of the IET Wiring Regulations for Electrical Installations (BS 7671).

Environment

WASTE ELECTRICAL PRODUCTS SHOULD NOT BE DISPOSED OF IN HOUSEHOLD WASTE. CONTACT YOUR RETAILER OR LOCAL AUTHORITY FOR RECYCLING INFORMATION.

www.fusebox.co.uk

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download FuseBox TD1 -Din Rail Mounted 7 Day Time LCD Switch Manual

Advertisement

Need Assistance?

Do you have a question about the TD1 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents