No parts of this publication may be copied, redistributed or published by means of photocopying, electronic copying or retransmission, printing or similar without the written consent of AddSecure Smart Rescue Nordic AddSecure Smart Rescue Nordic AB reserves the right to change the publication or the products described in the publication without prior notice.
Subnet Mask:255.255.255.0 Press OK. Now you can connect a network cable between the PC and CAT12CE for programing via the WEB interface. To configure alarm terminal CAT12 CE, a WEB interface is used located at the URL http://<CAT12CE ip address>.
OK - When the user wants changes made to be saved/implemented, he clicks on this button. • Cancel - When the user does not want changes made to be saved, he clicks on this button. 60206560-100-SE Sid: 5/51 AddSecure Smart Rescue...
In the Password field, type a new password To confirm the new password, type it in the Password field again. Click OK. After a new user is created, you receive the following informational message: User <name> successfully added 60206560-100-SE Sid: 6/51 AddSecure Smart Rescue...
Removal is confirmed by pressing OK. A dialog indicates removed user with text: User <user name> removed If you try to remove logged-in users, you receive the following error message: Cannot remove currently logged user 60206560-100-SE Sid: 7/51 AddSecure Smart Rescue...
Number of retries - Number of retries in case of failed connection retries are recommended and set by default. If alarms cannot be transmitted, the queue is saved and sent as soon as CAT12CE has contact with the receiver again •...
GPRS drop-down menu. using the • APN - Name - The name of the access point via GSM data. AddSecure Link Telia mobiflex.ts.m2m AddSecure Link, up to 1 GB: mobiflex.tele2.m2m AddSecure Link, over 1 GB: mobiflex.4g.tele2.m2m Maingate open network: maingate.telia.se Maingate end network: maingatelan.telia.se...
Modem model Model of radio in the TC8000 modem • Fw... Radio software version • Number of retries the number of times CAT12CE will try to send a message if it does not succeed the first time • Timeout between retries 60206560-100-SE...
Connection of Pocsag Settings to handle POCSAG transmitters connected to CAT12CE via the rs485 port. POCSAG can be used to send alarms to pagers. • Transmitter frequency Displays the frequency of the transmitter used in paging. This value can be changed.
Alarm phone / V22M. Activation of the function is done by selecting Alarm Phone / V22M in menu Inputs\Extension card. Below is the default connected phone setting. • Volume speakers. Speaker volume to connected phone. 60206560-100-SE Sid: 12/51 AddSecure Smart Rescue...
If you want to clear this queue, to prevent the alarms from being sent, clear the check box next to the alarm recipient's name. Note! Remember to activate the check box again if you want to re-establish communication with the alarm receiver. 60206560-100-SE Sid: 13/51 AddSecure Smart Rescue...
The alarm transmitter sends pings message for control of communication routes and alarms for various alarm events e.g. activated alarm input. Example. CAT12CE communicates with Telecall alarm receiver Primary alarm message route via Ethernet IP and secondary via GSM modem 4.1.2 SMS message Alarms can be sent as SMS to any mobile number.
Securitas - Selected if alarms are to be sent to Securitas Sweden. Securitas has 2 receivers that are the same for CAT12CE across the country. Alarm routes with IP addresses, etc. are automatically configured when selecting Securitas as the receiver.
• All paths offline - Specify which output to activate by marking the relevant check box. Out 2 should be used for this function. (Ut1 is used for operation indication, General system failure Ut4) 60206560-100-SE Sid: 16/51 AddSecure Smart Rescue...
An existing alarm route is removed by clicking on the remove icon for the alarm route. A dialog to confirm the removal of the alarm path is shown and pressing ok confirms the removal. Cansel aborts the action. 60206560-100-SE Sid: 17/51 AddSecure Smart Rescue...
Encryption - Specifies whether (box checked) and how to use SSL encryption. • Test alarm path – When the button is pressed, a test message is sent over the alarm route. This is not an alarm, only a ping message to the recipient. 60206560-100-SE Sid: 18/51 AddSecure Smart Rescue...
Transmitter - ID - Sender ID displayed in e-mail at the recipient. • Sender address - Here you can enter the name of the sender. Address must be valid e-mail format. (xxxx@xxxxx.xx) Information for the remaining settings depends on the e-mail provider used. 60206560-100-SE Sid: 19/51 AddSecure Smart Rescue...
Transmitter ID - Sender ID displayed in SMS at the recipient. Add number. • Name - Names that appear in the list of sms recipients. • Number – Phone number to which SMS should be sent. 60206560-100-SE Sid: 20/51 AddSecure Smart Rescue...
Name - Names that appear in the list of message recipients. • Number – Number of Tetra terminal to which the message should be sent and setting for ISSI or MSISDN • Type - Choice to send SDS or Flash SDS 60206560-100-SE Sid: 21/51 AddSecure Smart Rescue...
Name - Name displayed in Pocsag recipient list • Address - Enter the address of the pager, not necessary if ESPA is selected as type • RIC - RIC calculated based on address and index 60206560-100-SE Sid: 22/51 AddSecure Smart Rescue...
Maximum 59 hours, 59 minutes, 59 seconds and 999 ms. • Priority - Selection of priority for handling in alarm queue. High priority takes precedence over low. Fire alarms shall be set as a high priority 60206560-100-SE Sid: 23/51 AddSecure Smart Rescue...
Page 24
Save - Changes made are saved. If the button is not pressed before going to other menu, the changes made are not stored. Note: Low battery voltage and AC OK are special inputs. Configuration is defined under the System section. 60206560-100-SE Sid: 24/51 AddSecure Smart Rescue...
Examples of values depending on the end resistors used. Alarm resistors of 1 kΩ shall not be used when end resitor is 4,7 or 5,6 kΩ,. Input mode 1 kΩ 2.2 kΩ 3 kΩ 4.7 kΩ 5.6 kΩ Short circuit Normal Alarm 18,0 18,0 18,0 18,0 18,0 Break 20,0 20,0 20,0 20,0 20,0 60206560-100-SE Sid: 25/51 AddSecure Smart Rescue...
Input Sabotage The tamper switch indicates that the CAT12CE cover has been opened Configuration according to 5.1 Inputs with the exception of: • Type - Choice Balanced is missing. The setting is "Normally Closed" by default. 60206560-100-SE Sid: 26/51 AddSecure Smart Rescue...
(Out1 is used for operation indication, General system failure Out4) • Save - Changes made are saved. If the button is not pressed before the page is left, the changes made are not stored. 60206560-100-SE Sid: 27/51 AddSecure Smart Rescue...
Battery low - Shows the status of input Low battery voltage. • AC OK - Shows the status of input Mains voltage OK. • Refresh after {count}sec - Status can be regularly updated by time set by using the arrow buttons. 60206560-100-SE Sid: 29/51 AddSecure Smart Rescue...
Panel - Choose whether to connect the V22M card to the ASSA Arx or Galaxy/other central unit • Send alarms – mark the check box to send alarms in case of errors in communication with extension board. Remaining fields - see 5.1 Inputs 60206560-100-SE Sid: 30/51 AddSecure Smart Rescue...
Control via SMS/Tetra or Telecall – mark the check box to be able to control the output via sms command and Tetra status message or from a AddSecure Telecall system. Password etc. for sms is defined under System To control from Telecall, contact AddSecure Smart Rescue for further information.
For the operation indication on Output 1, this shall be set to Level and inverted Output used for All alarm paths should be set to Level Output 4 is activated in case of system failures such as configuration errors and should be set to Level 60206560-100-SE Sid: 32/51 AddSecure Smart Rescue...
This tab provides information about the alarm terminal that is not specified elsewhere. Alarm terminal CAT12 CE - System • CAT12CE Name - Object name, shown in the upper right corner along with the alarm terminal system time. • SMS password - Password for using SMS commands.
Page 34
• UPS Battery low - Button for configuring battery alarms from connected power supply. Configuration similar to inputs • UPS Power fault - Button for configuring supply voltage alarms. Configuration similar to inputs 60206560-100-SE Sid: 34/51 AddSecure Smart Rescue...
Setting parameters can only be done when the channel is idle. Activate RS232 port 1 / 2, Activate RS485 port 3 Alarm terminal CAT12CE can communicate with external devices using RS232 and RS485. Connecting to CAT12CE RS232 serial port For connection to devices using 9-pin D-sub to CAT12CE CH1/CH2...
Page 36
Stop Bit - Number of stop bits, 1 or 2 Listening Port – Port for connection to IP Settings according to the above should be made by service technician or other person experienced in serial communication. 60206560-100-SE Sid: 36/51 AddSecure Smart Rescue...
Page 37
See Transparent port for information about the first four settings Event code - Alarm code to be sent to the receiver if CAT12CE loses communication with the Tetra modem Assigned ARCs - Alarm receivers that communication faults with the Tetra modem should be sent to...
Page 38
ESPA Variant - Here you can choose to use either standard ESPA 444 or EBL-Talk which is a special protocol for specific EBL fire alarm centrals. CAT12CE only receives fire information from EBL. Local address - CAT12CE device address in ESPA communication.
Page 39
Event code Alarm code to be sent to the receiver if in case of alarm informationcomplete information is sent its own field in the protocol and works only with AddSecure Smart Rescue Telecall as receiver Com,. Error coe, Comm. Restore code & section...
Page 40
Communication with Central Equipment Sentrion S3/S4. The connection is made via rs232 (Note. Use common ground point to Sentrion/CAT12CE to avoid communication disturbance). Event code - Alarm code to be sent to the receiver if CAT12CE loses communication with Sentrion. By default set to 87, but this can be changed freely.
Page 41
RIIO Function for connection to serial printer port to receive alarm information. This can be used with AddSeccure Blis Boss or other systems to send alarm information via CAT12CE Text encoding – Selectin of encoding for the communication Event code Alarm code to be sent to the ARC when a message is received on the serial port...
System. Tab: Shared In/Out CAT12CE, in combination with Nova system, can act as a central unit (CCU) for access and burglary and alarm transmitters. It sets out the inputs and outputs to belong to CAT12CE or Nova 60206560-100-SE Sid: 42/51...
Selected synchronization with SNTP Server, the server's IP address and the synchronization interval to use are specified. If synchronization with Alarm Receivers is selected, the time is synchronized with the time specified in the ARCs response to the ping request. Synchronization takes place 2 times a day. 60206560-100-SE Sid: 43/51 AddSecure Smart Rescue...
System Tab: Configuration • Export Configuration - Press the Export button to save the CAT12CE configuration file to your computer. • Import Configuration - Press the Browse button... to download the configuration file from your computer. Then press the Import button, the configuration file loads.
The current status of the alarm terminal, the program version of the alarm terminal and whether any expansion board is installed. V22M info: displayed only if V22M extension board is enabled. Here you can see the fw. version of the card from version 15 and up 60206560-100-SE Sid: 45/51 AddSecure Smart Rescue...
Browsing the log and clearing the log is done using buttons at the bottom of the image The event log can be saved to a file in html format that can be opened and printed in browsers. 60206560-100-SE Sid: 46/51 AddSecure Smart Rescue...
Press Upload to load the file to CAT12CE. Prepared version Shows version when the file is loaded Press Upgrade to start upgrading the fw Now CAT12CE will restart and the browser will count down for reconnection. 60206560-100-SE Sid: 47/51 AddSecure Smart Rescue...
SMS MANAGEMENT When sending SMS to alarm terminal CAT12CE, no distinction is made between lowercase or uppercase letters. The primary password is checked only if it is configured on the system page. A secondary password can also be configured on the system page to disconnect the SMS function.
Page 49
Outputs can be controlled via SMS only if they are not used for other signalling (e.g. ethernet loss) and provided that SMS control has been configured on the output page (Checked via ticked SMS checkbox). Example of SMS request to CAT12CE: <password>, out1 on, out3 off, out4 on Tetra status message...