Quick Links

Slim Type
HSR-2SL
2-Phase Solid State Relay
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
Safety information
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
DANGER indicates an imminently hazardous situation which, if
DANGER
not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation which, if
WARNING
not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, if
CAUTION
not avoided, may result in minor or moderate injury
DANGER
Do not touch or contact the input/output terminals because they may cause electric shock.
WARNING
•Before you use, please read safety precautions carefully, and use this product properly.
• If you are concerned about serious accident due to the malfunction of products, please
install the external safety equipment
• To prevent defection or malfunction of this product, supply proper power voltage in
accordance with the rating.
• To prevent electric shock or devise malfunction of this product, do not supply the
power until the wiring is completed.
• Reassemble this product while the power is off. Otherwise, it may cause malfunction or
electric shock.
• If the user uses the product with methods other than specified by the manufacturer,
it will brings the bodily injuries or property damages.
• Due to the danger of electric shock, please use this product installed onto a panel
while an electric current is applied.
CAUTION
• Before using the product you have purchased, please check out if it is exactly what you ordered.
• Do not use this product at any place with corrosive gas (especially noxious gas or
ammonia) or flammable gas.
• Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents.
• Do not use this product at any place with excessive induction trouble, static electricity
or magnetic noise.
• Do not use this product at any place with possible thermal accumulation due to direct
sunlight or heat radiation.
• When the product gets wet, the inspection is essential because there is a danger of
an electric leakage or fire.
•Do not connect anything to the unused terminals.
•For DC types, please connect wires at the correct position after checking polarity of terminal.
•When product is disposed, treat as a industrial waste.
•Since a heat sink corner is sharp, it would lead to a serious injury.
• When electricity flows, desktop or heat sink's corner temperature would be high so
that it could lead people to suffer burns.
•When it is out of order, please separate SSR from head sink and change only SSR.
•This model has epoxy molding for the purpose of safety, reliability and extends of the life.
• When applying an electric current, SSR is heated more and more. So, it has more durable
at low heat sink temperature and ambient temperature.
Suffix code
Model
Code
HSR-2SL
   
Input Control Voltage D
25
Rated load current
40
2
Rated load voltage
4
Operation method
Z
Specification
Low
HSR-2SLD252Z
Model
High
HSR-2SLD254Z
Low
Rated Load
Voltage
High
Low
Peak Voltage
(Non-repetition)
High
Rated load current
Frequency
Low
Surge current
(8.3 ms No repeti t i o n)
High
Leakage current
Output ON voltage dropping
Low
Rated impulse
withstand voltage
High
Information
2-Phase Solid State Relay
4 - 32 V d.c.
25 A
40 A
90 - 264 V a.c. (Low voltage)
90 - 480 V a.c. (High voltage)
Zero Cross Switching (Standard product)
HSR-2SLD402Z
HSR-2SLD404Z
90 - 264 V a.c.
90 - 480 V a.c.
600 V
1,200 V
25 A
40 A
50/60 Hz (Dual usage)
260 A
420 A
250 A
370 A
10 ㎃ max
1.8 V (R.M.S) max
4 ㎸
6 ㎸
HEAD OFFICE
Specification
Rated Voltage
Operating Voltage Range
Impedance
Operation Voltage
Reset Voltage
Input Current
Rated Voltage
Operating Voltage Range
Power consumption Max 25 ㎃, Max 40 ㎃ in case of Alarm output (Base on 24 V d.c.)
Collector pressure
Maximum rated
through current
Max. collector
power consumption
Output type
Transistor open collector (Hi at detection of problem)
Response Time
1/2 Cycle + 1 ms max. ("R"type below 1 ms)
Insulating Resistance
500 V d.c., 100 ㏁ (Between the input / output and case)
Dielectric strength
Vibration resistance
10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
Shock resistance
Storage Temperature
Ambient Temperature
Ambient Humidity
Pollution level grade
Degree of protection
Usage
Accepted standard
● HSR_2SLD 외형 및 패널 가공치수 (단위:mm)
Certification
Weight (with box)
Approx. 1,000 g
79.0
Dimension
4.5
● HSR_2SLD 외형 및 패널 가공치수 (단위:mm)
● HSR_2SLD 외형 및 패널 가공치수 (단위:mm)
13.85
 HSR-2SLD252Z, 254Z
79.0
79.0
4.5
13.85
20.5
10.0
95.0
4.5
20.5
13.85
20.5
10.0
10.0
 HSR-2SLD402Z
95.0
95.0
4.5
13.85
20.5
10.0
● HSR_2SLD 404Z 외형 및 패널 가공치수 (단위:mm)
20.5
20.5
※ DIN Rail 사용불가
10.0
10.0
 HSR-2SLD404Z
110.0
● HSR_2SLD 404Z 외형 및 패널 가공치수 (단위:mm)
● HSR_2SLD 404Z 외형 및 패널 가공치수 (단위:mm)
※ DIN Rail 사용불가
※ DIN Rail 사용불가
110.0
6.5
50.0
6.5
MC0701KE230807
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea
TEL : +82-32-876-4697
http://www.hanyoungnux.com
5 - 24 V d.c.
4 - 32 V d.c.
Less than 4 ㏀
More than 3 V d.c.
Less than 1.5 V d.c.
Constant-current system : 10 ㎃ (±3)
24 V d.c.
20 - 26 V d.c.
30 V d.c. max
50 ㎃ max
500 mW
2,500 V a.c. (For 1 min at 60 ㎐)
1,000 ㎨, X,Y,Z each axis 3 times
-30 ~ 90 ℃
0 ~ 25 ℃ (But without frostiness)
45 ~ 85 % R.H.
2 level pollution
IP20
Resistive load / Inductive load
IEC 62314
Approx. 1,300 g
131.3
131.3
4.5
131.3
13.85
156.7
156.7
4.5
156.7
13.85
140.1
41.0
99.1
140.1
110.0
41.0
41.0
6.5
50.0
● HSR_
● H
[Unit : mm]
140.1
99.1
99.1

Advertisement

loading

Summary of Contents for HANYOUNG NUX HSR-2SL

  • Page 1 MC0701KE230807 Slim Type HSR-2SL 2-Phase Solid State Relay INSTRUCTION MANUAL HANYOUNGNUX CO.,LTD Thank you for purchasing HANYOUNG product. 28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea Please check whether the product is the exactly same as you ordered. HEAD OFFICE TEL : +82-32-876-4697 Before using the product, please read this instruction manual carefully.