Summary of Contents for Vents HE 500x300-5.1-1

  • Page 1 INSTALLATION INSTRUCTION HE 500x300-5.1-1 HE 700x400-12.0-3 HE 500x300-9.0-3 HE 800x500-24.0-3 HE 600x350-5.1-1 HE 1000x500-24.0-3 HE 600x350-9.0-3 HE 1200x600-24.0-3 HE 600x350-12.0-3 Electric heater...
  • Page 2: Table Of Contents

    CONTENTS Designation key ....................................3 Technical data ....................................3 Heater installation ..................................4 Electrical connections ................................6 Technical maintenance ................................8 Storage and transportation regulations .......................... 9 Manufacturer’s warranty ................................10 Certificate of acceptance ................................11 Seller information ..................................11 Installation certificate ..................................
  • Page 3: Designation Key

    Unit type Number Total power TRIAC Power Total of electric [kW] controller current [A] heating elements [pcs.] HE 500x300-5.1-1 AV02 RP 1500 5.10 RNS -5,1 1/230 22.2 HE 500x300-9.0-3 AV02 RP 2500 RNS-12,0 3/400 13.0 HE 600x350-5.1-1 AV02 RH 1500 5.10...
  • Page 4: Heater Installation

    Unit standard Electric heater Weight [kg] size AV02 HE 500x300-5.1-1 HE 500x300-9.0-3 HE 600x350-5.1-1 HE 600x350-9.0-3 HE 600x350-12.0-3 AV03 HE 600x350-12.0-3 AV03 HE 700x400-12.0-3 AV07 HE 800x500-24.0-3 1000 AV07 HE 1000x500-24.0-3 1280 1000 AV12 HE 1200x600-24.0-3 1410 1200 HEATER INSTALLATION Unscrew the screws and remove the side panel from the heater.
  • Page 5 Remove the cartridge with the heating elements from the heater casing. Fasten the heater casing to the unit with the screws (3). Install the cartridge with heating elements into the casing. Fix the angle (2). Insert the wires into the cable glands and connect them to the terminal block in accordance with the wiring diagram. Install the side panel.
  • Page 6: Electrical Connections

    ELECTRICAL CONNECTIONS For single-phase heaters Supply air duct Automation unit Electric heater ТК90 ТК60 Board Power 230 VAC 50 Hz GN_YE GN_YE Power 230 VAC 50 Hz For three-phase heaters Supply air duct Automation unit Electric heater ТК90 ТК60 Board Power 400 VAC 50 Hz...
  • Page 7 The electric heater has two built-in thermal contacts for overheating protection: TK60 with an actuation temperature of +60 °C with automatic restart and TK90 with an actuation temperature of +90 °C with a manual restart. To restart the TK 90 thermal contact, remove the cartridge with heating elements from the heater casing and press the restart button on the thermal contact.
  • Page 8: Technical Maintenance

    TECHNICAL MAINTENANCE During the operation of the air handling unit, when the heater does not work, dust may settle on the heating elements. When the heater is turned on, heavy contamination can cause the smell of burning dust or even cause a fire. Regularly (annually) and before the heating season, check the condition of electrical connections, heating elements and their contamination level.
  • Page 9: Storage And Transportation Regulations

    STORAGE AND TRANSPORTATION REGULATIONS • Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5...+40 ˚С and relative humidity up to 70 %. • Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
  • Page 10: Manufacturer's Warranty

    MANUFACTURER’S WARRANTY The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC.
  • Page 11: Certificate Of Acceptance

    CERTIFICATE OF ACCEPTANCE Unit Type Electric heater Model HE __ ___x___-__-__ A__ Serial Number Manufacture Date Quality Inspector’s Stamp SELLER INFORMATION Seller Address Phone Number E-mail Purchase Date This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.