LG ZPLT1A51A Installation Manual page 17

Drain pan heater

Advertisement

Step 4
4. Unroll the flexible heater element and form it to the geometric shape shown in the figure below. Heater must be formed and the ends
extended through the bottom knockouts to the inside of the outdoor unit.
• Six inches from each end of the element are not heated.
• Minimum heater bend radii are 1 inch.
Figure 8: Form heater element and extend ends through the knockouts at bottom of ODU (6.0 Ton).
Attach the heater element using
the clamps (10 places) and
self-drilling screws provided.
Hex Head drilling screws for metal.
High-strength 410 stainless steel,
#8 size, 1/2" long.
Turn off power to outdoor unit before installation.
Electric shock can cause physical injury or death.
Do not puncture the outdoor unit coil or other interior components when drilling holes for the screws.
If there is a hole in the outdoor unit coil, there is a risk of refrigerant leak. Exposure to high concentration levels of refrigerant gas may lead to
illness or death.
DRAIN PAN HEATER INSTALLATION
6 Ton Multi V 5 ODU bottom view.
Route heater element along the taped path not allowing the element
to have direct, physical contact with the base pan paint surface.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.