MBS UBR-01 Mk II Manual

Universal bacnet router
Hide thumbs Also See for UBR-01 Mk II:

Advertisement

Quick Links

MANUAL
Universal BACnet Router
UBR-01
Mk II
|

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UBR-01 Mk II and is the answer not in the manual?

Questions and answers

Summary of Contents for MBS UBR-01 Mk II

  • Page 1 MANUAL Universal BACnet Router UBR-01 Mk II...
  • Page 2: Table Of Contents

    3 Classification and purpose ........7 4 Features ..............8 5 Specifications and connected loads ....12 6 Installation .............. 14 7 Configuration ............17 8 Reset ............... 45 9 Product support ........... 46 MBS UBR-01 | Mk II Inhalt 2 von 46...
  • Page 3: Introduction

    Limitation of liability All information and notes in this manual were compiled taking the applicable standards and regulations, best engineering practice and the manufacturer's extensive knowledge and experience into consideration. MBS UBR-01 | Mk II Introduction 3 von 46...
  • Page 4 The device is intended exclusively for coupling networks in building Intended use and industrial automation, with the connection values specified in the technical data. Notice This manual is part of the product and must remain with the end customer. MBS UBR-01 | Mk II Introduction 4 von 46...
  • Page 5: Safety

    The configuration of the device may only be carried out by qualified personnel who are familiar with the network configuration! No connection to a network may be established before the device has been completely configured! MBS UBR-01 | Mk II Safety 5 von 46...
  • Page 6 Notice Operation of this device may cause radio interference in residential areas. In this case, the operator may be required to take appropriate measures and to pay for them (EN 55032). MBS UBR-01 | Mk II Safety 6 von 46...
  • Page 7: Classification And Purpose

    2 PC with projecting software or building control system 3 RS485 (two-wire network) 4 DDC automation station 5 MBS universal BACnet router 6 DDC automation station 7 Field device, e.g. pump MBS UBR-01 | Mk II Classification and purpose 7 von 46...
  • Page 8: Features

    9,600 / 19,200 / 38,400 / 57,600 / 76,800 / 115,200. The bus terminating resistor and the network bias resistors can be activated via the DIP switch. The RS485 interface (BACnet MS/TP) is potential-free. MBS UBR-01 | Mk II Features 8 von 46...
  • Page 9 This new topology greatly simplifies configuration, commissioning and management. At the same time, BBMDs and their configuration become obsolete. MBS UBR-01 | Mk II Features 9 von 46...
  • Page 10 The certification and registration authorities responsible for the internet in connection with public key infrastructures are not specified in BACnet/SC. This means building automation operators can take account of their individual network structures. MBS UBR-01 | Mk II Features 10 von 46...
  • Page 11 The advantage of this is that the existing system can always communicate with the new BACnet/SC devices via appropriate routers. Notice The configuration of BACnet/SC connections is described in this document under BACnet settings (page 32). MBS UBR-01 | Mk II Features 11 von 46...
  • Page 12: Specifications And Connected Loads

    10/100 Mbit, TP RJ45 socket MS/TP 4-pole Weidmüller socket with the connections: B(+), A(-), SGND (Signal Ground), SHLD (cable shield) LED TX and RX to display sending and receiving data MBS UBR-01 | Mk II Specifications and connected loads 12 von 46...
  • Page 13 Operation of this device may cause radio interference in residential areas. In this case, the operator may be required to take appropriate measures and to pay for them (EN 55032). MBS UBR-01 | Mk II Specifications and connected loads 13 von 46...
  • Page 14: Installation

    MS/TP RS485 Shld Shielding SGND Signal ground Inverted wire Non-inverted wire GND, ground Supply voltage 12-24 V, DC or AC, PELV LAN Ethernet RJ45 5.1 LED 10/100 Mbit/s 5.2 LED Link/Activity Reset MBS UBR-01 | Mk II Installation 14 von 46...
  • Page 15 Connecting cables should be unplugged during disassembly, to avoid damage. Power connection The device is exclusively operated with protective extra low voltage (PELV). The permissible voltage range must be taken from chapter 5 Specifications and connected loads. MBS UBR-01 | Mk II Installation 15 von 46...
  • Page 16 S3 provides a switchable 120 Ohm terminating resistor that terminates the end of a segment in an MS/TP network. Termination may only be done when the device is at the end of such a network segment. MBS UBR-01 | Mk II Installation 16 von 46...
  • Page 17: Configuration

    To call up the configuration interface, the following address is entered: http://169.254.0.1 or https://169.254.0.1 To log in to the web server for the first time, the user name and the preset password must be entered. MBS UBR-01 | Mk II Configuration 17 von 46...
  • Page 18 Passwords can be reset only if the SSH option has been enabled before. HTTPS For a connection via https (Hypertext Transfer Protocol Secure), the device has its own security certificate when delivered. MBS UBR-01 | Mk II Configuration 18 von 46...
  • Page 19 Menu structure The menu structure of the web server is described in this manual in the categories GENERAL / BACNET / DIAGNOSTICS / HELP. These categories are structured into their corresponding subitems. MBS UBR-01 | Mk II Configuration 19 von 46...
  • Page 20 Type: Device type Name: Designation Location: Installation location Description: e.g. Universal BACnet Router System start: last system start CPU load: current CPU load Free system memory: free / occupied in MByte MBS UBR-01 | Mk II Configuration 20 von 46...
  • Page 21 Contact person 2: Free text, Name of person(s) Image (exactly 80x160 pixels), for person or logo Show on login: Shows the above information already in the login screen. Images are not shown. MBS UBR-01 | Mk II Configuration 21 von 46...
  • Page 22 IP addresses for nameservers for name resolution (DHCP) Nameserver 2: Services Web server access: communication via: http (port 80) unencrypted; https (port443) encrypted; or both. enable ssh access: SSH access (encryption) on/off MBS UBR-01 | Mk II Configuration 22 von 46...
  • Page 23 NTP time synchronization NTP Server receives the time information from the registered NTP server Evaluate BACnet The device listens to sent BACnet messages for time synchronization time synchronization and processes them adequately. MBS UBR-01 | Mk II Configuration 23 von 46...
  • Page 24 Diagnostics – Statistics Routing Diagnostics – Statistics Datalink Diagnostics – MS/TP devices Diagnostics – Packet logging Diagnostics – WSSC connections HELP – Info about HELP – BACnet PICS HELP – System – Logfiles MBS UBR-01 | Mk II Configuration 24 von 46...
  • Page 25 With this button the password of the respective user can be changed. Automatic login as guest Calling the WEB server always leads automatically to the account guest. Only after logging out as guest, another user can be selected. MBS UBR-01 | Mk II Configuration 25 von 46...
  • Page 26 ATTENTION: If you restore the backup archive, the current configuration will be lost. Do you really wan't to restore the archive? Press <Start> to begin the process. The device then automatically performs a restart. MBS UBR-01 | Mk II Configuration 26 von 46...
  • Page 27 The device will not transfer any data for a few minutes afterwards. The configuration is completely retained. The device cannot perform its function in the network during the restart. The web server cannot be reached during the restart. MBS UBR-01 | Mk II Configuration 27 von 46...
  • Page 28 BACnet MS/TP are specified. Non default configuration Users can freely configure the number and type of data links. Hinweis BACnet/SC is configured in the router mode "no default configuration". MBS UBR-01 | Mk II Configuration 28 von 46...
  • Page 29 Sets the IP mode of the router for this datalink. Normal: Default operating mode for a BACnet IP datalink. BBMD: Operating mode as "BACnet Broadcast Management Device". Foreign Device Operating mode as "Foreign Device". MBS UBR-01 | Mk II Configuration 29 von 46...
  • Page 30 (1...127). Default value is 1. Token timeout Minimum amount of time without a “Data Available” or “Receive Error” event, that a node must wait for a remote node to use a MBS UBR-01 | Mk II Configuration 30 von 46...
  • Page 31 MS/TP slave devices. The slave proxy option allows other BACnet devices to find the connected MS/TP slave devices in the network without having to configure the slave addresses in each device individually. MBS UBR-01 | Mk II Configuration 31 von 46...
  • Page 32 "Non default operation". Notice The properties of the data connection ‘mstp’ are called up with the edit button. The link type is set there to "Secure Connection". MBS UBR-01 | Mk II Configuration 32 von 46...
  • Page 33 Alive check interval: Default 300 seconds Connect timeout: Default 5 seconds Reconnect delay: Default 5 seconds Reconnect retries: Default 5 URI Cache timeout Default 3600 seconds Use websocket Ping Enable Websocket Ping MBS UBR-01 | Mk II Configuration 33 von 46...
  • Page 34 Server checks Verification of client certificates is enabled. client cert.: Security Level Accept SSL v2 connections Accept SSL v3 connections Accept TLS 1.0 connections Accept TLS 1.1 connections Accept TLS 1.2 connections MBS UBR-01 | Mk II Configuration 34 von 46...
  • Page 35 IP address is due to a restriction in the BACnet network layer, which only allows addresses with a maximum length of 8 bytes. But since BACnet/SC should also work for IPv6 (with 16 byte addresses), virtual VMACs are used. MBS UBR-01 | Mk II Configuration 35 von 46...
  • Page 36 (alive check). Direct connection Virtual MAC address: configurations: z. B.: „d728ae328d3b“ Allow connection: Switch this defined connection on or off. Maximum idle count: see “Direct Connection idle count” MBS UBR-01 | Mk II Configuration 36 von 46...
  • Page 37 Unique name of the device manufacturer Model-Name: Type designation Firmware-Revision: Firmware version of the device software Maximum telegram size in Byte. APDU Max-Length- Possible are: 50, 206, 480, 1024 und Accepted: 1476 Byte. MBS UBR-01 | Mk II Configuration 37 von 46...
  • Page 38 Value determines after which period of time an acknowledgment-requiring, segmented APDU Segment- telegram is evaluated as failed, if the Timeout: segment confirmation is missing. Default value is 2,000 milliseconds. MBS UBR-01 | Mk II Configuration 38 von 46...
  • Page 39 Counts itemized by APDU type Confirmed service Counts of confirmed services, itemized by counts service. Unconfirmed service Counts of unconfirmed services itemized by counts service. Object type counts Count itemized by object type. MBS UBR-01 | Mk II Configuration 39 von 46...
  • Page 40 Information for Max-Master of the MS/TP bus device. Max-Info Frames Information about the Max-Info frames of the MS/TP bus device. Protocol-Revision Information on the implemented BACnet protocol revision of the MS/TP bus device. MBS UBR-01 | Mk II Configuration 40 von 46...
  • Page 41 BACnet/SC connections, divided into the following connection types: Incoming direct connections Incoming hub connections Outgoing connections Primary hub connection Failover hub connection The following parameters are displayed: Port-Id Connection-state Connection-attempts Connection-time MBS UBR-01 | Mk II Configuration 41 von 46...
  • Page 42 Peer address UUID VMAC Supported BVLC bytes Supported NPDU bytes Sent frames Received frames Bad frames Bad replies MBS UBR-01 | Mk II Configuration 42 von 46...
  • Page 43 Status of the last update Logfiles Allows log files to be recorded. <Start for 60 sec.> Starts recording for 60 seconds. <Stop> Stops the recording. <Show history log> Lists the captured log entries. MBS UBR-01 | Mk II Configuration 43 von 46...
  • Page 44 8.3% nice 83.3% idle 0.0% io Example 0.0% irq 0.0% softirq Load average: 0.00 0.00 0.00 Laufende Prozesse (Beispiel) PPID USER STAT %MEM %CPU COMMAND nobody 1468 16.6 top -b -n1 MBS UBR-01 | Mk II Configuration 44 von 46...
  • Page 45: Reset

    Notice When resetting to factory settings, all previous configurations are lost. Passwords are NOT reset. Soft-Reset This reset is executed via the configuration interface under GENERAL / Restart. See chapter Configuration. MBS UBR-01 | Mk II Reset 45 von 46...
  • Page 46: Product Support

    47809 Krefeld Germany Telephone +49 21 51 72 94-0 +49 21 51 72 94-50 E-Mail support@mbs-solutions.de Internet www.mbs-solutions.de wiki.mbs-software.info Monday to Friday: 8:30 to 12:00 Service times 13:00 to 17:00 MBS UBR-01 | Mk II Product support 46 von 46...