Universal Measuring Device UMG 96L Operating Instructions Brief instructions see last page Supply Mean value Programming mode Sum measurement Phase to phase Password Voltage transformer Current transformer Peak value Minimum value Key 1 Key 2 Janitza electronics GmbH Vor dem Polstück 1 D-35633 Lahnau Support Tel.
Table of contents Uncertainty of measurement The meaning of symbols Configuration data Hints for the user Declaration of conformity Receipt control Safety guidelines Contents of delivery Test voltage Hints for maintenance EMC requirements Service Technical data Product description Ambient conditions Intended use Measurement Functional description...
Attention! If a UMG 96L is installed in panels of metal, the panel must be earthed. This manual also describes options, which have not been delivered and do not belong to the contents of delivery.
Hints for maintenance Service If there are questions, which are not described Before delivery the device is tested in various in this manual, please contact us directly. safety checks and marked with a seal. If the For an efficient handling we need the following device is opened, these checks must be re- information: peated.
Due to the high resistance against interference, one second are safely recognized. the UMG 96L is suitable for continous and un- For each random test one period is scanned. supervised operation. From those sampled values the microproces- sor calculates the electric quantities.
UMG 96L via a separation (switch or power switch) and an overcurrent protection - The switch has to be near the instrument and (2-10A) within the building installation.The con-...
Page 7
The minimum working current is 20mA. At short circuited or open current measurement input, Attention! the UMG 96L can indicate a small current. This The program allows current and voltage current is within the range of the allowed meas- transformer ratio setting only, if the maxi- urement inaccuracy.
Connecting options UMG96L UMG96L Voltage Measure- Current Voltage Measure- Current ment measurement ment measurement see type plate 0,02 .. 5A see type plate 0,02 .. 5A 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 L1 L2 L3 N 1k 1l 2k 2l 3k 3l...
Page 9
UMG96L Voltage Measure- Current ment measurement see type plate 0,02 .. 5A 1 2 3 4 5 6 7 8 9 10 L1 L2 L3 N 1k 1l 2k 2l 3k 3l ../5(1)A ../5(1)A ../5(1)A Diagr.: Connection example 7 Measurement in IT networks via three current transformers.
Putting into service Attach measuring and operating voltage The putting into service of the UMG 96L should The allowed measuring and operating voltage be carried out as follows: of UMG 96L is indicated on the type plate. Installation The UMG96L is designed for mounting in low...
The appar- ent power of this phase at UMG 96L must be indicated by zero. Spannungsmessung If the apparent power is indicated correctly, but Voltage Measurement the real power has a „-“...
Elimination of errors Reason Elimination Error Display dark. Prefuse released. Insert fuse. Device defective. Send the device to the producer for repair. Measured value can- The indication has been de- Add the required measured value indica- not be called up. leted from measured value se- tion to the measured value selection.
Error messages While exceeding an allowed measured value A = Current path range, the UMG 96L indicates the error mes- V = Voltage path sage „Err“. Hz = Frequency An exceeding of a measured value range arises, if at least one of the three existing cur- rent or voltage inputs or the frequency is out of the specified measuring range.
Usage and indication Programming mode The usage of the UMG96L is carried out via the keys one and two. Measured values and pro- gramming data are indicated on the liquid crys- tal display. You must distinguish between ϕ ϕ ϕ ϕ ϕ MkWh MkVArh Indication mode and...
Key functions Programming mode Password Indication mode simultaneous simultaneous Measured Program- values ming menu Program- Measured ming menu values Measured Program- Measured values ming menu values long short Program- Confirm selection ming menu short digit +1 long digit -1 short value *10 (decimal point to the right) flashing...
Page 16
Table, measured value indication Measured values Maximum values Minimum values L1-N Voltage L1-N Voltage L1-N Voltage L2-N Voltage L2-N Voltage L2-N Voltage L3-N Voltage L3-N Voltage L3-N Voltage Measured values Maximum values Minimum values L1-L2 Voltage L1 Real power L1 Real power L2-L3 Voltage L2 Real power L2 Real power...
Page 17
Measured values Mean values Max. values (ind) L1 Reactive power L1 Reactive power L1 Reac. power L2 Reactive power L2 Reactive power L2 Reac. power L3 Reactive power L3 Reactive power L3 Reac. power Measured value Max. value (ind) Mean value reactive power reactive power reactive power...
Current transformer Current transformers with either 1A or 5A sec- Primary (5.00kA = 5000A) ondary can be connected to the UMG96L. A transformer ratio of 5A/5A is preset by the manufacturer. In programming mode the cur- rent transformer setting is marked by the sym- bol „CT“.
Voltage transformer Primary voltage The phase to phase voltage (L-L) is indicated on display of the UMG 96L as secondary and primary voltage. The transformer ratio is calcu- lated from the programmed primary and sec- ondary voltage. In programming mode, the vol- tage transformer settings are marked by the symbol „VT“.
Averaging times Method of taking the mean A mean value is calculated for the most at the The used exponential method reaches at least current and power values. A common averag- 95% of the measured value after the set aver- ing time for the current measured values L1, aging time.
Measured value rotation time Measured value indication Both methods are available simultaneously. Once in a second all measured values are cal- The measured value rotation is programmed, if culated and can be indicated on the display. at least one measured value indication and one Two methods are available for calling up the measured value rotation time bigger than 0 measured value indications (see table 1).
Measured value selection All measured values stated in table 1 (see page 16 and 17) can either be displayed via keep 1 and 2 measured value selection or automati- cally measured value rotation. All measured values for the measured value selection are preset by the manufakturer.
Delete minimum and maximum values In programming mode, „Deletion of minimum and maximum values“ is marked by arrows up- wards and downwards. All minimum and maxi- mum values will be deleted simultaneously in menu „Deletion of minimum and maximum val- ues“.
Working hours counter The working hours counter detects the time, in which the UMG96L measures and indicates data. The time is measured with a resolution of 15 minutes and is indicated in hours. The work- ing hours counter cannot be deleted. Display example: The UMG96L indicates 40201 working hours.
Software Release The internal software of the UMG96L will be improved and extended continuously. The soft- ware update is registered in the device by a specific number the so called software release. The software release cannot be changed by the user.
Uncertainty of measurement Quantity Indicating range Measuring range Measurement uncertainly Auxiliary voltage 196..255V Voltage L-N 0 .. 34kV 50 .. 255V +-1,5% rng Voltage L-L 0 .. 60kV 87 .. 442V +-2,0% rng Current 0,00 .. 9,99kA 0,02 .. 6,00A +-1,0% rng Current in N 0,00 ..
Page 27
These specifications presuppose a yearly calibration and a warm up time of 10 minutes. Used abbreviations: = of measuring range = of measured value Measuring range with scale factor = 1, (Current tranformer = 5/5A, 1/1A) ) In the range of -10..18°C and 28..55°C, an additional error of +-0,5‰ of measured value has to be considered per K.
Declaration of conformity The UMG96L fulfills the protection guidelines of: Guideline 89/336/EWG in combination with DIN EN61326 (2002-03) as well as Guideline 73/23/EWG and 93/68/EWG in combination with EN 61010-1 (2002-08) Safety guidelines Safety requirements for electrical equipment for measurement, control, and laboratory use Part1: General requirements : EN61010-1:2001, IEC 61010-1:2001 Test voltage...
Page 30
Technical data Weight : 250g Calorific value : 2,2MJ (610Wh) Ambient conditions Measurement category : III (Measurement within building installation) Pollution degree Protection class : II = with protective earth Ambient temperature : -10°C .. +55°C Storage temperature : -25°C .. +70°C Humidity : 15% up to 95% without dew Protection class...
Page 32
Brief instructions Change current transformer ratio Programming mode Shift to programming mode If you are in the indication mode please press the keys 1 and 2 simultaneously for approx. 1 second. Now you reach pro- gramming mode. The symbols for programming mode PRG and for the current transformer CT appear.