Hitachi RAK-25PEDC Installation Manual
Hitachi RAK-25PEDC Installation Manual

Hitachi RAK-25PEDC Installation Manual

Split-unit air conditioner
Hide thumbs Also See for RAK-25PEDC:

Advertisement

Quick Links

FOR SERVICE PERSONNEL ONLY
EN
1
RAK-18PED/RAC-18WED
RAK-25PEDC/RAC-25WED
RAK-25PED/RAC-25WED RAK-35PEDC/RAC-35WED
RAK-35PED/RAC-35WED
RAK-50PEDC/RAC-50WED
R32
RAK-50PED/RAC-50WED
SAFETY PRECAUTION
This appliance is filled with R32.
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION
.......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
Be sure to use the specified piping set for R410A, R32. Otherwise, this may result in broken copper pipes or faults.
When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R32)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.
Never install a drier to this R32 unit in order to guarantee its lifetime.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.
When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
The electric cables should neither be reworked nor added.
Make sure to use an exclusive circuit breaker.
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
Otherwise, over heating at terminal contact, fire or electric shock might occur.
Make sure that there is no dust on any connected points of electric cables and fix firmly.
Otherwise, fire or electric shock might occur.
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire
if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your fu niture.
An IEC approved power cord should be used. Power cord type: NYM.
1
Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
The draining of the water container inside the Indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Visible outline of the
450mm
indoor unit
445mm
220mm
15mm
123mm
22mm
60mm
85mm
440mm
534mm
780mm
Level
Screw for Hanger
Hanger
Line
Weight
Wall hole
Procedures of Installation and Precautions
Procedures to fix the hanger.
1. Drill holes on wall.
2. Push plug into the holes.
(As shown below)
(As shown below)
Wall
Hanger
Screw
32mm
Wall
Wall Penetration and Installation of Protection Pipe
Drill a ø65mm hole on wall which is
slightly tilted towards the outdoor side.
Indoor
Drill the wall at a small angle.
Cut the protection pipe according to the
wall thickness.
Seal with
Empty gap in the sleeve of protection
putty
pipe should be completely sealed with
putty to avoid dripping of rain water into
the room.
Please ensure smooth flow of water
Protection
when installing the drain hose. Improper
pipe
installing may wet your funiture.
An IEC approved power cord should be
used. Power cord type: NYM.
RAK_RAS_18/25/35/50PEC_IM_English
1
WARNING
CAUTION
2
Installation Of The Indoor Unit
Cutting Low Cover bush
While installing the pipe from the right, left or
bottom side, use a knife to cut openings as
shown in figure. Then smoothen the edges of
openings with a file.
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
123mm
Installation
Insert the pipe through the wall hole.
The upper part of the Indoor unit is hanged on the
32.5mm
hanger.
The projection at the lower part of the Indoor unit is
hooked onto the hanger.
Drain Hose
65mm
80mm
Hanger
Screw the hanger at the
positions possibly near the
upper and lower hooks where
the indoor unit is hung. Use 4 or
Protection
more screws to fix the hanger.
Drain Hose Connecting Cord
Pipe
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap.
3. Fix the hanger on wall with
(This is an easier way to remove the drain
4.1 x 32 screw.
cap).
(As shown in figure below)
Plug
Ceiling
Drain hole
(Procure
locally)
Hexagonal wrench
key (Φ4mm)
Drain hole
WARNING
Outdoor
2-5mm
Be sure that the wire is not
in contact with any metal in
The rubber strap used for fixing the insulator
Seal with
the wall. Please use the
should not be tied with great force. Otherwise,
putty
protection pipe as wire
this will damage heat insulation and causes
passing through the hollow
water condensation.
part of the wall so as to
Please pull the lower part of the Indoor unit
prevent the possibility of
outwards to check if the unit is hooked onto
WALL
damaged by mouse.
the hanger. Improper installation may cause
Sleeve of
Unless it seals completely,
vibration and noise.
protection
any air with high humidity
Transform the piping while holding down the
pipe
flows from outdoor and any
lower portion of pipe-support by hand.
dew may drop.
THE CHOICE OF MOUNTING SITE
WARNING
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air
R410A R32)
outlet is allowed.
The clearance distances from top, right and left are
specified in figure below.
The location must be convenient for water drainage and
pipe connection with the Outdoor unit.
To avoid interference from noise, please place the unit and
its remote controller at least 1m from the radio and
television.
To avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
The installation height should be at least 2300 mm or more
from the floor.
Names of Indoor Components
No.
Item
Qty
Hanger
1
Screw for Hanger
2
AAA size Battery
3
Screw for holder of
Remote Controller
4
Remote Controller
L.H
5
Insulation sheet
6
Drain Pipe
7
Bush
8
(RAC-50WED)
Binding band
9
The component of
The component of
7
8
is included in
is included
the package of the outdoor unit.
the package of the outdoor unit.
r
Openings
Connecting cords, pipe and
drain hose must be laid
together with Vinyl tape.
Wall hole
Cable
Hanger
Drain layout of
Lift the body
backward piping
Refrigerating
of the unit
Pipe
upwards and
then force it
downwards.
Projection
CAUTION
Insufficient insert may
result in water leakage.
Push the pipe deeply until the insulating
Drain cap
Drain Hose
section of the drain hose end gets over
the rib at the indoor unit side.
Remove low cover
Insert drain cap up to the
location securely till the cap stops.
Please use hexagonal wrench key( Φ 4mm) to insert the drain cap.
Hexagonal wrench
(This is an easier way to install the drain cap.)
key (Φ4mm)
CAUTION
Pipe
Rubber strap tied
with great force
Pipe
support
Transform after
bending downward.
(Please note the following matters and obtain permission from customer before installation.)
The Outdoor unit must be mounted at a location which can
support heavy weight. Otherwise, noise and vibration will
increase.
Selecting the installation location: Suitable location that
will reduce the impact from rain and direct sun that may
affect the unit performance.
Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to
animals or plants.
The clearances of the unit from top, left, right and front are
specified in figure below. At least there of the above sides
must be open air.
Be sure that the hot air blown out of the unit and noise do
not disturb the neighbourhood.
Do not install at a location where there is flammable gas,
steam, oil and smoke.
The location must be convenient for water drainage.
Place the Outdoor unit and its connecting cord at least 1 m
away from the antenna or signal line of television, radio or
telephone. This is to avoid noise interference.
Direction of Piping
Backward piping
Figure showing the Installation
from left
of Indoor and Outdoor Unit.
Connection
There are 6 directions allowed,
namely,
backward
piping,
backward piping from left,
above 50mm
horizontally piping from right,
horizontally piping from left,
Be sure to
vertically down from right, vertically
completely
down from left.
seal any gap
with putty.
Dimension of Mounting
Stand of the Outdoor unit
(unit : mm)
Mounting
RAC-18/25/35WED
Stand
50
12
34
500
80
660
RAC-50WED
Mounting
Stand
57
12
39
500
146
792
above 200mm
The clearances of the
unit from top, left, right
and front are specified
in figure below. At least
three of the above sides
must be open air.
above 100mm
above 300mm
For outdoor unit installation, allow at least
2 sides of space around the unit to ensure
ventilation flue.
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
The refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further
connection.
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing low
Openings
cover.
(Refer to "CONNECTION OF POWER CORD")
After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to
hold them tight.
Be sure to cut the extra binding band.
(Otherwise, it may result in abnormal noise or dewfall.)
THE CONNECTION OF REFRIGERATING PIPE DURING
THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
Pipe
transform and are attached.
Drain hose
Please bend at a small
Installation
radius to form an arc
Hang the indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
Wall hole
Refrigerating
Pipe
pipe
Pull this to the front during the
Drain
connection of refrigerating
Cable
hose
Heat
pipe to ease task.
Drain layout of
insulation pipe
Connecting
backward piping
cord
from left
3
Heat Insulation and Finish of the Piping
The connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
Do not tie the terminals with the tape too tight.
If any clearance or over-tightening may cause
condensation.
Please tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of
Indoor and Outdoor units.
To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the
drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
4
Installation of Drain Hose
Ditch
Condensed
water pond
Bending upwards Condensed water
pond
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
CAUTION
unit during installation. (Careless may result in water leakage.)
WARNING
CAUTION
above
50mm
2
1
above 50mm
2300 mm or more
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)
The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 10m.
The connecting pipe, no matter
above 50mm
big or small, should all be
give clearance
insulated with insulation pipe and
as wide as
then wrapped with vinyl tape.
possible
(The insulator will deteriorate if
it is not wrapped with tape).
above
The connection of insulated drain
200mm
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
Drain hose
Connecting cord
Pipe
Binding band
9
Binding band can be
installed to whichever
side of the installation
Insulation pipe (must be
points. However, it is
wrapped with
vinyl tape
recommended to attach
at every 120 mm)
it on the right side
viewing from the rear.
The end of the refrigerating pipes are at
locations marked with " " symbol.
below
5mm
Projection
Hook
about 15cm
Protection
pipe
Drain
hose
Connected
Connecting cord
section
Insulation material for pipe
connection
Sleeve of
protection pipe
Putty
Putty
CAUTION
Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.

Advertisement

loading

Summary of Contents for Hitachi RAK-25PEDC

  • Page 1 R410A R32) will reduce the impact from rain and direct sun that may outlet is allowed. RAK-18PED/RAC-18WED RAK-25PEDC/RAC-25WED affect the unit performance. The clearance distances from top, right and left are Besides, ventilation must be good and clear of obstruction.
  • Page 2 Preparation of Pipe Please mount the Outdoor unit of stable ground to prevent vibration and increase Remove of Air From The Pipe And Gas Leakage Inspection of noise level. Use a pipe cutter to cut the copper pipe and remove burr. Decide the location for piping after sorting out the different types of pipe available.