Hydraulic Connections; Hydraulic Circuit Diagram; Pressure Variator - Riello RLS 1300/EV C11 Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner
Table of Contents

Advertisement

5.12.3 Hydraulic connections

 Make sure that the flexible hoses to the pump
supply and return line are installed correctly.
CAUTION
Follow the instructions below:
 Tighten the flexible hoses with the supplied
gaskets.
 Take care that the hoses are not stretched or
WARNING
twisted during installation.
 Place the pipes so that they are not crushed
or are in contact with hot parts of the boiler
and so it is possible to open the burner.
 Finally, connect the other end of the flexible
hoses to the suction and return pipes.

5.12.4 Hydraulic circuit diagram

Key (Fig. 21)
1
Pump suction
2
Pump return line and nozzle return line
3
Pump pressure regulator
4
Delivery safety valve
5
Delivery safety valve
6
Nozzle delivery line
7
Nozzle without interception rod
8
Nozzle return line
9
Pressure variator on nozzle return line
10 Pressure variator servomotor
11 Pressure switch on nozzle return line
12 Safety valve on nozzle return line
13 Safety valve on nozzle return line
14 Pressure switch on pump delivery line
M
Pressure gauges
V
Vacuometer connection
TEST
Pre-purging phase:
valves 4), 5), 12) and 13) closed.
Ignition and operation phase:
valves 4), 4), 12) and 13) open.
Stop: All valves closed.

5.12.5 Pressure variator

The pressure variator (Fig. 22), allows the pressure on the return
line of the nozzle to be varied according to the required output.
The pressure on the return line is adjusted by varying a section
by means of the rotation of the servomotor 23)(Fig. 4), which also
controls the gas butterfly valve at the same time.
 Regulator at 0° (maximum opening) = minimum pressure on
the nozzle return line.
 Regulator at 90° (minimum opening) = maximum pressure
on the nozzle return line.
The servomotor is controlled by the electronic cam 3)(Fig. 5);
thanks to this device, it is possible to set different curves for oil
and gas on the same servomotor (also for the air damper servo-
motor 4)(Fig. 4).
 When adjusting the gas, it is recommended the servomotor
be adjusted to about 90° to reduce leaks from the gas butter-
fly valve.
 When adjusting the oil, the adjustment is done based on
the nozzle fitted and on the required degree of modulation;
in a situation of minimum firing rate, a rotation of 20° can be
enough.
Installation
13
12
3
1
2
V
Key (Fig. 22)
1
Nozzle return pressure gauge
2
Position indicator (0 ÷ 90) of the pressure variator
3
Maximum oil pressure switch on return circuit
20125166
23
GB
8
10
11
M
P
M
9
4
5
14
P
1
2
3
7
6
20124121
Fig. 21
Fig. 22
20124030

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls001t2

Table of Contents