Trane A4AC3018D Installation And Operation Manual page 36

Condensing units
Table of Contents

Advertisement

520
INDOOR ENTERING
WET BULB CURVES
470
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
420
370
(4)
320
270
220
170
40
170
INDOOR ENTERING
165
WET BULB CURVES
TOP TO BOTTOM
160
71, 67, 63 AND 59 DEG F.
155
150
145
(5)
140
135
130
125
120
115
110
40
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) LIQUID PRESSURE @ 600 CFM IS 305 PSIG
(5) SUCTION PRESSURE @ 600 CFM IS 140 PSIG
36
PRESSURE CURVES (Refer below table for models)
(3)
(1)
50
60
70
OUTDOOR TEMPERATURE (Degree F)
(1)
50
60
70
OUTDOOR TEMPERATURE (Degree F)
80
90
100
110
(3)
80
90
100
110
ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
(2)
OD Model
120
A4AC3035D1
A4AC3036D1
71
(2)
67
63
59
120
88-A4AC3001-1J-EN
Cooling
@SCFM
1000
950

Advertisement

Table of Contents
loading

Table of Contents