Infrared Three-Wavelength Flame Detector
Type
Infrared Three-Wavelength Flame Detector
Model
PDCJ001-D
Detection wavelength band
Three wavelength bands between 4.0 μm and 5.0 μm
Detection sensitivity
33 ㎠ Normal Heptane Flame Detection at 60m Front Distance
Horizontal and vertical 90 °(The angle at which the monitoring
Detection viewing angle
distance is 1⁄2 to the front direction)
Rated voltage
24 VDC
Monitoring & Alarming: 15 mA, Testing: 95 mA,
Consumption current
Transmitting: 100 mA plus to the value on the above
Delay time
Approximately 3 seconds (default), Changeable by setting
Indicator light
Red LED
The contamination of the light-receiving window and the
operating status of the internal circuit are checked by the
Test function
pseudo-fire light, and a trouble signal is transmitted in case of
an abnormality
The internal circuit is constantly checked, and if an error
Self-diagnosis function
occurs, a trouble signal is transmitted.
Power supply voltage
When the power supply voltage drops below specified value,
a trouble signal is transmitted.
monitoring function
General purpose terminals: φ0.9 〜 1.6 shielded
communication cable (Recommendation: Heat-resistant
Connection cable
shielded cable)
specifications
Transmission purpose terminals: φ0.9 shielded twisted pair
cable (Recommendation: N-300-SB0.9-1P manufactured
by Nippon Electric Wire & Cable Co., Ltd.)
Operating temperature: −20 to 60℃
Environmental condition
Operating humidity: 0 to less than 100% (RH), No condensation
Aluminum alloy
Main material
Finish
Urethane paint
Dimensions
H118×W118×D84(mm)
Weight
Approximately 1.3 kg
Note) The detector may operate in response to sparks of arc welding.
This product is non-explosion proof. For explosion-proof products, please contact us.
Safety cautions
●For safety purposes, carefully read the instruction manual before use and
properly maintain the system.
●This product is different from the fire detection system defined in the Fire
Service Act.
●This product is a fire detection device. Do not use it for any other purpose.
●The appearance and specifications of this product are subject to change without
notice.
●The color of the product in this brochure may be slightly different from the actual
product color due to printing concerns.
●For maintenance of your important fire detection system, please contact our
authorized distributor.
●The contents of this brochure are correct as of September 2019.
Tel: +81-3-3265-0231 Fax: +81-3-3265-5348
https://www.nohmi.co.jp/english/
Head O ce: 4-7-3 Kudan-Minami, Chiyoda-ku, Tokyo 102-8277, Japan
PAPJ002-R-4L
Dedicated control panel
Type
Dedicated control panel
PAPJ002-R-□L (□:Number of
PAPJ002-R-□L-P (□:Number of
Model
zones) Without battery
zones) With battery
Number of circuits
4 / 8 / 12 zones
Mounting type
Wall mounting, indoor use
Main power supply
100 VAC±10%, 50/60Hz
5 VDC: Microprocessor, IC, display
5 VDC: Microprocessor, IC,
circuit, and switching circuit
Circuit voltage
display circuit, and switching circuit
56 VDC: Battery charging circuit
24 VDC: Others
(Half-wave rectification)
24VDC: Others
Power consumption
21VA (Monitoring), 100 VA (Alarm)
PDCJ001-D, PDCJ002-E
Maximum number
of devices
Infrared Three-Wavelength Flame Detector: 1 unit/circuit
Panel sound
Built-in electronic buzzer (Alarm: Constant, Trouble: Intermittent)
Number of local
alarm circuit
Maximum number of
15 units (10mA/unit in active condition)
local alarm devices
Detector
Manual operation test of the detector
operation test
(by the test switch)
Reset
Reset of detectors and signal-receiving circuits (by the reset switch)
Signal cut-off
Cut-off of alarm and trouble output signals (by the signal cut-off switch)
Alarm silence
Silence of the control panel (by the alarm silence switch)
Silence of the control panel and local audible devices during
Maintenance
alarm silence
the maintenance (by pressing the alarm silence switch 5 seconds)
Local alarm silence
Silence of the local audible devices (by the local alarm silence switch)
Alarm verification release: Alarm notification without verification
Alarm verification
release
(by the alarm verification release switch)
Manual test of the battery
Battery test
(by the aux. power test switch)
Detector line open, Device fault,
Detector line open, Device fault, AC power
Trouble notice
AC power fault, Circuit valtage fault,
fault, Circuit valtage fault, Fuse blown,
function
Fuse blown, Alarm receiving circuit fault
Alarm receiving circuit fault, battery fault
Input (terminal symbol)
Detector monitoring (C, L)
General Alarm: 2 points (Dry A contact, 24VDC/1A)
Signal output
Trouble: 1 point (Dry C contact, 24VDC/1A)
Zone: 2 points (Dry A contact, 24VDC/1A)
Operating temperature: 0〜40℃
Environmental
condition
Operating humidity: 20〜85%(RH), No condensation
560 m (when the cable size is φ0.9),
Maximum cable
length
990 m (when the cable size is φ1.2)
End-of-line resistor
10 kΩ, 1/2 W (Connected to the terminal in the detector)
Main material
Steel plate t1.2
Paint color
White
Weight
4L: 13 kg, 8L: 18 kg, 12L: 19 kg
4L: 15 kg, 8L: 20 kg, 12L: 21 kg
4L:H 550×W 450×D 125(mm)
Dimensions
8L・12L:H 840×W 450×D 145(mm)
● A dedicated control panel for transmission system is also available. Please contact us for details.
190905  D -F-24000YO1
Non-Explosion-Proof-Type
Infrared Three-Wavelength Flame Detector
Hig h sen si tiv ity e yes ca tch fire q u ickly.
PDCJ001-D
FLAME DETECTOR

Advertisement

loading

Summary of Contents for NOHMI PDCJ001-D

  • Page 1 Indicator light Red LED Power consumption 21VA (Monitoring), 100 VA (Alarm) PDCJ001-D, PDCJ002-E The contamination of the light-receiving window and the Maximum number Hig h sen si tiv ity e yes ca tch fire q u ickly. operating status of the internal circuit are checked by the...
  • Page 2 10° Nohmi's infrared three-wavelength flame detector (PDCJ002-E) is designed to detect the presence of fire from the radiant energy produced by 33 ㎠ normal heptane fire tray flames (CO resonance radiation) and flame flicker. The PDCJ002-E quickly detects fire even in places with ventilation flow, external air, or high ceilings where detection is often difficult for the ordinary detectors.