Download Print this page

Samsung MWR-SH11N Installation Manual page 17

Hide thumbs Also See for MWR-SH11N:

Advertisement

Main
Sub
menu
menu
Indoor unit
discharge
2
temperature
setting/
checking 2)*
Fresh duct
indoor unit
discharge
5
3
temperature
setting/
checking 2)*
AHU Indoor
unit discharge
4
temperature
setting/
checking 2)*
View master
1
setting/
checking
7
Mode master
2
indoor unit
setting/
checking
3
1
Status of automatic air volume setting
8
2
3
Automatic air volume voltage setting
1
0
2
Reset
3
1)* Relative temperature means that the wired remote controller only displays the temperature increase or decrease (± 3)
compared to the reference temperature . Reference temperature is determined by other controller's desired temperature
setting .
(Example : DMS set 24 °C (75 °F)  24 °C (75 °F) is reference temperature . Wired remote controller displays it as '0' )
2)* Only the celsius temperature unit is allowed when this function setting and checking in the service mode .
For the fahrenheit temperature, you need temperature conversion before this function setting and checking
by the celsius temperature unit .
3)* When setting the address/option, you can set the target indoor unit by selecting sub menu 1 .
SOL 터치간단유선 유럽향 IM_EN_DB68-08073A-00.indd 17
Function description
Use of discharge
temperature control
Cooling discharge temperature
Heating discharge temperature
Cooling discharge temperature
Heating discharge temperature
Use of discharge
temperature control
Cooling discharge temperature
Heating discharge temperature
Indoor unit view master setting/
checking
Mode master indoor unit
checking
Mode master indoor unit setting
6)*
Automatic air volume operation
Factory setting
Power master reset 8)*
Outdoor units reset
ENGLISH-17
Setting value
Value
Factory default
0 - No use, 1 - Use
0
8~18 °C
15
30~43 °C
38
13~25 °C
18
18~30 °C
25
0 - No use, 1 - Use
0
8~25 °C
15
18~43 °C
38
Indoor unit view
Indoor unit view
master address
master
(Example : 20 02 1F)
Indoor unit master
address (Example :
none
20 02 1F)
0-No use, 1-Use,
none
2-Release 7)*
1
0
1
0
1
2
1
0
1
0
1
0
Page
Save location
01
Indoor unit
02
Indoor unit
03
Indoor unit
Fresh duct
01
indoor unit
Fresh duct
02
indoor unit
01
AHU Indoor unit
02
AHU Indoor unit
03
AHU Indoor unit
01~03
None
01~03
None
01
None
01
Indoor unit
01
Indoor unit
01
Indoor unit
None
None
None
2018-10-11 오후 3:35:07