LCI2 and Router Quick-Start Setup Instructions
SUPERSEDES: New
Overview
This document provides quick-start Ethernet setup instructions for the LCI2 in a typical home network. It explains how to
configure the LCI2 to communicate with PCs on the Internet.
NOTE: You must have a Static IP address from your Internet Service Provider (ISP) to ensure that you will
always be able to contact your LCI.
Many home network connections receive a Dynamic IP address by default. Dynamic IP addresses can be
changed by your ISP at any time. If this happens, you won't be able to reach your LCI over the Internet.
Please contact your ISP to determine and/or change your IP address type.
Configuring the LCI2 for communications on the Internet
The following procedure should be used to configure the LCI2 to communicate to any PC on the Internet. The router refer-
enced in the example is a Linksys brand router; default router addresses and settings may vary based on the router manu-
facturer.
Procedure Part A - Configure the LCI2 IP Address
1.This example assumes that the router has already been installed and connected to the Internet and is functioning
properly. If you are not sure about installing and connecting your router, please contact your router manufacturer for
assistance.
2.Connect the LCI2 to the router using a standard Ethernet cable.
3.Verify that the LCI2 obtained an IP address automatically from the router.
4.Sign-on to the LCI2 using the password.
5.Select Utilities from the Home screen
6.Select Network Setup from the Utilities screen
7.Select Ethernet Settings from the Network Setup screen
8.Verify Enable DHCP is set to "Yes"
9.If it is set to "No," set to "Yes" and Save
10.Verify an IP address has been automatically placed in the following fields: IP address, Subnet mask, Default Gate-
way, Primary DNS, Secondary DNS and External Gateway.
11.Now that the IP addresses have been automatically set, disable DHCP (Set Enable DHCP to "No"). By setting this to
"No," the LCI2 can be always accessed from the Internet using the same IP address.
NOTE TO IT PROFESSIONALS:
DHCP must be turned OFF on the LCI to manually set the IP address
Ensure that there are no IP address conflicts.
Ensure that the IP address assigned fits into the router's static IP address range.
© 2011 Taco Electronic Solutions, Inc.
Application Note
502-002B
EFFECTIVE: March 11, 2011
1

Advertisement

loading

Summary of Contents for Taco Electronic Solutions iWorx LCI2

  • Page 1 DHCP must be turned OFF on the LCI to manually set the IP address Ensure that there are no IP address conflicts. Ensure that the IP address assigned fits into the router's static IP address range. © 2011 Taco Electronic Solutions, Inc.
  • Page 2 To use a computer outside your network to connect to the LCI2 that was configured, launch Internet Explorer if using a Windows PC. Mac users must use Crossover and Internet Explorer for Mac. Type the following in the address line: http://<Public or Outside IP_address_of_router>:11001 502-002B, Effective: March 11, 2011 © 2011 Taco Electronic Solutions, Inc.
  • Page 3 Taco Electronic Solutions, Inc. is a subsidiary of Taco, Inc. Visit our web site at: http://www.taco-hvac.com Printed in the USA iWorx® and iView® are registered trademarks of Taco Electronic Solutions, Inc. © 2011 Taco Electronic Solutions, Inc. LON, LONWORKS, & LONMARK are trademarks of Echelon Corporation...