CONTROL MODULE Digireg evo.018 ® user manual de.elektrodesign.cz User manual Elektrodesign Digireg evo.018 ® version 2022 EN 1.0 Company of Soler & Palau Ventilation Group Digireg evo.018 switchboard Digireg evo.018 IP65 switchboard ® ®...
Icons used as bottoms to adjust unit function ..............22 Additional control module adjustments and functions ............23 Technical support ......................... 24 Unit decommissioning ......................24 Disposal and recycling ......................24 Technical list and registration sheet ................... 25 Warranty claim form ......................26 elektrodesign@elektrodesign.cz de.elektrodesign.cz...
• air temperature – inappropriate use – normal wear and tear of components ELEKTRODESIGN ventilátory s.r.o. reserves – failure to observe the instructions for the right to decide whether warranty repair safety, use and commissioning specified...
The catalog sheet in close cooperation with authorized service Group. Each Digireg module can control one can be found at ELEKTRODESIGN ventilá- technician who is familiar with the controller. piece of air handling equipment (unit) fitted tory s.r.o. website or in ELEKTRODESIGN...
Supply air unit is interconnected dard, as will all the options for adding diffe- with exhaust air unit while both units are rent types of heating and cooling provisions. controlled by controller mounted on user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
2 minutes. Cooling Each unit can be equipped with several types of cooling provisions: Compressor / compressor with inverter Chilled water coil Heat pump with reversible evaporator coil elektrodesign@elektrodesign.cz de.elektrodesign.cz...
Can also be used to reduce indoor humidity by increasing fresh air supply or by reducing the amount of air being recirculated. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
The outdoor temperature sensor must be installed in order for added heating and cooling provisions to work properly. The service technician can set the tempe- rature shift for automatic selection of the Summer/Winter mode by ±5 °C. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
First response is to attempt to warm up water and if water temperature continues to drop, the device is switched off completely. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
AHU box for controlling several units. Also, it is not po- ssible to use a condensing unit dedicated for split systems controlled by combined analogue input for regulating and input for cooling/heating switching. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
Start sequence to modulate dampers to open or close position is delayed by adjustable interval of 30 to 240 seconds. Both dampers must have common source of power supply, combination of 24 VAC and 230 VAC is not possible. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
The control module must be connected to its control board with a SYKFY 2x2x0.5 or equivalent (UTP) data cable. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
Mounting screws (Fig. 2) of the controller on the base in the picture below. Damage of the threads can lead to inco- rrect fastening and damage to the device, responsibility of the installer. Fig. 2 elektrodesign@elektrodesign.cz de.elektrodesign.cz...
Page 15
Default screen for adjusting different values Default screen for adjusting temperature value, fan speed value and access to misce- llaneous items. Setting desired temperature value Setting desired temperature value after clicking on the thermometer icon. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
The “Arrow” icon pointing left will display air temperature and fan speed adjustment screen. Setting for desired air temperature and fan speed. Graphic interpretation of current time intervals together with air temperature se- ttings and fan speed settings. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
The actual restart of AHU is performed by switching the control module OFF and ON. Restart is also possible by switching the AHU main power supply OFF and ON. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
Can be accessed only by entering appropri- ate codes. Password for service access: ....Accessing the service setting gains access Password to lock the display: 8080 to selecting the initial screen display, bloc- king parameters access to unauthorized Display customization password: 1110 personnel etc. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
Supply air unit with hot water heating and mechanical cooling. Active time interval program settings. Supply air and exhaust air unit coupled with electric heating and mechanical coo- ling. Mixing valve and active time interval program settings. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
Page 20
Active time interval program settings. Heat recovery unit with electric heating and mechanical cooling. By-pass damper and mixing air damper with active time program. Heat recovery unit with hot water heating and mechanical cooling. Active time inter- val program. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
Error indication icon. This signal requires intervention from a service tech. (the unit may stop running, depending on the type of error). Icon indicating clogged up filter (does not prevent operation of the unit). user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
Icon for de-activating program based on time interval settings. Button to access program to set time inter- vals and function settings. Button for manual control of mixing damper (access to Bi-valence submenu). Button for language selection. elektrodesign@elektrodesign.cz de.elektrodesign.cz...
5) Blocking access to parameter settings graphical visualization screen. in order to prevent any unauthorized person or unintentional changes to saved settings. 6) Adjusting transition time going from active to inactive screen. user manual Elektrodesign Digireg evo.018 version 2022 EN 1.0 ®...
® Technical support Wide network of S&P‘s technical support technical support office for further assistan- contact any branch of ELEKTRODESIGN teams guarantees sufficient response time ce. Any unauthorized tampering with the ventilátory s.r.o. to find your nearest dealer, with any technical issues. If any faulty issue device will void the warranty.
ČR OLOMOUC BRNO PÍSEK ŽILINA KOŠICE BRATISLAVA HEADQUARTERS de.elektrodesign.cz +420 722 986 995, mvoznak@elektrodesign.cz Boleslavova 15, CZ-140 00 Praha 4 +420 722 990 519, zhakos@elektrodesign.cz CENTRAL WAREHOUSE Company of Soler & Palau Ventilation Group Boleslavská 1420, CZ-250 01 Stará Boleslav...